Delta DVP04DA-S – 4-Channel Analog Output Module

Delta DVP04DA-S provides four 12-bit analog outputs for compatible Delta DVP Slim PLCs. It converts a digital value calculated by the PLC into a voltage or current signal. Typical uses include speed references for drives, proportional valve commands and signals for process recorders. See DVP Slim analog modules for the product family.

Output modes and scaling

Set each channel's range in CR#1. Mode 0 gives 0–10 V, mode 1 gives 2–10 V, mode 2 gives 4–20 mA and mode 3 gives 0–20 mA. The factory setting is H0000, which selects 0–10 V for all four channels. Match the receiving device's analog input range to the selected mode.

The nominal digital command range is 0–4000. With default calibration, commands 0, 2000 and 4000 produce 0, 5 and 10 V in 0–10 V mode or 4, 12 and 20 mA in 4–20 mA mode. Delta specifies 2.5 mV/LSB and 5 µA/LSB for the base ranges. The specified response time is 3 ms × number of channels.

Power supply and terminals

The module requires an external 24 V DC supply. Its supply range is 20.4–28.8 V DC and maximum consumption is 4 W. Use the channel's V+ and COM terminals for voltage or I+ and COM for current. The voltage output requires a load impedance of at least 1 kΩ. The current loop supports a total load of up to 500 Ω.

Optocouplers isolate the analog circuit from the digital circuit. The analog channels share a reference and lack galvanic isolation from one another. Route signal wiring away from power cables and terminate the shield according to Delta's grounding diagram. See Delta DVP PLC files for the terminal layout.

Control registers, software and programming cable

On the expansion bus, TO writes the output modes and values. FROM reads identity and status. CR#6, CR#7, CR#8 and CR#9 hold the commands for CH1 through CH4 respectively. CR#0 returns model code H0089. CR#30 reports errors. The first special module is assigned number 0. If the module order changes, check the module number in the ladder program.

Use WPLSoft or ISPSoft with the supported Slim CPU. For example, the DVP-SS2 CPU's COM1 RS-232 port accepts UC-PRG020-12A for USB or UC-MS020-01A for a native PC serial port. After installing the USB cable driver, select its assigned COM number. Set the COMMGR channel for ISPSoft.

The module’s own RS-485 port provides ASCII or RTU access to control registers in standalone operation. Delta specifies that the module’s RS-485 port is unavailable while the module is connected to the PLC expansion bus.

Related analog modules

DVP02DA-S has two analog outputs. DVP04DA-S2 has four analog outputs and reports model code H0091. Check that code if the existing program identifies the module through CR#0. DVP04DA-SL is a high-speed left-side analog output module. DVP04AD-S provides four analog inputs.

Editor's Note

On a used module, read the -S suffix on the label. Inspect the terminals, the expansion connector and the 24 V supply connections.

Disconnect the machine wiring and measure the supply on the bench. Check the POWER, RUN and ERROR indicators. If the PLC fails to detect the module, check the module number and identity in CR#0.

For the voltage output, measure between V+ and COM with a multimeter. In mode 0, commands 0, 2000 and 4000 should give approximately 0, 5 and 10 V on each channel.

For a current output test, connect a suitable 250 Ω resistor between I+ and COM. In 4–20 mA mode, expect approximately 1, 3 and 5 V across the resistor for the same three commands. This gives each channel the same test load.

If a channel reads incorrectly, check the mode, COM return and load impedance first. Record the existing settings before adjusting GAIN or OFFSET. Confirm what the zero and full-scale commands will do on the machine before connecting the drive.

Related topics

Delta PLC · Delta DVP series · DVP expansion modules · Analog and digital signal differences · Delta DVP PLC PDF files · Second-hand Delta equipment

External references

Delta DVP04DA-S / DVP04DA-S2 Instruction Sheet (DVP-0010330-01, 24 February 2021, wiring and register table on PDF pp. 3–6). Delta PLC/HMI Cable Selection Guide (SS2 connections on PDF p. 18).