Delta DVP06XA-H

Delta DVP06XA-H Analog Input/Output Module

Delta DVP06XA-H is a mixed expansion module developed for DVP-EH systems, providing 4 analog inputs + 2 analog outputs. It is not a PLC CPU; the control program runs in the host CPU. It combines analog input/output functions in one housing. The two outputs are voltage/current analog channels, rather than relay or transistor digital outputs.

The difference between analog and digital inputs matters: this module measures signal magnitude, rather than presence alone. An analog signal is converted into numerical data by the ADC; the CPU’s command becomes a field signal through digital-to-analog conversion.

Input channels, ranges and resolution

CH1–CH4 are four analog input channels. Basic ranges are ±10 V and ±20 mA. With factory conversion characteristics, voltage uses −2000…+2000 raw values and current uses −1000…+1000. One LSB is approximately 5 mV for voltage and 20 µA for current. The manufacturer specifies these paths as 12-bit and 11-bit respectively.

Selecting analog voltage or analog current requires matching wiring and channel mode. Input impedance is at least 200 kΩ for voltage and 250 Ω for current. The ±15 V / ±32 mA absolute limits are not normal measuring ranges.

Do not assume identical scaling for 0–10 V and 4–20 mA. With factory OFFSET/GAIN preserved, voltage input gives 0 V → 0, 5 V → 1000 and 10 V → 2000. Current-input mode 2 maps 4 mA to 0 and 20 mA to 1000; in mode 3, 4 mA gives approximately 200 and 20 mA gives 1000. Engineering-unit conversion must follow the selected characteristic.

Output channels and application limits

CH5–CH6 are two analog outputs. Available modes are 0–10 V, 2–10 V, 4–20 mA and 0–20 mA. The factory command range is 0…4000. In 0–10 V mode, 2000 produces 5 V; in 4–20 mA mode, 0 produces 4 mA and 4000 produces 20 mA. Modified OFFSET/GAIN settings can change these relationships.

Outputs can provide a drive speed reference, controller setpoint or suitable actuator command. If a servo requires a bipolar ±10 V speed/torque reference, the DVP06XA-H’s 0–10 V output cannot provide both command polarities by itself. This is not a pulse/direction motion module either. A PID control calculation can run in the CPU, with its result scaled for the analog output.

Output resolution is 12-bit; one LSB is 2.5 mV on the basic 0–10 V path and 5 µA on the 0–20 mA path. The permitted current-output load is 0–500 Ω. Input and output do not share one raw scale: 10 V corresponds to 2000 at the input and a command of 4000 at the output.

Power supply and field wiring

The external supply is 24 V DC, with a permitted range of 20.4–28.8 V DC. Use shielded analog cables and suitable separation from motors, power cables and other electromagnetic interference sources. Follow the manufacturer’s diagram for AG/FG and grounding connections.

Voltage input uses V+ and COM; current input requires bridging that channel’s V+ and I+ terminals and using the I+/COM connection. Verify terminal positions from the label and wiring diagram. Assess a two-wire transmitter’s supply, current loop and common connection together; an analog current input is not automatically a transmitter power output.

For a pressure sensor or pressure transmitter, verify whether the signal is 0–10 V, 4–20 mA or another type. Pt100 and thermocouple sensors cannot connect directly as temperature sensors. They require suitable converters or dedicated temperature modules. Analog/digital isolation does not mean the analog channels are isolated from one another.

Which software and programming cable are used?

DVP06XA-H does not run a separate PLC program. PLC programming is performed through the host CPU; channel settings and data are handled by FROM/TO instructions. Legacy DVP-EH projects use WPLSoft. Select ISPSoft according to the complete host CPU’s software support; the module name alone does not establish compatibility.

Control registers are accessed from the ladder diagram. For a PC connection to the CPU’s RS-232 programming port, use UC-PRG020-12A USB-to-RS-232 or a suitable UC-MS020-01A serial cable. Confirm the PLC-side mini-DIN connection for the exact CPU. Check the USB cable driver and assigned COM number; use COMMGR where required for ISPSoft. If the CPU has another programming port, select its appropriate cable separately.

Control registers and module addressing

CR#0 identifies the module; DVP06XA-H returns H’0604. Special modules are numbered 0…7 starting nearest the CPU; this is not digital X/Y addressing. For the first special module, FROM K0 K0 D0 K1 reads CR#0 into D0. Module number K0 applies only when it actually occupies that position.

CR#1 holds all four input modes and both output modes in one word: b0…b11 for CH1–CH4, b12…b13 for CH5 and b14…b15 for CH6. Preserve other channels’ bits when changing one channel. CR#2–#5 set input averaging; CR#6–#9 contain averaged input values; CR#12–#15 contain present input values.

CR#10 and CR#11 are the CH5/CH6 output commands. CR#30 reports errors and CR#34 reports module software version. Back up OFFSET/GAIN registers before changing them. The earlier instruction sheet and later shared manual give different averaging-count limits, so match the permitted setting to the actual module version.

Standalone RS-485 operation

The module supports Modbus ASCII and Modbus RTU over RS-485. CR#31 sets the station address; CR#32 controls baud rate/protocol settings. A standalone PC connection requires a suitable USB-to-RS-485 converter and D+/D− wiring. The CPU’s USB-to-RS-232 programming cable is a different interface.

The module’s own RS-485 communication is disabled when it is attached to the CPU expansion bus. Do not design for simultaneous FROM/TO bus access and standalone use of the module’s RS-485 port. Modbus register addressing and local CR numbers must also be distinguished in the communication software.

Editor’s Note

Start by confirming the label reads DVP06XA-H exactly. Connector similarity does not make H2 or H3 the same module. Check CPU compatibility and the existing register layout.

Disconnect field devices and begin with known test signals. Test voltage inputs at 0/5/10 V and current inputs at 4/12/20 mA with the correct loop wiring. Check raw data separately from displayed engineering units.

Prevent connected drives or valves from moving during output tests. Measure voltage outputs in parallel; test current outputs within a suitable loop and load. Do not place an ammeter across a voltage output and create a short circuit.

Do not use calibration to conceal unstable readings. First check supply, the V+/I+ bridge, commons, shielding and CR#30 error information. Excessive averaging can slow the response.

Back up OFFSET/GAIN settings and the CPU program. For H2/H3 replacements, verify exact CPU compatibility and unipolar/bipolar output ranges in the manufacturer’s documentation.

For repair inspection, disconnect power and verify capacitor discharge before examining terminals, the supply and affected analog channel. Complete testing on every channel with suitable loads and controlled power cycles.

Manuals and related models

Use Delta DVP PLC files for wiring and control-register documents. DVP04AD-H provides analog inputs, while DVP04DA-H provides analog outputs. DVP06XA-H2 and DVP06XA-H3 are different generations requiring separate assessment, rather than guaranteed direct replacements.

Navigation: Delta Automation · Delta PLC · DVP PLC series · DVP expansion modules · DVP-H modules · DVP06XA-H main page

External references

DVP06XA-H Instruction Sheet, 2004 English edition · Delta Special Modules Application Manual, 2013 English edition; Chapter 3 · Delta PLC/HMI Cable Selection Guide, English