Delta DVP-F232
Delta DVP-F232 RS-232 Communication Card
Delta DVP-F232 is an RS-232 serial communication card that fits the function card slot of compatible DVP-EH2 and DVP-EH3 CPUs. It connects the PLC to a computer, an operator panel or a compatible serial device. The host CPU generation determines the port number.
EH2 and EH3 port assignments
EH2: On compatible CPUs such as the DVP32EH00R2, the card converts COM2 to RS-232. Installing the card disables the built-in COM2 RS-485 interface. Account for this change when a drive or another device already uses that RS-485 connection.
EH3: On compatible CPUs such as the DVP32EH00R3, the DVP-F232 operates as COM3. The CPU's built-in COM2 RS-485 remains available. On both generations, configure the card port as master or slave to suit the application. See the Delta DVP PLC files for the exact host CPU documentation.
DB9 pins and cable selection
The card uses a male DB9 connector with pin 2 Rx, pin 3 Tx and pin 5 signal GND. For a standard PC serial port, connect card pin 2 to PC pin 3, card pin 3 to PC pin 2, and pin 5 to pin 5. Verify the HMI end against the panel’s own wiring manual. Matching connectors can have different pin assignments.
Delta's EH3 cable guide lists the USB-to-female DB9 connection of the UC-PRG020-12A for a PC on DVP-F232 COM3. For a PC with a native RS-232 port, it lists the UC-PRG030-10A crossed female-to-female DB9 cable. For the built-in COM1 port, use the CPU's own diagram to select a mini-DIN cable such as the UC-MS020-01A.
Programming and first connection
Use WPLSoft or ISPSoft with a supported EH2/EH3 CPU. The application program is stored in the host PLC. Check the computer's COM number separately from the PLC’s COM2 or COM3 assignment. After installing the USB cable driver, select the COM port shown in Windows Device Manager. Set the COMMGR channel for ISPSoft.
Match baud rate, data bits, parity, stop bits and protocol at both ends. Select the correct PLC station address when the protocol uses one. Switch off the CPU and observe electrostatic precautions before installing the card.
Related function cards
DVP-F422 provides RS-422, DVP-F485 provides RS-485 COM3 for EH3, and DVP-FEN01 provides Ethernet for compatible EH3 CPUs. DVP-F2AD and DVP-F2DA add analog inputs and outputs respectively. For the older DVP-F232S, check its own pin diagram, host generation and port assignment. See the differences between RS-232, RS-422 and RS-485 when selecting an interface.
Editor's Note
Read the card label and the complete CPU code together. Confirm whether the existing card is an F232 or an F232S before buying a replacement.
On an EH2 system, record the devices already using COM2. If it carries a drive network, plan the new connection before converting the port to RS-232.
On a used card, inspect the DB9 pins, socket and board connector. Disconnect both ends of the cable and verify conductors 2, 3 and 5 with a multimeter.
Start with a short known good cable and a single connected device. Check the PLC port assignment and PC COM number, then compare the serial settings one by one.
Back up the existing CPU program and serial settings. Verify communication with a read or monitoring session before transferring a program.
Related topics
Delta PLC · Delta DVP series · DVP expansion modules · DVP function cards · Delta DVP PLC PDF files · Second-hand Delta equipment
External references
Delta DVP-EH Function Card Instruction Sheet (DVP-0407730-02, 21 May 2024, DVP-F232 wiring on PDF p. 2). Delta PLC/HMI Cable Selection Guide (EH3 COM3 cables on PDF p. 76). Delta DVP catalogue (EH2 COM2 and EH3 COM3, printed p. 43).