Delta AH08PTG-5A
Delta AH08PTG-5A – 8-Channel RTD Temperature Input Module
The Delta AH08PTG-5A is an 8-channel RTD temperature input module for the Delta AH500 rack. Inputs CH0–CH7 accept 2-, 3- or 4-wire Pt100, Pt1000, Ni100 and Ni1000 sensors. The module sends the measured temperature to the PLC as a digital value. It can monitor several points on a tank, mould or machine from a single rack.
Measurement Range, Power and Conversion Time
The rated input range is −180 to +800 °C for Pt100 and Pt1000 and −80 to +170 °C for Ni100 and Ni1000. A separate 0–300 Ω resistance measurement mode is available. Temperature resolution is 0.1 °C or 0.1 °F and the specified module accuracy is ±1 °C. The module has a removable terminal block and uses a 24 V DC supply (20.4–28.8 V DC).
Quick mode uses one channel from each pair. Conversion takes 20 ms per channel with 2- or 4-wire wiring and 200 ms per channel with 3-wire wiring. In general mode, these times are 200 and 400 ms per channel respectively. In general mode, the conversion times for both channels in a group are added together.
Wiring and ISPSoft Setup
Check the rack and slot in HWCONFIG in ISPSoft. Set each channel’s sensor type, wire configuration and temperature unit. Map the channel fault status to the HMI so the operator can identify a disconnected probe. See section 5.2.9 of the manual for wiring diagrams and section 5.2.11 for setup and monitoring.
For four RTD inputs, see the AH04PT-5A. For thermocouple inputs, see the four-channel AH04TC-5A or eight-channel AH08TC-5A. For process signals such as 0–10 V and 4–20 mA, choose a Delta AH analog input module with the matching input range.
Editor’s Note
When buying a used module, check the AH08PTG-5A nameplate and make sure the removable terminal block comes with it.
On the bench, use a known-good Pt100 to test channels CH0 through CH7 individually.
If the reading is consistently high, check the sensor type and wire setting first. In a 2-wire circuit, lead resistance adds to the reading.
If the reading jumps when a drive starts, check whether the probe cable shares a route with power cables.
Save the HWCONFIG settings before swapping modules. After replacement, check the channel type, filter and sensor-break settings in the monitor.
User Manual and PDF Files
Delta AH500 Module Manual – English PDF. The AH08PTG-5A is covered in section 5.2, starting on printed page 5-38. See the Delta AH PLC PDF files for other documents in the series.
Related Topics
Temperature sensors · Pt100 sensors · What is PID control? · Temperature controllers · Delta PLC software
Delta Automation · Delta PLC · Delta AH PLC series · Delta AH expansion modules · Delta AH temperature and motion modules
External reference · Delta AH500 Module Manual