The inverter restarts automatically, be careful of the machine because it may suddenly restart.
Err1    Frequency point setting error alarm    The frequency setting signals at points 1 and 2 are set too close to each other.    Set the frequency setting signals at points 1 and 2 apart from each other.

Cler    Clear command acceptable    This message is displayed when pressing the STOP key while an error code is displayed.    Press the STOP key again to clear the trip.

H1oFF    Emergency stop command acceptable    The operation panel is used to stop the operation in automatic control or remote control mode.    To cancel the emergency stop, press any other key.

AH    Setting error alarm    An error found in a setting when data is reading or writing.    Check whether the setting is made correctly.

HErrd    Display of first/last data items    The first and last data item in the RUN data group is displayed.    Press MODE key to exit the data group.

db    DC braking    DC braking in progress.    The message goes off in several tens of seconds if no problem occurs. Note 1

Ldb    Flowing out of excess number of digits    The number of digits such as frequencies is more than 4. (The upper digits have a priority.)    Reduce the frequency to be less than 100 Hz.

Stp    Momentary power failure detection and trip stop prohibition function activated    The slowdown stop prohibition function selected with F306 (momentary power failure ride-through operation) is activated.    To restart operation, reset the inverter or input an operation signal again.

tEP    Auto-tune because continuous operation selected    The automatic tune function selected with F65 was activated.    Check the operation. When frequency reaches LL or operation signal is input, normal operation starts.
Iinit    Parameters in the process of initialization    Parameters are being initialized to default values.    Normal if the message disappears after several seconds.

P-01    Points setting alarm 1    In case of P-1, there are same setting value at least two parameters of F190, F192, F193, F194, F195, F196, or F198 beep occurs.    Set the points to different values.

R-02    Points setting alarm 2    In case of P-2, the inclination of V/f is too high.    Set the inclination of V/f to flat.

R-05    Output frequency upper limit    An attempt was made to operate at a frequency higher than 10 times the base frequency (set to F103).    Operate at a frequency within 10 times the base frequency.

R-17    Operation panel key (RUN or STOP key) pressed too long    The RUN or STOP key is held down for more than 20 seconds.    Check the operation panel.

R-28    ST terminal alarm    Slide switch SW2 and parameter F147 settings are different.    Match the settings of SW2 and F147. Power supply OFF and ON after these settings.

Rt    Auto-tuning    Auto-tuning in process.    Normal if the message disappears after a few seconds.

AL5    Break in analog signal cable    The input signal from VIC is below the analog signal detection level set with F633 and setting value of F634 is 1 or more.    Check the cable for breaks. Check the setting of input signal or setting value of F633 and F634.

Fire    In forced operation    F1-F7 and operation frequency is displayed alternately in operation of forced free-speed control.    It is normal as the alarm is gone out after the forced free-speed control operation.

Pr    STOP signal OFF    STOP terminal is in open-circuit.    Close STOP and S-CC circuit.

PAS    Password verification result    After the password setting (F738), the password is read. F739 (password verification).    If the password is correct, PAS is displayed and if it is incorrect, P1 is displayed.
EASy    Switching display of easy setting mode/standard setting mode    The EASy key was pushed in the standard monitor mode.    When F459 is displayed, setting mode becomes easy setting mode. When Std is displayed, it becomes standard setting mode.

SEt    Region setting of SEt mode    A region setting is not input yet. Power supplied to the inverter at first time as checking the region setting parameter SEt is set to 0, inverter return to default setting.    Set a region setting by using setting dial. Refer to section 3.1.

SEt2    Note    SEt is blinking after power supply is on. In this time, the keys are not operated.    SEt parameter SEt is lighting is same as other parameters and is not blinking.
nErr    No trip of past trip    No record of past trip, after past trips were clear.    Normal operation.
- - - -    No detailed information of past trip    The detailed information of past trip is read by pushing the enter of setting dial during blinking nErr = number.    Normal operation. To be returned by pressing MODE key.
Prealarm Display

C    Overcurrent alarm    Same as OC (overcurrent)    Same as OC (overcurrent)
P    Overvoltage alarm    Same as OP (overvoltage)    Same as OP (overvoltage)
l    Overload alarm    Same as OL1 and OL2 (overload)    Same as OL1 and OL2 (overload)
OH    Overheat alarm    Same as OH (overheat)    Same as OH (overheat)
t    Communication alarm    Same as Err5 (communication fault)    Same as Err5 (communication fault)

If two or more problems arise simultaneously, one of the following alarms appears and blinks.

CP, PL, t

The blinking alarms C, P, L, t are displayed in this order from left to right.

+ Toshiba VF-MB1 Catalog (pdf)

+ Toshiba VF-MB1 User manual (ingilizce pdf)

////////////

+ VF-MB1 User manual  

+ VF-MB1 Fault index 

+ VF-MB1 Fault codes 1 >>

+ VF-MB1 Fault codes 2 >>

+ VF-MB1 Fault codes 3 >> 

+ Toshiba VF-MB1 -

+ Toshiba Main page  

++ VFD Main page  

-

"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."  28.06.2013      

Refine Search