Toshiba VF-MB1 VFD Features

The Toshiba VF-MB1 is a compact variable frequency drive designed with a slim body, flexible operation, advanced motor control and extensive programmable functions. Despite its compact size, the series provides PID control, vector control, PM motor control, multiple preset speeds, automatic restart and configurable input/output functions for a wide range of industrial applications.

Control system: Sinusoidal PWM control.

Output voltage range: Adjustable from 50 to 330V for the 240V class and 50 to 660V for the 500V class by correcting the supply voltage.

Output frequency range: 0.1 to 500.0Hz. Default setting: 0.5 to 80Hz. Maximum frequency setting: 30 to 500Hz.

Minimum frequency setting steps: 0.1Hz via analog input when the maximum frequency is 100Hz, and 0.01Hz through the operation panel or communication setting.

Frequency Accuracy

Digital setting: Within ±0.01% of the maximum frequency (-10 to +60°C).
Analog setting: Within ±0.5% of the maximum frequency (25°C ±10°C).

Voltage / frequency characteristics: V/F constant, variable torque, automatic torque boost, vector control, automatic energy-saving, dynamic automatic energy-saving control, PM motor control, 5-point V/F setting and auto-tuning. Base frequency can be adjusted from 20 to 500Hz, torque boost from 0 to 30%, and starting frequency from 0.1 to 10Hz.

Frequency setting signal: Setting dial on the front panel, external frequency potentiometer with a rated impedance of 1k-10kΩ, 0-10Vdc / -10-+10Vdc (input impedance: 30kΩ) and 4-20mAdc input (250Ω input impedance).

Terminal board base frequency: The characteristic can be freely configured using a two-point setting. Adjustable analog inputs: VIA, VIB and VIC.

Frequency jump: Three independent frequency ranges can be configured by setting the jump frequency and its corresponding range.

Upper and lower frequency limits: The upper limit can be set from 0 to the maximum frequency, while the lower limit can be set from 0 to the configured upper-limit frequency.

PWM carrier frequency: Adjustable from 2.0kHz to 16.0kHz. Default setting: 4.0kHz.

PID control: Proportional gain, integral gain, differential gain and control waiting time can be adjusted. The drive can compare the process value with the feedback value for closed-loop control.

Acceleration / deceleration time: Three selectable acceleration/deceleration time settings are available from 0.0 to 3600 seconds. Automatic acceleration/deceleration, S-pattern acceleration/deceleration, forced rapid deceleration and dynamic rapid deceleration functions are also available.

DC Braking

Braking start-up frequency: Adjustable from 0 to the maximum frequency.
Braking rate: 0 to 100%.
Braking time: 0 to 25.5 seconds.

The drive also supports emergency DC braking and motor shaft fixing control.

Dynamic braking drive circuit: The control and drive circuitry is built into the inverter, while the external braking resistor is optional.

Programmable input terminal functions: Approximately 110 functions, including forward/reverse run, jog run, operation base and reset signals, can be selected and assigned to eight input terminals. Input logic can be selected between sink and source.

Programmable output terminal functions: Approximately 150 functions, including upper/lower frequency limits, low-speed detection, specified-speed reached and failure signals, can be assigned to the FL relay output, open-collector output and RY output terminals.

Forward / reverse operation: The RUN and STOP keys on the operation panel can be used for local start and stop operation. Forward/reverse commands can also be controlled through communication or logic inputs on the terminal block.

Jog operation: When jog mode is selected, jog operation can be controlled from the terminal board or a remote keypad.

Preset speed operation: Up to 15 preset speeds can be selected by changing the combination of four contacts on the terminal board together with the frequency references.

Retry operation: The inverter can automatically restart after checking the main circuit elements when a protective function has been activated. Up to 10 retries can be selected by parameter.

Parameter protection / password setting: Parameters can be write-protected, and changes to panel frequency settings or operation-panel functions such as operation, emergency stop and reset can be restricted. Parameter write protection can also be applied using a 4-digit password and terminal input.

Regenerative power ride-through control: During a momentary power failure, the motor can continue running by using its regenerative energy. This function is disabled by default.

Automatic restart operation: Following a momentary power failure, the inverter detects the rotational speed of the coasting motor and outputs a suitable frequency to restart the motor smoothly. This function can also be used when switching to commercial power.

Light-load high-speed operation: Machine operating efficiency can be increased by raising the motor speed when the load is light.

Drooping function: When two or more inverters operate a common load, this function helps prevent the load from concentrating on a single inverter because of imbalance.

Override function: The operating frequency command can be adjusted by an external input signal.

Relay output signal: 1c-contact and 1a-contact outputs. Maximum switching capacity: 250Vac-2A and 30Vdc-2A at resistive load cosΦ=1; 250Vac-1A at cosΦ=0.4; 30Vdc-1A at L/R=7ms. Minimum permissible load: 5Vdc-100mA or 24Vdc-5mA.


+ VF-MB1 User Manual

+ VF-MB1 Fault Index

+ VF-MB1 Fault Codes 1 >>

+ VF-MB1 Fault Codes 2 >>

+ VF-MB1 Fault Codes 3 >>

+ Toshiba VF-MB1

+ Toshiba Main Page

+ VFD Main Page


The user manuals, commissioning suggestions, error codes and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we welcome suggestions and contributions. If you have field experience or practical information that may improve ease of use, please do not hesitate to share it with us. 28.06.2013