Toshiba VF-MB1 fault codes 1

OC1 0001 Overcurrent during acceleration

- The acceleration time ACC is too short.
- The V/F setting is improper.
- A restart signal is input to the rotating motor after a momentary stop, etc.
- A special motor (e.g., motor with a small impedance) is used.
- Low inductance motor especially High speed motor is used.
+ Remedy:
- Increase the acceleration time ACC.
- Check the V/F parameter.
- Use F301 (auto-restart) and F302 (ride-through control).
- In case of P3, P2, and P1, increase b.
- In case of P2 to P1, set F415 (Motor rated current) and make an auto-tuning.
- Choose the higher power range drive (1 class up drive is recommended).

OC2 0002 Overcurrent during deceleration

- The deceleration time DEC is too short.
- Low inductance motor especially High speed motor is used.
+  Remedy:
- Increase the deceleration time DEC.
- Choose the higher power range drive (1 class up drive is recommended).

OC3 0003 Overcurrent during constant speed operation

- The load fluctuates abruptly.
- The load is in an abnormal condition.
- Low inductance motor especially High speed motor is used.
+ Remedy:
- Reduce the load fluctuation.
- Check the load (operated machine).
- Choose the higher power range drive (1 class up drive is recommended).

OC4 0004 Overcurrent (An overcurrent on the load side at start-up)

- The insulation of the output main circuit or motor is defective.
- The motor has too small impedance.
    Remedy:
- Check the secondary wiring and insulation state.
- Set F513=2.3.

OCR Arm overcurrent at start-up

- A main circuit element is defective.
+ Remedy:
- Contact your Toshiba distributor.

EPH1 0008 Input phase failure

- A phase failure occurred in the input line of the main circuit.
- The capacitor in the main circuit lacks capacitance.
+ Remedy:
- Check the main circuit input line for phase failure.
- Check the capacitor in the main circuit for lack of capacitance.

EPH0 0009 Output phase failure

- A phase failure occurred in the output line of the main circuit.
+ Remedy:
- Check the main circuit output line, motor, etc., for phase failure.
- Select output phase failure detection parameter F605.

OP1 000A Overvoltage during acceleration

- The input voltage fluctuates abnormally.
- The power supply has a capacity of 500kVA or more.
- A power factor improvement capacitor is opened or closed.
- A system using a thyristor is connected to the same power distribution line.
- A restart signal is input to the rotating motor after a momentary stop, etc.
+ Remedy:
- Use F301 (auto-restart) and F302 (ride-through control).

OP2 000B Overvoltage during deceleration

- The deceleration time DEC is too short. (Regenerative energy is too large.)
- The input voltage fluctuates abnormally.
- The power supply has a capacity of 500kVA or more.
- A power factor improvement capacitor is opened or closed.
- A system using a thyristor is connected to the same power distribution line.
+ Remedy:
- Increase the deceleration time DEC.
- Set overvoltage limit operation F305 is set to 1. (Disabled).
- Insert a suitable input reactor.

OP3 000C Overvoltage during constant-speed operation

- The input voltage fluctuates abnormally.
- The power supply has a capacity of 500kVA or more.
- A power factor improvement capacitor is opened or closed.
- A system using a thyristor is connected to the same power distribution line.
- The motor is in a regenerative state because the load causes the motor to run at a frequency higher than the inverter output frequency.
+ Remedy:
- Insert a suitable input reactor.
- Install an optional dynamic braking module.

OL1 000D Inverter overload

- The acceleration time ACC is too short.
- The DC braking amount is too large.
- The V/F setting is improper.
- A restart signal is input to the rotating motor after a momentary stop, etc.
- The load is too large.
+ Remedy:
- Increase the acceleration time ACC.
- Reduce the DC braking amount F251 and the DC braking time F252.
- Check the V/F parameter setting.
- Use F301 (auto-restart) and F302 (ride-through control).
- Use an inverter with a larger rating.

OL2 000E Motor overload

- The V/F setting is improper.
- The motor is locked up.
- Low-speed operation is performed continuously.
- An excessive load is applied to the motor during operation.
+ Remedy:
- Check the V/F parameter setting.
- Check the load (operated machine).
- Adjust OL1 to the overload that the motor can withstand during operation in a low-speed range.

OL3 003E Main module overload

- The carrier frequency is high and load current has increased at low speeds (mainly at 15Hz or less).
    Remedy:
- Raise the operation frequency.
- Reduce the load.
- Reduce the carrier frequency.
- When an operating motor is started up at 0Hz, use the auto-tuning function.
- Set carrier frequency control mode selection F36 to 1 (carrier frequency within the auto-tuning operation).

+ VF-MB1 User manual  

+ VF-MB1 Fault index 

+ VF-MB1 Fault codes 1 >>

+ VF-MB1 Fault codes 2 >>

+ VF-MB1 Fault codes 3 >> 

+ Toshiba VF-MB1 -

+ Toshiba Main page  

++ VFD Main page  

-

"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."  28.06.2013 