Toshiba VF-MB1 fault codes 3


UP1 001E Undervoltage trip (main circuit)

- The input voltage (in the main circuit) is too low.
    Remedies:
- Check the input voltage and secure the voltage within the specified range. Enable F607 (undervoltage trip selection) and F605 (ride-through control). Use F301 (auto-restart) and F302 (ride-through control).


Etn 0028 Auto-tuning error

- The motor parameters (U, L, Io, F405, F415, F417) are not set correctly.
- The motor with a capacity of 2 classes or less than the inverter is used.
- The output cable is too thin.
- The inverter is used for loads other than those of three-phase induction motors.
- The motor is not connected.
    Remedies:
- Set the left column parameters correctly and set the motor name plate and make an auto-tuning again.
- Set parameters U, L, Io, F405, F415, F417 in the right column again, then auto-tuning again.
- Set the left column parameters correctly and set the motor name plate and make an auto-tuning again.
- Use three-phase induction motors.
- Connect the motor.
- Check whether the secondary magnetic contactor or an electromagnetic contactor.

Etn1 0034, Etn2 0055, Etn3 0056 Auto-tuning error

- The motor is rotating.
- Parameter Pg-6 is set and High speed motor is connected.
    Remedies:
- Check whether the motor shaft stops the rotation of the motor disposal.
- Choose the higher power range drive (1 class up drive is recommended).

EF2 0022 Ground fault trip

- A ground fault occurs in the output cable or the motor.
- Overcurrent of dynamic braking resistor.
    Remedies:
- Check the cable and the motor for ground faults.
- Increase the deceleration time DEC.
- Set the supply voltage correction F307 to 0 or 3.

SOLt 002F Step-out (for PM motor drive only)

- The motor shaft is locked.
- One output phase is open.
- An impact load is applied.
- Using the DC braking function.
    Remedies:
- Unlock the motor shaft.
- Check the interconnection cables between the inverter and the motor.
- Prolong the acceleration/deceleration time.
- Turn off the Step-out function when using the DC braking function or the braking resistor with dynamic braking.

Pcf 0035 Safe torque off error

- Error of safe torque off circuit.
    Remedies:
- Contact your Toshiba distributor.

E-13 002D Over speed fault

- The input voltage fluctuates abnormally.
- Over speed fault due to the overvoltage limit operation.
    Remedies:
- Install an optional dynamic braking module.

E-18 0032 Break in analog signal cable

- The input signal from VIC is equal to or less than the F633 setting.
    Remedies:
- Check the wiring between the inverter and analog input signal device, cables, etc.

E-19 0033 CPU communications error

- A communication error between control CPUs.
    Remedies:
- Check the control device, cables, etc.

E-21 0034 Excessive torque boosted

- The automatic torque boost parameter F402 setting is too high.
- The motor has too small impedance.
    Remedies:
- Set a lower automatic torque boost parameter F402 setting to the rated value and make an auto-tuning again.

E-23 0037 Optional unit fault 2

- An optional device is defective.
    Remedies:
- Contact your Toshiba distributor.

E-32 0040 CPU fault 2

- The control CPU is defective.
    Remedies:
- Contact your Toshiba distributor.

E-33 0041 PTC fault

- PTC thermal sensor is open.
    Remedies:
- Check the PTC-in and output connection to the inverter.

E-37 0045 Servo lock fault

- The motor shaft is not locked in servo lock state.
    Remedies:
- Reduce the load in servo lock operation.

E-39 0047 Auto-tuning error

- When auto-tuning (relating parameters are Pg-6, F400=2) or initial position estimation for permanent magnet motor (relating parameters F9-5, F9-6, F9-7) is activated, the current of the permanent magnet motor exceeded the threshold level.
- The inductance of permanent magnet motor is too small.
    Remedies:
- Auto tuning for permanent magnet motor is not allowed for this motor, please increase inductance value.
- When tuning with initial positional estimation, if the condition with initial positional estimation (F9-5, F9-6, F9-7) is not met, choose other modes should be selected (F9-5 = 0).
- Set F9-5 to 3 for the SPM motor.

+ VF-MB1 User manual  

+ VF-MB1 Fault index 

+ VF-MB1 Fault codes 1 >>

+ VF-MB1 Fault codes 2 >>

+ VF-MB1 Fault codes 3 >> 

+ Toshiba VF-MB1 -

+ Toshiba Main page  

++ VFD Main page  

-

"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."  28.06.2013   