6ES5 752-0AA43

Siemens 6ES5 752-0AA43 – RS-422-A / RS-485 Interface Submodule

Siemens 6ES5 752-0AA43 is an RS-422-A / RS-485 serial interface submodule for SIMATIC S5. Part of the S5 interface module range, it provides a 15-pin D-sub connection and differential RS-422 signal circuits isolated from the PLC supply.

It fits the appropriate submodule receptacle in a CP 524, CP 544 or CPU 928B. It supplies the electrical interface; the host CPU/CP configuration determines the protocol, transmission rate and character format.

RS-422 and RS-485 operation

The differences between RS-232, RS-422 and RS-485 matter when selecting a replacement. This card should not be treated as a direct same-cable substitute for an RS-232 interface or a TTY current-loop interface.

RK 512, 3964/3964R and standard open-driver links use RS-422 full-duplex operation. Half-duplex RS-485 communication requires a suitable special driver and jumper configuration. Modbus RTU capability likewise depends on the installed driver; fitting the interface alone does not implement the protocol.

Transmission rate, connector and cable

The upper rate is 19,200 bit/s with a CPU or CP 524, and 76,800 bit/s in a suitable CP 544 application. Protocol-specific and aggregate port-rate limits still apply. Cable length must be assessed with the rate; the 1,200 m upper limit does not apply at every speed.

The main pins are 2: T(A), 9: T(B), 4: R(A), 11: R(B), 8: GND and 1: shield. For RS-422 full-duplex wiring in the S5 connecting cable, connect each transmit pair to the partner’s receive pair. Match A/B designations against the partner’s wiring diagram.

Signal GND and cable shielding serve different purposes. Follow the manufacturer’s grounding and reference wiring diagram. When investigating electromagnetic interference, inspect the twisted pairs, shield contact and routing near power cables together.

Jumpers and the 0AA43 revision

X3 jumper 16–18 selects full duplex; 18–20 selects half duplex, which requires a suitable special driver. The factory BREAK-detection preset uses jumpers 12–14 and 4–6. Identify pin numbers from the correct viewing direction before changing links.

The Siemens CP 544 documentation supplement explicitly permits operation without a fan with the 0AA43. Check the host CPU/CP’s own installation and cooling requirements as well. Do not transfer the earlier RS-422/485 module’s fan and jumper instructions unchanged.

Configuration and commissioning

Back up the PLC program and CPU/CP parameters. Review COM 525 for CP 524, and the applicable COM PP settings for CP 544 and CPU 928B point-to-point links. During troubleshooting, compare the rate, parity, data/stop bits and driver selection with the partner device.

Distinguish the tasks of the S5 communications processor from those of this submodule. In a Siemens S5 system, checking the cable and electrical interface first, followed by protocol settings and program data handling, provides a clear troubleshooting sequence.

Editor’s note

Check those last two digits first: this module is 0AA43. The earlier 0AA42 has a different jumper layout. Keep its photograph for reference, but check the pin numbers before moving links onto the replacement. Similar-looking boards can be surprisingly easy to mix up.

If the interface transmits but receives no reply, trace the T(A)/T(B) and R(A)/R(B) pairs at both ends before blaming the card. With another manufacturer’s device, follow the actual signal definitions rather than matching the A/B letters by appearance alone.

If the existing card is a V.24 interface such as 0AA23, do not simply install this one and reuse the cable. The electrical interface, wiring and device settings must agree. Establishing that match first is much easier than chasing communication errors afterwards.

A 15-pin socket is not enough to identify the interface. Distinguish other 752 submodules such as 0AA53 by their full order code. Use the machine documentation to establish which port handles programming and which handles device communication.

When assessing a used card, go beyond the first successful connection. Test transmission and reception together, at the operating rate and for a meaningful period. Keep photographs of the jumpers, connector and solder joints; they give you a useful reference if an intermittent problem appears later.

OtomasyonAVM resources and PDFs

+ Browse our S5 interface modules and S5 communications modules for the host-board and interface-submodule groups.

+ Siemens S5 shared PDF archive and manuals. Manufacturer references for pin assignments, jumpers and the 0AA43 update are provided below.

Related topics

+ 6ES5 752-0AA42: the earlier RS-422/RS-485 version; review its different jumper arrangement and cooling requirements.

+ 6ES5 752-0AA12 · 6ES5 752-0AA23 · 6ES5 752-0AA53 · 6ES5 752-0AA62: other 752 interfaces; establish the full code and function before treating them as alternatives.

Browse SIMATIC S5

+ S5 interface modules · S5 communications modules · SIMATIC S5

+ Siemens S5 PLC · Siemens second-hand equipment

Siemens and external references

+ Siemens S5-135U/155U System Manual – English; §5.11.5, pages 5-112–5-117, pin assignments and jumper settings.

+ Siemens CP 544 Manual, documentation supplement – English; fanless operation with 6ES5 752-0AA43.

+ Siemens S5R007 special-driver manual – English; final-page 0AA43 jumper update. Its Modbus application is specific to the CP 524 / CP 525-2 driver.