6ES5 301-3AB13
Siemens 6ES5 301-3AB13 — IM 301-3 Central Controller Interface Module
The Siemens 6ES5 301-3AB13 is an IM 301-3 interface module installed in the central controller of a SIMATIC S5 system. Its lower connection supports distributed expansion up to 200 m; its upper connection supports additional centralized expansion. Within the S5 interface range, it combines these two connection roles.
Siemens ST 50 specifies up to 0.8 A from the internal 5 V supply, 4 W power loss and one slot for the IM 301 family. These are the board’s own figures; calculate expansion-rack module supply requirements separately.
Distributed connection with IM 310 and 721 cable
The lower front connection uses a 6ES5 310-3AB11 IM 310 at the expansion end. An arrangement using 721 S5 connecting cables supports up to four expansion units with a maximum total of 200 m from the central controller to the last unit.
The system manual lists EU 183U, ER 701-2 and ER 701-3 arrangements. Observe the I/O-module restriction for EU 185U. The IM 301/310 arrangement is limited to I/O modules and IPs without page addressing.
Upper connection and two terminator types
The upper front connection provides centralized EU 183U expansion through an IM 312-3. This group includes cable-length variants such as 312-3AB12 and 312-3AB32. Keep the centralized branch’s cable calculation separate from the distributed line’s 200 m limit.
Use a 760-0AB11 terminator on a free upper centralized connection and a 760-0AA11 on a free lower distributed connection of the IM 301-3. Check the function before exchanging similar-looking plugs.
Indicators and address checks
The front panel has two red fault LEDs. The manual describes indications during CPU restart when the internal 5 V supply or external 24 V load supply fails. Monitoring an external 24 V supply does not make 24 V the board’s operating supply.
During troubleshooting, identify the affected branch, then check cables, terminators, supplies and cabinet grounding in sequence. Compare addresses in the PLC program as well; central and expansion modules must not share conflicting addresses.
Rack selection and related models
Match the rack and slot arrangement to the manual for the existing S5-135U or S5-150U installation. Photograph the jumpers before removal. Do not assume that a replacement board has suitable settings from its appearance alone.
The 300-3AB11 belongs to centralized connections; compare the IM 301-3’s additional distributed role separately. The 301-5CA12 uses the EU 184U/EU 187U group at its upper centralized connection. Similar front panels do not establish interchangeability between IM 301-3 and IM 301-5.
Editor’s note
Start by tracing the upper and lower cables. This board has two separate connections. Add the cable destinations to the label photograph so the replacement request is clear from the outset.
An unused socket may need a terminator rather than another cable. Read the upper and lower plug codes separately. A small missing plug can otherwise lead to replacing a sound board.
Record whether one expansion unit disappears or the whole line fails. That small observation often gives a much better starting point for the investigation.
Record jumpers, slot position and cabling, and back up the program. Switch off power and follow the system instructions for replacement. Keeping the original settings to hand makes the replacement much easier to assess.
For used equipment, ask for the connection you intend to use to be tested with a suitable partner module. Where possible, check the upper and lower connections separately. A working test on one branch does not prove the other has been checked.
OtomasyonAVM resources and PDFs
+ About Siemens S5 PLCs · S5 interface modules
+ Siemens S5 PDF files — our manual archive. Manufacturer catalogue and system-manual references for this model appear below.
Related topics
+ 310-3AB11 · 312-3AB12 · 312-3AB32 · 760-0AB11 · 760-0AA11
Browse SIMATIC S5
+ S5 interface modules · S5 racks · S5 cables · SIMATIC S5 · Siemens second-hand equipment
Siemens and external references
+ Siemens ST 50, 1998 — 4/142: exact 301-3AB13 code, technical data and terminator selection (English)
+ Siemens S5-135U/155U system manual — 7-10–7-13: connections, indicators and arrangement (English)
+ Same manual — 7-23: terminators for free centralized and distributed connections