6ES5 183-3UA13

Siemens SIMATIC S5 6ES5 183-3UA13 · EG 183U expansion rack

The 6ES5 183-3UA13 is a 21-slot S5 expansion rack for SIMATIC S5-135U and S5-155U systems. It has its own power supply, fan cooling and cable duct. The CPU in the central rack, such as the 188-3UA12, runs the STEP 5 program. Interface modules carry data between the CPU and the cards installed in the expansion rack.

120/230 V AC input and output ratings

Siemens pairs this rack with the 6ES5 955-3LC42 power supply. The front-panel selector sets the input to 120 or 230 V AC. The AC input terminals are marked L1, N and PE. At rated load, input current is 2.5 A RMS at 120 V or 1.5 A RMS at 230 V. Siemens rates the main output of this S5 power supply at 5.1 V DC / 18 A. Auxiliary outputs are 15 V DC / 0.5 A and 24 V DC / 1 A.

The 183-3UA22 in the same EG 183U family uses the 955-3NC42 with a 24 V DC input. Both racks have an 18 A rating on the 5 V rail, so check the rack order number and the power supply input label when selecting a spare.

Slot assignments and supported modules

The EG 183U slot table covers digital inputs, digital outputs and analog I/O. Check the order number and slot when transferring a combined digital I/O card. Support for intelligent peripheral modules is limited to types without page addressing. Siemens lists CP communications processors and interrupt processing as unsupported on the EG 183U.

Interface modules, cables and terminators

Before replacing expansion hardware, record the interface modules at both ends and the fitted terminator. One Siemens centralized configuration uses an IM 300-3 in the central rack and an IM 312-3 in slot 163 of the EG 183U. The last IM 312-3 in the chain takes a 6ES5 760-0AB11 terminator.

One distributed configuration uses an IM 304 in the central rack and an IM 314 in slot 3 of the EG 183U. This arrangement uses a 6ES5 721-0xxxx series interconnecting cable and a 6ES5 760-1AA11 terminator on the last IM 314.

Editor’s Note

For a used 3UA13, ask for photos of the rack and 955-3LC42 nameplates and the front-panel voltage selector. Check the selector against the line voltage before applying power. A 120 V setting on a 230 V supply can damage the power supply. For a bench test, request evidence that the fans run and that the 5 V rail holds under load.

Selling a 6ES5 183-3UA13? Send the nameplate photos, quantity, working condition and asking price to otomasyonavm@gmail.com.

PDF archive

Shared SIMATIC S5 PDF archive

Related topics

6ES5 183-3UA12 · 6ES5 184-3UA21 · 6ES5 185-3UA11

Navigation

S5 central and expansion units · SIMATIC S5 · Used Siemens automation · Used automation equipment

References

Siemens S5-135U/155U System Manual (English, C79000-G8576-C199-07). Rack and slots pp. 4-15–4-19, AC wiring p. 4-27, voltage selector p. 4-34, power supply ratings pp. 4-51–4-53, interface connections pp. 2-4–2-5.

Siemens S5-155H Manual, Volume 1 (English, 6ES5 998-4SR21, p. xi). Lists the exact order number as an EG 183U expansion unit.