6ES5 482-4UA11

Siemens 6ES5 482-4UA11 – 24 V DC Digital Input/Output Module

Siemens 6ES5 482-4UA11 is a DI/DQ 482-4 digital input/output module for Siemens S5 installations. Designed for S5-135U/155U and EU 185U applications, this SIMATIC S5 module provides 32 process channels at 24 V DC. It supports 16 inputs plus 16 outputs or 24 inputs plus 8 outputs, with eight shared channels individually usable as inputs or outputs. Its flexible channel allocation and IP 257 connection distinguish it within the S5 digital input/output module range.

Typical duties include reading contacts and compatible inductive sensors, and switching suitable 24 V DC loads such as relays. Its semiconductor outputs are rated for up to 0.5 A per channel. All process channels form one jointly isolated group; individual channels are not isolated from one another.

Using the eight shared channels

Channels 0.0–0.7 are dedicated outputs, while 2.0–3.7 are dedicated inputs. Channels 1.0–1.7 can be used individually as inputs or outputs. Selection therefore involves more than comparing the number of digital inputs and digital outputs: the actual allocation required by the machine matters.

The shared channels are controlled through the PLC program and its read/write accesses. The output-register bit for a shared channel used as an input must remain at 0. If any shared channel is used as an input, its connected sensors and the module's 1L+ terminal must use the same power supply. Unused channels should be left unwired and should not be addressed by the program.

Input signals and output loads

For the 4UA11 version, the input ranges are −33 to +5 V for logic 0 and +13 to +33 V for logic 1. Typical input current is 8.5 mA, input resistance 2.8 kΩ, and delay 0.3 ms. The manual specifies 22–33 V DC for two-wire BERO operation; the sensor's off-state leakage current also needs checking.

Output switching current is 5 mA–0.5 A, with a combined limit of 4 A per eight outputs. The specified output levels are at least L+ − 1.5 V at logic 1 and no more than 3 V at logic 0. Each group of eight outputs in the 4UA11 uses a 6.3 A slow-blow fuse. When selecting fuses, do not apply the different rating specified for the 4UA20.

Total load capability is 100% with ventilation. Without ventilation, the general factor is 50%, increasing to 100% up to 35 °C. Maximum switching frequency is 120 Hz for resistive loads; for inductive loads it is 2 Hz at 0.3 A or 0.5 Hz at 0.5 A. Assess coil current together with cabinet temperature.

42-pin connection and power supplies

The module uses a 497-series, 42-pin front connector. Options in the S5 cables and connectors range include the crimp-terminal 6ES5 497-4UA12 and screw-terminal 6ES5 497-4UB31. The wiring diagram assigns pins 4–11 to dedicated outputs, 13–20 to shared I/O channels, and 25–32 plus 34–41 to dedicated inputs.

The field supply is 24 V DC, with typical system-bus consumption of 80 mA at 5 V. For the 4UA11, typical consumption from L+/L− is 150 mA and nominal power loss is 13.6 W. Follow the manual's single-group isolation arrangement when planning grounding and reference connections. Approximate dimensions are 20 × 255 × 195 mm and weight is 0.4 kg; check the compatible S5 rack and front connection together.

Addressing, IP 257 and the 4UA20 distinction

The start address is set on the module's addressing switch; the slot number alone does not define its address. Check the shared byte's input/output use against the program. For installations considering separate modules, the 6ES5 431-4UA12 input and 6ES5 451-4UA13 output pages can help compare channel arrangements; connector and signal requirements must also be matched.

The 4UA11 has a local-bus interface for the IP 257. For operation without the IP 257, slide switch S2 must be in position 1. SYNIN/SYNOUT are specific to IP 257 operation. When reviewing S5 function modules and interface modules, establish the purpose of this connection in the existing installation. The 6ES5 482-4UA20 provides similar basic I/O functionality but lacks the IP 257 connection interface.

Editor's note

Start with a clear photograph of the label and check the 4UA11 suffix. The wider Siemens S5 system includes several different 482 modules. If the existing module connects to an IP 257, matching the channel count alone will not make a 4UA20 suitable.

If the shared channels behave unexpectedly, check the program before condemning the hardware. During PLC debugging, monitor the output bit associated with the affected channel. An output command applied to a shared channel wired to a sensor is one of the first things to investigate.

Trace the sensor supply back to its source. When shared channels are used as inputs, the sensors and 1L+ must use the same supply. Two separate supplies are not interchangeable simply because both measure approximately 24 V.

If an output command is present but the load does not operate, check the field supply, 6.3 A slow-blow fuses and front connector first. Inspect the red short-circuit indicator and the H+ common fault output. Disconnecting the field load and testing with an appropriate substitute load helps separate a wiring fault from an output-stage problem.

Before fitting a replacement, photograph and compare the address switches, S2 position and X20 enable jumper. Use S2 position 1 for operation without the IP 257. X20 determines whether the F+/F− enable circuit is active; understand the existing arrangement before changing the jumper.

For a used module, one illuminated input LED is only a starting point. Test dedicated inputs, dedicated outputs and shared channels in their required directions. Measure outputs under load and record intermittent behavior as the cabinet warms up. A useful spare is one tested against the machine's actual wiring and program.

OtomasyonAVM resources and PDFs

Start with About Siemens S5 PLC and the S5 digital input/output modules section.

+ OtomasyonAVM S5 PDF archive: use alongside the S5-135U/155U system documentation. Sections 8.1.4 and 8.4.19 of the English Siemens manual linked below are the model-specific references used here.

Related topics

+ 6ES5 482-4UA20: Version without the IP 257 local-bus interface.

+ 6ES5 431-4UA12: Separate digital input module comparison page.

+ 6ES5 451-4UA13: Separate digital output module comparison page.

Browse SIMATIC S5

S5 digital input/output modules · SIMATIC S5 · Siemens S5 PLC · Used Siemens equipment · S5 cables and connectors

Siemens and external references

+ Siemens S5-135U/155U System Manual, English, C79000-G8576-C199-07: §8.1.4, printed pages 8-12–8-13; §8.4.19, printed pages 8-69–8-71. Covers channel use, the 4UA11/4UA20 distinction, specifications and wiring.