6ES5 526-3LB01

6ES5 526-3LB01 Siemens SIMATIC S5 CP 526 Monochrome Process Display Module

The Siemens 6ES5 526-3LB01 is a CP 526 communications processor that generates operator displays for a SIMATIC S5 PLC. The 3LB01 version supports a monochrome monitor and uses natural convection cooling. Its front panel has a 75 Ω BNC composite video output and a 15-pin, 20 mA TTY interface for a process keyboard or programming device. Siemens documents CP 526 base module installation in specific racks and slots for the S5-115U, S5-135U, S5-150U and S5-155U.

The card displays process values and messages from the PLC. Operators can call up screens and enter values in fields configured for input using the process keyboard. The 6ES5 526-3LA01 also supports a monochrome monitor and requires forced-air cooling. Check the full order number when replacing a card or moving it to another rack.

How do the monitor and keyboard connect?

Connect the monochrome monitor to the single front-panel BNC output. The BAS composite signal carries picture and sync on the same line. Siemens specifies a 0.7 V picture component and a 0.3 V sync component into 75 Ω. When tracing S5 cables in the cabinet, label the BNC video line and the 15-pin TTY line separately.

The monochrome version uses the low-resolution setting. Siemens specifies 640 × 234 pixels and a 15.44 kHz horizontal scan rate for this mode. The X10 and X14 settings must match, and X17 must be in position B for monochrome composite video.

The 15-pin D-sub port accepts either a process keyboard or a programming device (PG). The 982 series 20 mA process keyboard, the replacement alphanumeric keyboard for CP 526 and the 6ES5 727-2CB00 keyboard cable have separate order numbers. The 727-2CB00 is the 10 m cable between a 982 process keyboard and the CP 526.

Which rack and power supply does it need?

Identify the S5 rack by order number, then check the CP slot. The S5-115U CR 700-2LB layout, for example, shows the CP 526 fitted in the 6ES5 491-0LB11 adapter casing. Siemens excludes CP 526 operation with the 3 A power supply in this rack configuration.

For central racks such as the S5-135U 6ES5 135-3UA11, S5-150U 6ES5 150-3SB61 and 135U/155U 6ES5 188-3UA22, confirm the CP position against the slot assignment table for the installed rack. Record the rack order number and the occupied slot together.

Siemens specifies 2.2 A at +5 V and 40 mA maximum at +24 V for the CP 526 base module. The process keyboard draws approximately 200 mA in addition on the 24 V rail. When checking a 6ES5 955-3LF12 rack power supply, for example, verify the installed system’s 24 V load as well as its main 5 V capacity.

How are the display project and PLC interface preserved?

Displays configured in COM GRAPH and the associated application data are stored on a RAM or EPROM memory submodule. Siemens uses the 6ES5 373-0AA41 EPROM as an example in the CP’s SYSID identification area. Use the installed memory order number and the project backup when preparing a replacement.

The CPU and CP exchange data after the SYNCHRON handling block runs successfully. In the CP 526 configuration documented by Siemens, the X7 jumpers set the SSNR interface number. If the display comes up but the PLC values stop updating, check the CP’s RUN/STOP selector, the X7 setting and the PLC handling blocks.

How do the other CP 526 order numbers differ?

The 6ES5 526-3LA11 is the forced-air version for colour monitors. The CP 526 base boards listed for S5-DOS also differ by monitor type and cooling. The 3LF01 supports monochrome and the 3LF11 supports colour. Both require external airflow. The naturally ventilated 3LG01 supports monochrome and the 3LG11 supports colour.

The 6ES5 526-3LA21 and 6ES5 526-3LA22 are separate CP 526 expansion boards. Siemens describes expansion functions such as trend curves and bar graphs under the colour CP 526 configuration. Record the base module and any fitted expansion board as separate items.

Editor’s note

Check the spare’s nameplate for 6ES5 526-3LB01. Even if the front panel has a single BNC output, verify from the order number that it is the naturally ventilated version.

Back up the COM GRAPH project before removing the card. Siemens states that unplugging the backplane-backed RAM submodule or withdrawing the CP card causes the application data in RAM to be lost.

With the rack powered down, photograph the X7, X10, X14 and X17 settings before removal. Include the rack slot and adapter casing order number in the replacement record.

If there is no picture, check the monitor power, the BNC line and the selected monitor input. If RUN and CP FAULT are on and STOP is off, the Siemens LED table also points to a possible break in the PG or keyboard serial link.

After replacement, call up a screen using the process keyboard. Then confirm that a known PLC value updates on screen and that the application handles an operator input correctly under controlled test conditions.

OtomasyonAVM resources and PDFs

Siemens SIMATIC S5 PLC guide · SIMATIC S5 communications processors

OtomasyonAVM SIMATIC S5 PDF archive

Related topics

Monochrome CP 526 versions · 6ES5 526-3LA01 · 6ES5 526-3LG01

Process keyboard connection · CP 526 replacement keyboard · 727-2 keyboard cable

Browse SIMATIC S5

Used Siemens SIMATIC S5 equipment › SIMATIC S5 › S5 communications modules

Siemens documentation and external references

Siemens COROS CP 526 Communications Processor manual · Chapter 3, specifications, monitor connection, jumpers and LED diagnostics

Siemens SIMATIC S5-115U system manual · CP 526 rack configuration and adapter casing

6ES5 526-3LB01 order number listing · Monochrome monitor and natural ventilation