6ES5 460-4UA11
Siemens 6ES5 460-4UA11 — 8-Channel Isolated Analog Input Module
6ES5 460-4UA11 is an eight-channel, compact U-format analog input module for U-periphery installations such as S5-135U and S5-155U. It measures voltage, current and Pt100 resistance signals using appropriate 498 range submodules. Within a SIMATIC S5 installation, its function depends on both fitted range submodules and the operating switches.
Each range submodule serves four channels; the main module has two submodule positions. The incoming analog signal is converted into a digital value through the selected input circuit. For pressure, level, temperature and other process measurements, match the sensor output to the configured range.
Choosing the range submodules
6ES5 498-1AA11 provides ±50 mV, ±500 mV and Pt100 operation; 498-1AA21 provides ±1 V; 498-1AA31 provides ±10 V; and 498-1AA61 provides ±5 V. These are the ranges associated with the appropriate standard operating modes.
498-1AA41 is for ±20 mA; 498-1AA51 is for 4–20 mA two-wire transmitters; and 498-1AA71 is for 4–20 mA four-wire transmitters. Different range submodules may be fitted to the two four-channel groups while retaining a compatible common basic mode.
The 4UA11 has no ±12.5 mV setting. That feature uses the additional amplifier in 6ES5 460-4UA12. Do not transfer the entire 460-4UA13 specification to this earlier version either. Thermocouple measurement requires the appropriate reference-junction compensation; Pt100 measurement requires the correct current-source and sensor wiring.
Power supply and front connector
The digital section takes 5 V from the system bus; the analog section requires an external 24 V DC supply. The F+/F− enable input also requires 24 V DC. Front-connector assignments are 1=F+, 2=F−, 3=L+ and 21=L−. When checking the S5 power supply, inspect load power and the enable circuit separately.
Voltage/current input pairs are CH0:4/6, CH1:8/10, CH2:13/15, CH3:17/19; CH4:25/27, CH5:29/31, CH6:34/36 and CH7:38/40, with the first terminal of each pair positive. Follow the numbering on the 42-way front connector. 22/23 are compensation connections and 41/42 are Pt100 constant-current connections; use the diagram for the actual sensor circuit.
Isolation depends on the wiring arrangement
For voltage and current measurement, the inputs are isolated from each other and from the 0 V reference. The permitted potential difference is 60 V AC / 75 V DC. Input-to-input isolation does not apply to Pt100 wiring. For two-wire transmitters, the Siemens supplement requires the common reference of the relevant channels to be connected to L−, removing their isolation from the L+/L− supply.
Do not apply one grounding arrangement indiscriminately to every sensor circuit. Review the S5 system wiring, fitted range submodule and transmitter supply arrangement together. Two-wire transmitters require the 500 mV basic mode.
Operating modes, addressing and diagnostics
Operating switches select the 50/500 mV basic mode, 50/60 Hz, single/cyclic scanning, value format and applicable open-circuit monitoring. The STEP 5 program must match the selected two’s-complement or magnitude-plus-sign format. Siemens specifies 13-bit two’s complement or 12 bits plus sign.
The nominal bipolar range corresponds to ±2048 measurement units; 4–20 mA corresponds to 512–2560 units. These numbers are not the same as the complete raw 16-bit input word. The eight channels occupy 16 address bytes, with the starting address set using the module’s address switch.
At 50 Hz, integration takes 20 ms and coding takes 60 ms per value; an eight-value cycle is approximately 0.48 s. During fault investigation, consider scanning time, overflow and open-circuit status together. Open-circuit monitoring is selectable for ±50/±500 mV and applicable Pt100 circuits; it is not available in the same way for every current range.
Differences from related modules
6ES5 465-4UA11 has a different, non-isolated 16/8-input design. 6ES5 463-4UA12 has four inputs and uses its wiring arrangement to select the range. Check channel count, isolation, range submodules, connector and program before treating either as a replacement.
Editor’s note
When buying this module, take a moment to read the two smaller 498 submodule labels as well as the main 460-4UA11 label. The main card can be correct while the fitted ranges are unsuitable for your sensors.
If four channels misread in the same way, start with that group’s range submodule and basic-mode setting. If only one channel is affected, start with its sensor, cable and connector contact. This can save replacing healthy equipment.
If the card has 24 V but cannot be read, check the F+/F− enable supply too. Do not apply the 4UA12 enable-jumper instructions to this earlier 4UA11 without checking the exact version.
For Pt100 or two-wire transmitter wiring, the word “isolated” on the main description is only part of the story. Both arrangements change the isolation conditions. Photograph the existing panel connections and compare them with the manufacturer’s drawing.
Testing one input on a used module is a useful start. Where possible, test both four-channel groups at several points using a suitable source. Keeping the range labels, switch settings and results together helps with later maintenance of an older S5 installation.
OtomasyonAVM resources and PDFs
+ S5 analog modules · About Siemens S5 PLCs · 498 range submodules.
+ OtomasyonAVM S5 PDF archive. For this exact order number, use the U Periphery manual below, §5.1, printed pages 5-1–5-5, together with its opening supplement on two-wire transmitters. The manufacturer documents are in English.
Related topics
+ 498-1AA31 for ±10 V · 498-1AA41 for ±20 mA · 498-1AA51 for two-wire 4–20 mA · 498-1AA71 for four-wire 4–20 mA.
+ 460-4UA12 · 460-4UA13 · 465-4UA11. Compare version-specific functions and wiring before selecting a replacement.