6ES5 858-0AA11

The Siemens 6ES5 858-0AA11 is the TK 858 telecommunications unit for SIMATIC S5 systems. It links a PLC or programmer’s TTY/V.24 serial interface to an external modem for remote programming or PLC-to-PLC data exchange over dial-up or dedicated lines. Siemens lists the 0AA11 order number for 220 V / 50 Hz mains.

This S5 communications unit is a desktop device with separate ports for the PLC or programmer and the modem. When restoring an existing link, first establish whether the installation was set up for remote programmer access or data exchange between controllers.

PLC/programmer and modem ports

The two rear 25-pin D-Sub ports have different roles. The PLC/PU port supports TTY or V.24, and the MODEM port uses V.24. Wiring inside the PLC/PU cable plug selects TTY or V.24. Match the pin assignment in the manual when choosing an S5 connecting cable.

Siemens specifies maximum interface rates of 9,600 baud for TTY and 19,200 baud for V.24. The rate over the telephone line depends on the modems and the settings at both ends. See our RS-232 guide and serial interface comparison for background on the electrical interfaces.

Remote programmer access and PLC coupling

The Siemens manual calls remote programmer access the PU function and describes PLC-to-PLC data exchange under computer coupling. Its PLC coupling examples cover systems from the S5-115U through the S5-155U. On an installation with an S5-135U central controller, identify the PLC-side card and interface by their full order numbers.

The PRODAVE DOS 64R section covers the CP 524 (6ES5 524-3UA13), CP 525 (6ES5 525-3UA21) and CPU 928B. For the CP 524/525, Siemens lists the 10 m TK 858 cable as 724-0CB00 for V.24 and 724-1CB00 for TTY.

Mains input, DIP settings and status LEDs

The general hardware specification describes a 230/115 V selector and a 48–63 Hz frequency range. Check the nameplate and selector against the site’s power supply. The enclosure measures 246 × 63 × 200 mm and is rated IP20.

S1 sets the modem port’s transmission rate and data format. S2 covers settings such as operating mode, line type and dialling method. Siemens specifies that changed DIP settings take effect after a power cycle.

DCD indicates modem carrier detection. The PLC/PU Fault and Modem Fault LEDs identify which interface reported the fault. The front-panel WRITE key switch controls remote write access.

Editor’s note

Photograph the underside nameplate. It carries the full order number and power information. Record the rear voltage selector position in the same service note.

Label the two cables before removing them. The PLC/PU and modem plugs look similar. Record which S5 interface each cable serves and whether the PLC side uses TTY or V.24.

Keep a record of the working setup. Save the S1 and S2 positions, modem model, line type and serial settings at the far end. These details make it easier to bring a replacement into service.

Check carrier and data transfer separately. If DCD is on but data is missing, check the PLC/PU cable and serial settings. Before testing a write, verify the program backup and record any installed S5 memory module.

Ask what comes with a spare. When buying used communications equipment, confirm whether the modem cable and WRITE key are included and which interface was used for testing.

OtomasyonAVM references and PDF archive

Browse our Siemens S5 PLC section for model pages and our S5 PDF page for published series manuals. The TK 858 commissioning manual is linked under External references below.

Related topics

See our PLC programming guide for program maintenance and our PLC CPU guide for background on the controller side of the link.

Site navigation

Siemens Automation › Siemens S5 PLC › S5 communications modules

External references

Siemens TK 858 Commissioning Instructions, 6ES5 998-0CM01 (English PDF) · See sections 1.4 for interfaces, 1.5 for settings, 1.9 for specifications and 1.10 for ordering data.

Siemens 6ES5858-0AA11 data sheet (German PDF) · Exact order number and TK 858 product identification.