6ES5 465-3AA13 Siemens S5 – 16 Analog Inputs / 8 Pt100 Inputs
6ES5 465-3AA13 is a non-isolated, compact K-design analog input module for S5-130W and S5-150K/150S systems. This Siemens S5 module supports 16 voltage/current inputs or 8 Pt100 inputs, depending on its hardware configuration. Its basic voltage ranges are ±50 mV and ±500 mV.
The module converts low-level analog input signals or Pt100 sensor resistance into digital values for the PLC. It does not have a fixed arrangement of eight mV channels plus eight Pt100 channels. The selected operating configuration determines the signal type and channel count.
Measurement ranges and hardware configuration
Jumper settings select ±50 mV, ±500 mV or Pt100 for all inputs together. When reviewing an analog I/O installation, do not assume that each channel has an independently selectable range. With PLC input modules, the software configuration must agree with the physical hardware settings.
±1 V, ±10 V and ±20 mA measurement requires appropriate measuring resistors in addition to the ±500 mV jumper setting. Changing software scaling alone cannot configure a 0–10 V / 4–20 mA installation. Match the analog signal, installed resistor set and circuit drawing.
The range-selection hardware of this K-design module differs from the 6ES5 498-1AA11 range submodule arrangement used with 6ES5 465-4UA13. A shared 465 family designation does not establish that another module's range hardware or wiring diagram can be used directly.
Pt100 and sensor connections
Pt100 operation supports eight sensors using four-wire connections; the catalog specifies a measuring current of 2.5 mA. Check the Pt100 sensor wiring with the differences between Pt100 and thermocouples in mind. A thermocouple installation also needs suitable cold-junction compensation and software conversion alongside the correct mV range.
A Pt100 reading must not be treated automatically as a temperature value. Check how the existing program converts resistance into °C. Siemens' BRAUMAT MESS documentation also states that additional Pt100 correction is needed and may be performed with POLY; this is an application-specific software requirement.
Power supply, reference potential and cabling
The internal supply is 5 V, with approximately 0.3 A consumption stated in the catalog. The inputs are not isolated; the permitted difference between a referenced sensor's common potential and the central grounding point is ±1 V maximum. Review S5 signal cabling and grounding connections accordingly.
At millivolt levels, cable routing, shielding and contact quality can materially affect the reading. Investigate electromagnetic interference alongside nearby motor and contactor wiring. An EMC filter alone cannot correct an unsuitable common reference or an incomplete sensor connection.
Measurement timing, addressing and programming
The numerical representation is 11 bits plus sign, with 2000 units corresponding to the nominal voltage/current range. Within the Siemens S5 architecture, do not transfer a newer module's scaling to this older design. Pt100 resistance representation requires separate interpretation.
At the 50 Hz setting, integration takes 20 ms and conversion takes up to 60 ms per reading. The catalog gives full scan times of 0.96 s for 16 inputs and 0.48 s for eight inputs. During PLC programming, distinguish the CPU scan time from the module's measurement update time.
Each measured value is processed through two bytes. During PLC troubleshooting, check address coding, sign handling and overrange status. Do not copy addressing or range settings directly from a different 465 model such as 6ES5 465-7LA13.
Editor’s note
Establish the operating mode first. Does the installation need 16 voltage/current channels or eight Pt100 channels? A working module can still be unsuitable for the installation if its configuration differs.
Inspect a replacement module's resistors. Identical order numbers can carry different resistor sets and jumper settings. Photograph the original hardware and compare it before making changes.
Test Pt100 operation with a known resistance. Use a suitable four-wire simulator or precision resistor to separate module testing from field-cable testing. A Pt100 resistance of 100 Ω represents 0 °C; the raw number is not automatically a temperature.
Never test an mV input with 24 V. This is a low-level measurement circuit. Verify the test source voltage and reference potential before connecting it; arbitrary voltage injection is not a diagnostic method.
Allow a complete measurement scan. Updating all channels can take much longer than a PLC scan. After changing the test signal, wait for the measurement cycle and record every channel separately when assessing a used module.
OtomasyonAVM resources and PDFs
+ About Siemens S5 PLC: system architecture and legacy installations.
+ S5 analog modules: individual analog input and output module pages.
+ S5 PDF files: the shared archive for S5 work outside the 90U group.
Related topics
+ 6ES5 465-4UA12: compact U design using measuring-range submodules.
+ 6ES5 465-4UA13: a 465 model with different hardware and range-selection arrangements.
+ 6ES5 465-7LA13: a different 465 module for the S5-115U family.
+ Pt100 versus thermocouples: choosing a sensor and measurement method.
Browse SIMATIC S5
+ S5 analog modules · S5 cables and connectors
+ SIMATIC S5 · Siemens S5 PLC · Siemens second-hand equipment
Siemens and external references
+ Siemens ST 53, 1985 – German catalog, archive copy: page 9/6 identifies the exact order number and systems; pages 3/23 and 8/18 describe the 465-3 family.
+ Siemens BRAUMAT/SISTAR Classic V5.3 – Bausteine S5, German: A5E00239367-04, page 2-69; 6ES5465-3AA13, MESS/POLY and current-signal processing.
+ Siemens compact analog modules – German hardware reference: C79000-B8500-C234-5 covers the earlier 465-3AA12 version. It does not establish revision-specific wiring approval for the 3AA13.