6ES5 930-7AA21
Siemens 6ES5 930-7AA21 SIMATIC S5-110A power supply
The 6ES5 930-7AA21 is a PS 930 power supply for the SIMATIC S5-110A. Siemens lists a 115 V AC input, and the nameplate reads 110/115 V AC. Exact-order-number parts records give 5 V DC at 0.7 A for the internal rack supply. The front panel has a 5 V indicator.
The PS 930 supplies the CPU 900 and the internal control circuits of the rack modules. Trace the field supply to sensors and actuators separately on the digital input and digital output circuits. For external field power, Siemens lists the 931-7AA21 at 115 V AC input and 24 V DC / 0.8 A output.
115 V AC input and fuse
With cabinet power isolated, compare the input rating and S5 connections with the cabinet drawings. Siemens shows the PS 930 PE terminal connected to protective earth. For this exact order number, the spare-parts table specifies a T 0.2 A time-delay fuse, part number 261 325.
Mint and PE in the programmer connection
Siemens figure 31 shows the 7AA21 with the 6ES5 500-7AA11 programmer interface. In that arrangement, Mint and PE are separate connection points. Trace the interface module and rack connections against the drawing. Figure 32 separately covers the 6ES5 500-7AA12 and the other PS 930 variants listed in the manual.
Distinguishing the 7AA21 from nearby 930 models
The 7AA11 and 7AA12 take 220 V AC, and the 7AA31 takes 24 V DC. The 7AA22 is also a 115 V AC model. Siemens lists it at 5.2 V / 0.9 A with a T 0.3 A fuse. The 930-8MD11 is a separate 24 V DC output model for the S5-100U. Match the full order number, input voltage and rack connection when selecting a spare.
Tracing a 5 V supply fault
If the 5 V indicator is lit but a 400-series input or 410-series output is unresponsive, check the relevant field supply. If the fault is limited to an expansion unit, check its supply and the connection between the racks separately.
During PLC fault finding, verify the supplies before tracing the 330 test module and programmer connections in their instructions. Before a planned shutdown, record the STEP 5 project backup and identify the program on the S5 memory module.
Editor’s note
Ask for a photo that shows the 930-7AA21 order number and the 110/115 V marking together. Identify the spare by the nameplate.
Recheck the full order number before replacing a fuse. Siemens specifies T 0.2 A for the 7AA21.
If the 5 V indicator is dark, have qualified maintenance staff check the input supply and the rack rail under load separately.
If the fault appears when a programmer is connected, record the 500 interface suffix and the existing Mint connection. Compare the cabinet drawing with figure 31.
For a used unit, ask for the 5 V reading under load, the test rack order number and a photo of the rear connection.
OtomasyonAVM resources and PDFs
+ SIMATIC S5 90/110 modules · S5-110A CPU 900
+ OtomasyonAVM Siemens S5 PDF archive
Related topics
+ 6ES5 930-7AA11 · 6ES5 930-7AA12 · 6ES5 930-7AA31 · 6ES5 930-8MD11
Browse Siemens S5
+ SIMATIC S5 power supplies · SIMATIC S5 · Used Siemens automation equipment
Selling this power supply? Send a nameplate photo, quantity, operating condition and asking price to otomasyonavm@gmail.com.
External references
+ Siemens S5-110A Operating Instructions, 6ES5 998-0AA22 · Page 2.8 shows the connection arrangements. Page 6.2 lists the fuses.
+ Niemann Siemens S5 parts list · Exact-order-number listing for 115 V AC and 5 V DC at 0.7 A.
+ 6ES5 930-7AA21 nameplate and front-panel photos · River City Industrial parts listing.