Siemens 6ES5 393-0UA11 – OP 393 Handheld Operator Panel
Siemens 6ES5 393-0UA11 is an OP 393 operator panel with a two-line LCD, 16 characters per line, and a physical keypad. It is used with SIMATIC S5 PLCs to view and change timer and counter settings and display process messages. Among Siemens operator panels, it is a legacy portable HMI device.
Its interface is serial TTY, a 20 mA current loop, and its supply specification is 5.2 V / 0.5 A. Power is supplied through the PLC connecting cable. Within the S5 system, the panel communicates with the CPU; it is not addressed as an I/O board installed in a rack slot.
TTY interface and cable selection
The panel connects to the PLC's programming/operator interface through the appropriate cable. TTY is electrically different from RS-232 and RS-485. A matching connector shape does not establish compatibility. Check the pin assignment and supply conductors of the S5 cable against the actual interface arrangement.
5.2 V describes the panel supply; the TTY interface's 20 mA describes the communication current. These serve different purposes. Do not apply 24 V directly to the panel connector. When selecting an extension or converter, verify both the signal connections and the power path.
PLC compatibility and the 984 adapter
Siemens' OP 393 / OP 393-II connection table shows adapter-free connection to the S5-95U, S5-100U, S5-101U and S5-115U. The updated German table identifies the supported S5-115U group as CPUs 941–944. Check the complete order number of the installed S5 CPU family.
For the same older panel family, the S5-90U, S5-135U and S5-150U require a 984 cable adapter. The manual also requires a 984 adapter for cable lengths exceeding 3 m. S5-115U CPU 945 and S5-155U are unsupported in the older OP 393 / OP 393-II column; compatibility listed for later OP 393-III versions must not be assigned to 0UA11.
Functions and software version
The basic functions concern internal PLC timers, counters and process messages. Establish how the PLC program uses those values. If the program overwrites a setting entered through the panel, that behaviour does not by itself indicate a faulty panel.
The OP 393 family manual describes data-word and diagnostic functions from V2.0 onward, and additional texts, flag control and password protection for input functions from V3.0 onward. These are version-dependent capabilities. The 0UA11 order number alone does not establish that every function is available. Record the startup software version together with the hardware label.
The manual's DB6 initialization parameters also belong to V2.0 and later and are held in a PLC data block. Where an application uses this arrangement, preserve the relevant block structures during panel replacement. Assess menus and diagnostics against the actual panel version.
Differences from 0UA12, 0UA13 and 0UA15
0UA11 and 6ES5 393-0UA12 are specified at 5.2 V / 0.5 A. The German technical table places 6ES5 393-0UA13 and 6ES5 393-0UA15 in the 5.2 V / 0.1 A group. The suffix matters for consumption and connection options; panels with a similar appearance should not automatically be treated as interchangeable.
Dimensions, protection and panel mounting
Housing dimensions are 200 × 120 × 45 mm, with an approximate weight of 700 g. The specified operating range is 0–45 °C, with storage at −20 to +55 °C. Standard protection is IP50; the manual specifies IP54 for panel installation using the appropriate 6ES5 982-3UA11 mounting frame. Housing dimensions must not be used as panel cutout dimensions.
Check the frame seating, cable entry and grounding arrangement together. Connection and configuration details for the different 6ES5 396-0UA11 OP 396 operator panel must not be applied directly to the OP 393.
Editor's note
A readable display is only the start of a useful test. Check every key, especially number entry, clear and enter, for missed presses or double registration.
Photograph the startup model and software version. Before treating a missing menu as a fault, establish whether that version supports the function shown in the newer manual.
During communication troubleshooting, include the cable and connector. If moving the cable interrupts operation, inspect the entry point and pins; the same connection also carries panel power.
Record the existing timer or counter setting before changing it. Test in a suitable controlled arrangement: confirming a random value on an operating machine can change the process setting.
For backup, retain more than photographs of the panel. Preserve the CPU project, relevant data blocks and installed S5 memory arrangement. Seeing the same screen after replacement does not establish that every setting is correct.
When buying used Siemens equipment or a used HMI, request a clear 393-0UA11 label, a readable LCD, working keys and a communication test with a suitable PLC. Confirm whether the cable and any required 984 adapter are included.
OtomasyonAVM resources and PDFs
Browse the S5-115U PDF archive for existing family documents and About Siemens S5 PLC for system background. The OP 393-specific manufacturer manuals are linked below. Match functions described for later software versions to the actual panel revision.
Related topics
+ 6ES5 393-0UA12: OP 393-II operator panel.
+ 6ES5 393-0UA13: a lower-consumption version in the OP 393 family.
+ 6ES5 393-0UA15: OP 393-III; check its connection and version requirements separately.
+ 6ES5 982-3UA11: OP 393 panel mounting frame.
Browse Siemens equipment
Siemens S5 PLC · Siemens HMI · S5 cables · S5 interfaces · S5 additional modules · Used Siemens equipment
Manufacturer documents and external references
+ Siemens OP 393 Handbuch – EWA 4NEB 810 1180-01g, German: printed page 1-1 covers connections and CPU compatibility; 2-1 gives specifications and exact order numbers; sections 2.5–2.7 cover the keypad, display and operation.
+ Siemens OP 393 Operator Panel Manual – EWA 4NEB 810 1180-02f, English: third-party archive copy of the manufacturer's manual. Printed page 1-1 covers adapters; 2-1 gives supply and specifications; 2-6 covers the display; chapter 3 explains version-dependent initialization.