6ES5 393-0UA15
Siemens 6ES5 393-0UA15 OP 393-III Operator Panel
The Siemens 6ES5 393-0UA15 is an OP 393-III operator panel with a two-line, 16-character-per-line LC display. 6ES5 393-0UA15 provides timer and counter operation, message display and, in suitable applications, data-word entry for SIMATIC S5 systems. This model in the Siemens operator panel range is portable and uses numeric and function keys.
When selecting an HMI or operator panel, consider its data mapping within the PLC application as well as the hardware. OP 393-III works with the relevant data blocks in the S5 PLC. In a PLC and HMI application, meaningful values depend on the CPU program and panel parameters agreeing.
Power supply and TTY connection
The specified supply is 5.2 V at 0.1 A, obtained from the PLC through the connecting cable. Communication uses a serial TTY current-loop interface. Check cables and connectors together with interface compatibility; matching Sub-D connectors alone do not establish a suitable connection.
Siemens requires a 984 line adapter for cable lengths above 3 metres. An appropriate 984 adapter arrangement is also required for an S5-150U connection. Select the exact adapter, supply arrangement and cable according to the CPU connection table.
CPU compatibility and panel version
The Siemens connection table covers families including S5-90U, S5-95U, S5-100U and S5-115U, with panel-version conditions. S5-115U CPU 945 and S5-155U require OP 393-III V3.1. Record the Vx.y version shown during startup before approving a unit solely from its OP 393-III designation.
S5-101U has a restricted function set: the manual specifies timer and counter operation and diagnostics. Do not assume that every data-entry or message function available with other CPUs also applies to that system.
Function keys and DB6 configuration
TMR, CTR, TXT, DB, DIA, FCT and TST cover timers, counters, messages, data entry, diagnostics, flag control and device tests. Availability depends on the panel version, CPU and application data blocks. Version V3.0 introduced additional text configuration and password protection for input functions.
DB6 is the panel parameter data block. It is read during startup; changes to DB6 are not automatically detected while the OP is running. Preserve the existing block and compare it with the structure for the correct version. The manual's *89 indication can also relate to missing or incorrectly configured data blocks.
Basic operation without DB6 can use default assignments, including DB11 for TMR and DB12 for CTR. These are documented defaults, not addresses to copy directly into an existing project. Also check the required DB5 structure for the diagnostic function.
Mounting, protection and environment
The device can be used handheld, on a desk or with a suitable mounting arrangement. Siemens specifies IP50, or IP54 with the mounting frame. Assess the 6ES5 982-3UA11 mounting frame and sealing arrangement together. Dimensions are 200 × 120 × 45 mm, weight is approximately 700 g, and the operating temperature range is 0–45 °C.
Comparison with related panels
6ES5 393-0UA11, 6ES5 393-0UA12 and 6ES5 393-0UA13 are different order codes within the family. The manual lists 0.5 A supply current for 0UA11/0UA12 and 0.1 A for 0UA13/0UA14/0UA15. Compare complete codes, software versions and connection requirements together.
6ES5 395-0UA11 and 6ES5 396-0UA11 are other S5 operator panel options. They must not be assumed to be direct replacements for the same project; review connections, data mapping and operating functions separately.
Replacement planning should also cover CPU memory cards, the PLC application and current parameters. Reduce the risk of data loss by retaining recoverable copies of relevant project blocks, including DB5/DB6, and the machine settings.
Editor's Note
Ask to see both the rear label and the startup screen showing OP 393 III and Vx.y. The version matters particularly for CPU 945 or S5-155U applications. Keep a photograph with the replacement records.
Check both display lines and every key individually. Faint characters, missing dots, stuck keys or an unreliable ENT key can cause problems during operation. Include the manual's display and keyboard tests in the assessment.
If the panel will not start, first check the cable, connector and supply from the PLC. This model uses a 5.2 V supply; do not connect an arbitrary 24 V source. Remember the 984 adapter requirement for longer cables.
An *89 indication does not immediately establish a hardware fault. Check the expected CPU data blocks, DB6 structure and assignment for the selected function. Do not overwrite a working machine's DB6 with a block copied from another project merely to test the panel.
First confirm communication by reading values. Test write functions in a controlled manner with the machine in a safe condition: changing a timer, counter or flag can change the process. Retain the original values and a project backup.
OtomasyonAVM resources and PDF documentation
Use About Siemens S5 PLC for system information and the Siemens S5 PDF archive for documentation. For this model, refer to the version and CPU connection table in OP 393 Handbuch, 6ES5 998-0UQ12 / EWA 4NEB 810 1180-01g.
Related topics
Siemens HMI panels · S5 cables and connectors · S5 memory cards · HMI and operator panel types
Navigation: 6ES5 393-0UA15 model page | SIMATIC S5 main page | Siemens S5 PLC models | Used Siemens products
Siemens documents and external references
Siemens OP 393 Handbuch — German PDF: chapter 1 for CPU and version compatibility; chapter 2 for supply, display and connections; chapter 3 for DB6; chapter 9 for device tests.