6ES5 454-4UA11

Siemens 6ES5 454-4UA11 — 16-Channel, 24 V DC / 2 A Digital Output Module

6ES5 454-4UA11 is a 16-channel, 24 V DC / 2 A electronic digital output module for the Siemens SIMATIC S5 U range. On this older model in the S5 digital output range, all 16 outputs form one galvanically isolated group. The permissible field-supply range is 20–30 V DC.

The SIMATIC S5 U Periphery manual identifies the exact 4UA11 code in §5.12. Siemens SINUMERIK 810/820 GA3 lists also show it as 16 outputs, 2 A and 40 mm wide, alongside add-on order code 6FC3 988-4DJ. Check the existing S5 rack and machine configuration before ordering.

Supply, channel current and total load

Use a suitable 24 V DC power supply for the field circuit, and check L+ feeds, the L− return and grounding against the diagram. The switching-current range for resistive and inductive loads is 10 mA–2 A per channel. The specified maximum total switching current is 4 A per four outputs.

The manual gives a 50% diversity factor; do not assume continuous 2 A loading on all 16 channels. When assessing contactors and valve coils, include the other loads in the same group as well as individual channel current. Lamp switching is separately limited to 0.45 A / 10 W.

Fuses and short-circuit indications

The specified protection uses one 6.3 A slow fuse per four outputs. Preserve the correct fuse characteristic on this current-limited module. If a fuse blows or a short-circuit indication appears, inspect the field wiring and load. There is one galvanic group, while fusing and short-circuit monitoring are arranged in four-output groups.

Green LEDs display channel status, while red LEDs indicate short circuits for each four-output group. An H+ short-circuit signalling output is also provided. When checking the signalling function, verify the manual’s specified 1L+ supply; an indication alone does not establish correct operation at the load.

Switching frequency and low-current loads

The maximum switching frequency for resistive loads is 100 Hz. For inductive loads, the limits are 0.2 Hz at 1 A and 0.1 Hz at 2 A. Do not plan rapid coil switching from the 2 A rating alone. Off-state leakage is maximum 1 mA, so interpret off-state measurements carefully when using low-current loads.

Front connector and enable input

The manual’s connector table lists the 40 mm wide, 25-pin screw-terminal 6ES5 497-4UB22 for the 454. When comparing the 497-4UB22 front connector and existing S5 wiring, match the supply terminals, F+/F− and H+ connections to the exact model’s diagram.

The F+ enable input is rated 24 V DC. Its “1” range is 13–33 V and its “0” range is −33–5 V. The manual specifies the enable-mode selection jumper only for 4UA12; that setting must not automatically be applied to 4UA11.

Program and field checks

Match the output address in the PLC program to the physical channel. Seeing the command change in the programming software does not establish correct load supply or switching. Where necessary, follow the logic from the relevant digital input condition, then test the output with a suitable load under safe conditions.

During troubleshooting, assess the channel LED, four-output fuse group, L+ supply, enable and load return together. Use the S5 system structure to distinguish a shared supply fault from a single-channel failure. Isolate system and field power before disconnecting wiring.

Comparison with nearby order codes

The 6ES5 454-4UA12 is covered alongside this model in the older manual, with the enable-mode difference explained separately. For comparisons with 6ES5 454-4UA13 and 6ES5 454-4UA14, verify the complete revision, terminal arrangement and manufacturer’s matching information. A similar model name alone does not establish direct interchangeability.

Editor’s note

Keep the 4UA11 suffix in view when choosing this board. Applying a later revision’s settings to the older unit can make a straightforward job take longer. Clear photographs of the label, connector and wiring before removal are a useful starting point.

If trouble began after adding a valve, calculate the group current first. Four outputs have a combined limit of 4 A; a 2 A channel rating does not make that group an 8 A supply. A small load calculation can save an unnecessary board replacement.

A red indication does not immediately condemn the board. A damaged cable, shorted coil or incorrect connection on one of the four channels may be responsible. Find the field-side cause before exposing a replacement board to the same fault.

If the green light is on but the valve does not operate, check at the load. Does the supply sag, is the return sound, and are you watching the correct channel? Seeing an indication and confirming useful power at the field device are separate checks.

When buying a used Siemens 454-4UA11, ask for all sixteen channels to be tested with suitable DC loads. Include enable, fuse groups and short-circuit signalling in the checks. A clean older board is welcome; a proper working test tells you much more about what you are buying.

OtomasyonAVM resources and PDFs

+ S5 digital output modules · 497-4UB22 front connector · S5 racks and expansion units.

+ OtomasyonAVM shared Siemens S5 PDF archive. U Periphery, §5.12, pp. 59–61 covers the exact 4UA11/4UA12 codes, electrical limits and wiring diagram. Consult the same manual’s §3.2 connector table for front-connector selection. The source is in English.

Related topics

+ 454-4UA12 · 454-4UA13 · 454-4UA14 · 497-4UB22 · Fuses.

Navigation

+ S5 digital output modules · SIMATIC S5 · Siemens S5 PLC · Used Siemens.

Siemens and external references

+ Siemens U Periphery — English; 6ES5 998-0PC22, §5.12, pp. 59–61: 454-4UA11/4UA12 ratings, enable distinction and wiring diagram.

+ Siemens SINUMERIK 810/820 GA3 Installation Lists — English; §1.2–1.3, p. 1-3: 454-4UA11, 16 outputs / 2 A / 40 mm and 6FC3 988-4DJ listing.