6ES5 454-4UA13 – SIMATIC S5 16-Channel 24 V DC / 2 A Digital Output Module
Siemens 6ES5 454-4UA13 is a 16-channel digital output module rated at 24 V DC and 2 A per channel for the S5-135U/155U family. Within the S5 digital output module range, it provides short-circuit-protected DC load switching. In a Siemens S5 system, all 16 outputs form one galvanic isolation group; the channels are not individually isolated from one another.
The permissible field supply is 20–30 V DC, and the channel current range is 10 mA–2 A. Match the field power supply and load currents in the SIMATIC S5 installation. Observe the 4 A total limit for each four outputs and the manufacturer’s 50% coincidence-factor requirement; do not assume continuous operation at 16 × 2 A.
Load type and switching limits
The maximum switching frequency is 100 Hz with resistive loads, but 0.2 Hz at 1 A or 0.1 Hz at 2 A with inductive loads. This distinction matters for loads such as contactor coils. The lamp-load limit is 0.45 A / 10 W, rather than the general 2 A channel rating.
Power dissipation at rated operation is specified as 17.5 W. Assess airflow and simultaneous loading in the control panel. With low-current loads, also account for an OFF-state residual current of up to 1 mA.
Fuse selection specific to 4UA13
The 454-4UA13 uses one 6.3 A slow-blow fuse for every four outputs. Keep fast and slow-blow fuse characteristics distinct. The 7 A fast fuse listed for 454-4UA14 must not be assigned to this revision.
During fuse checks, preserve the specified operating characteristic as well as the current rating. Examine the load and cable before simply replacing a blown fuse. Short-circuit protection depends on the manufacturer’s line and circuit conditions.
Enable input and common fault output
The F+/F– enable input permits module operation when the enable circuit is active. If all outputs are inactive, include the supply, enable voltage and existing X20 jumper position in troubleshooting. Record the module’s address switch and field wiring before changing the PLC program.
A red LED indicates a short circuit for four outputs. The H+ output provides a common short-circuit signal for the module; it does not identify an individual channel address. The 1L+ supply is important for H+ operation. Assess the output command, indicator and actual load switching together.
Subrack and front connector
The 4UA13 housing measures 40 × 255 × 195 mm. Select the S5 subrack and front connector for the actual installation. One suitable screw-terminal option is 6ES5 497-4UB12, with a 40 mm width and 42 contacts. Use in S5-115U requires an adapter casing and a suitable slot arrangement.
Preserve the grounding and L– reference arrangement. The 453-4UA12 and 451-4UA13 have different output structures and current specifications. Match the complete code, load conditions, fuse, connector and enable arrangement when replacing a module.
Editor’s note
Read the full label on this S5 module: 454-4UA13. Take your time when comparing it with UA14. Check the fuse and housing differences before deciding that a replacement will fit.
“2 A per channel” does not mean every channel can run at 2 A simultaneously. Calculate the four-output load limit and simultaneous loading first. If a module overheats, check the load distribution before replacing it.
If four outputs stop working together, check that section’s supply, 6.3 A slow-blow fuse and load wiring. If the fuse blows again, find the cause instead of increasing its rating.
If all sixteen outputs are inactive, check the F+/F– enable circuit and existing X20 setting before changing the CPU program. Record the working arrangement; random jumper changes can add another fault.
For a used Siemens spare, ask about load testing of all 16 channels and the front connector’s condition. Photograph the address and wiring before removal, and isolate power before replacement. Understand the existing arrangement first, then work through one step at a time.
OtomasyonAVM resources and PDFs
+ S5 digital output modules · 497-4UB12 front connector · S5 subracks.
+ Siemens S5 PDF archive. The detailed specifications for this model appear on pages 8-54–8-55 of the English S5-135U/155U manual linked below.
Related topics
+ 454-4UA14 · 453-4UA12 · 451-4UA13.
+ Fast and slow-blow fuses · Contactors · PLC troubleshooting.
Browse SIMATIC S5
S5 digital outputs · S5 cables and connectors · SIMATIC S5 · Siemens S5 PLC · Siemens second-hand main page