6ES5 453-4UA11

Siemens 6ES5 453-4UA11 – 16-Channel Isolated Digital Output Module, 24 V DC / 2 A

The 6ES5 453-4UA11 is a 16-channel, 24 V DC / 2 A transistor output module in the SIMATIC S5 U-periphery family. Part of the S5 digital output range, it transfers CPU commands to DC field loads. Each of the 16 outputs is individually galvanically isolated. The wiring arrangement permits L+ or L− switching.

Nominal load voltage is 24 V DC, with a permissible range of 20–30 V DC. Switching current is 10 mA–2 A. Size the power supply for the actual field load, and check rack power, load power and the enable circuit separately.

Individual channel wiring and load selection

Follow the diagram for each channel's supply and load connections. Common supply links in the wiring assembly can externally join otherwise isolated channels. Assess grounding and reference connections against the existing project. When selecting an interface relay or coil load, check continuous current and inrush.

F+/F− enable input and fault signalling

F+/F− is the module's 24 V DC enable input. A PLC output command alone is insufficient; the enable circuit must also receive the correct supply. Do not assume that the 4UA12 enable-mode jumper exists on the 4UA11. A common red indicator and isolated H+/H− signalling output report short-circuit or overcurrent conditions; check the signalling circuit's separate supply.

The module combines current-limited outputs with individual fusing. Siemens specifies 16 × 2.5 A slow-blow fuses. Correct the load or wiring fault before replacing a fuse. Do not fit a larger fuse to suppress the symptom.

Cooling and simultaneous output operation

For rated-load operation, Siemens specifies 100% simultaneity with a fan, 25% without a fan, or 50% without a fan up to 20 °C. This refers to the number of outputs on simultaneously. Check fan operation and cabinet temperature instead of assuming every channel can operate at full load simply because it is rated for 2 A.

Maximum switching frequency is 100 Hz for resistive loads and, for inductive loads, 0.2 Hz at 1 A or 0.1 Hz at 2 A. Check the required coil switching rate against these limits.

40 mm module and front connector

The module is 40 mm wide. The Siemens U Periphery table lists the 497-4UB12 as a 42-pole, 40 mm screw-terminal front connector for the 453. Do not treat other 497 codes such as the 497-4UA12 or 497-4UB31 as interchangeable merely because their pole counts match; check width, termination type and coding together.

Addressing and spare selection

The 16 outputs occupy two consecutive output bytes. Set the start address using the module's addressing switch and match it to the PLC program. During testing, check the actual load response and any digital input feedback. During troubleshooting, examine the address, F+/F− enable and load supply together.

The 453-4UA12 is covered in the same technical section, but version differences include enable settings and isolation test values. The 454-4UA11 and 457-4UA12 also have different output arrangements. “A 16-output S5 card” is insufficient identification for a replacement.

The 453-7LA11 and 453-8MA11 belong to different S5 module families. Specify the complete 6ES5 453-4UA11 code, hardware version and front-connection photograph when requesting a spare. Disconnect system and load supplies before removal or installation.

Editor’s note

Individual output isolation is a useful feature of this card. Inspect the existing supply links before changing them. Adding a common connection may simplify the wiring while also changing the machine's original isolation arrangement.

If none of the outputs works, start with the F+/F− enable supply before condemning the card. A correct program and healthy load cannot compensate for a missing enable signal. A simple supply check can save an unnecessary replacement.

A 2 A rating does not mean every output can always carry that current simultaneously. Fan-cooled and uncooled operation have different limits. Check the rack fan as carefully as the replacement card; a failed fan can remain unnoticed in an older installation.

If a fuse has opened, inspect the cable, coil and suppression component before replacing it. Look for crushed insulation, a faulty load or reversed suppression polarity. Increasing the fuse rating can put more strain on the card.

Where practical, test a used module's 16 channels, enable input and fault signalling with a suitable setup. Ask whether the front connector is included. Keep photographs of the original address setting and label to make installation easier.

OtomasyonAVM resources and PDFs

+ Siemens S5 PDF archive: our documentation page. The relevant technical source for this model is the U Periphery manual below.

+ S5 digital output modules · S5 racks · S5 cable types

Related topics

+ 453-4UA12 · 454-4UA11 · 457-4UA12: version and output-arrangement comparisons.

+ 497-4UB12 front connector · PLC programming · PLC troubleshooting

Browse SIMATIC S5

S5 digital output modules · S5 racks · Siemens S5 PLC · Used Siemens equipment

Siemens and external references

+ Siemens U Periphery – English, 6ES5 998-0PC22: digital I/O section 5.11, printed pp. 56–58 / PDF pages 259–261; explicitly covers both 4UA11 and 4UA12. Enable circuits are in Section 1.3.5, addressing in Section 3.1 and front connectors in Figure 9. Third-party archive copy of a Siemens publication.

+ Siemens 6ES5453-4UA11 product record – English: exact ordering code, compact U design, 16 isolated outputs and 24 V DC / 2 A description.