6ES5 453-8MA11
Siemens 6ES5 453-8MA11 – 8-Channel 5–24 V DC / 0.1 A Digital Output Module
6ES5 453-8MA11 is a Siemens SIMATIC S5 module with 8 transistor outputs, a nominal load voltage of 5–24 V DC and a rating of 0.1 A per channel. Within the S5 digital output range, it serves low-current signal and interface circuits. The permitted load supply range, including ripple, is 4.75–30 V DC.
Isolation and output configuration
The outputs form one optocoupler-isolated group of eight; the individual channels are not independently isolated. When driving a low-current input, such as a channel on the 6ES5 433-8MA11, check voltage levels, current direction and common-terminal arrangements together.
Siemens catalog ST 50 identifies source or sink versions for this code and instructs the reader to check the front panel. The S5-100U manual illustrates a TTL-compatible open-collector version switching to M potential. Confirm the installed card’s output direction before connecting it to digital inputs or combined input/output modules.
Current limits and short-circuit protection
The nominal output current is 100 mA per channel, with a catalog total of 0.8 A. There is no internal short-circuit protection. Use a suitable load and a current-limited setup when testing a used output module; assess coil pickup current and other inrush demands against the 100 mA limit.
Supply and switching specifications
Choose the load power supply using the nominal 5–24 V DC range, the receiving circuit’s requirements and its common reference. Arrange grounding and M connections according to the system wiring plan. Operation with a 5 V supply does not mean that the output automatically generates 5 V under every supply condition.
The maximum switching frequency is 100 Hz for resistive loads and 2 Hz for inductive loads. The catalog gives an off-state residual current of 0.1 mA maximum. Do not transfer the load ratings of cards such as 6ES5 451-8MA11 or 6ES5 441-8MA11 to this model.
Bus module and installation
The card plugs into a suitable bus unit; 6ES5 700-8MA11 is a bus module from this system family. Prepare field cables and connections for the bus unit’s terminal arrangement. Match mechanical coding and slot addressing to the existing installation.
Catalog ST 50 lists the module in the S5-90U, S5-95U/F and S5-100U family. For an S5-90U CPU or another SIMATIC S5 system, check the CPU’s expansion requirements. This is a standard digital output card; inclusion in the S5-95F module table does not make it a failsafe output.
The ET 100U manual also lists this model. In a distributed I/O arrangement, assess interfaces such as IM 316-8MA12 and IM 318-8MA12 against the station’s wiring and addressing plan. Do not assume that a central-system slot address remains valid when moving the module to another station.
Operating conditions and used-module inspection
The S5-100U manual permits ambient temperatures of 0–60 °C for horizontal installation and 0–40 °C for vertical installation. Maximum unshielded cable length is 100 m, typical power loss is 1 W and approximate weight is 220 g.
Back up the program and memory unit before replacement, and record the existing S5 system’s I/O addresses. Loaded checks of all eight channels, output direction and common terminals provide more useful evidence than unloaded voltage readings alone.
Relay-contact cards such as 6ES5 452-8MR11 have a different connection arrangement from this transistor output. For used Siemens modules, state the label details, version, physical condition, included parts and channel-test results for the individual item.
Editor’s note
Check the output direction first. A matching order number is a starting point. Read the front panel and existing drawing to establish whether the card is source or sink, then check that the receiving circuit matches.
Keep the 100 mA rating in mind. Even a small coil can draw more current during pickup than expected. Check the load’s label and specifications before connecting it directly.
Give the test setup its own current limit. This model has no internal short-circuit protection. A suitable current limit helps avoid damaging a sound channel while testing it.
Take a moment over the 5 V connection. An open-collector output is not a self-contained 5 V source. The supply, load and common reference must work together before a measurement tells you much.
Finish by checking all eight channels. One working output does not establish the condition of the whole card. Save the program first, test each channel with a suitable load and keep a short record of the results.
OtomasyonAVM resources and PDFs
+ Shared SIMATIC S5 manuals and PDF archive
+ S5 digital output modules and model pages
Related topics
+ 6ES5 433-8MA11 digital input module
+ 6ES5 451-8MA11 digital output module
Browse SIMATIC S5
+ Back to S5 digital output modules
+ Used Siemens products and models
Siemens and external references
+ Siemens S5-100U manual – 453-8MA11 wiring and specifications, 14-33 (English)
+ Siemens ST 50, 1998 – source/sink version and front-panel check, 2/30 (English)
+ Siemens ST 50 – 453-8MA11 technical table, 2/32 (English)
+ Siemens ET 100U manual – module list and 453-8MA11, 2-2 and 2-31 (English)