The Siemens 6ES5 444-3AA11 is a 16-channel, 24 V DC / 2 A digital output module for SIMATIC S5 systems. Within the S5 digital output range, it is a compact K version without galvanic isolation.
The nominal load supply is 24 V DC, with a permitted range of 20–30 V DC. Outputs are arranged in four L+ supply groups of four channels. The 2 A per-channel rating must be used alongside the maximum total current of 4 A per group.
Group current and fuses
Add the load currents separately for each group. Four loads drawing 2 A each would total 8 A and exceed the 4 A limit. Siemens ST 53 specifies 50% loading at 55 °C relative to the sum of nominal currents through each L+ supply.
The module has electronic short-circuit protection and a T4 A time-delay fuse for each of its four groups. Match the fuse current rating and operating characteristic. Investigate a repeatedly blown fuse instead of increasing its rating.
Non-isolated outputs and load selection
Because the board has no galvanic isolation, wire the load return and cabinet grounding according to the existing diagram. When reviewing NPN/PNP connection principles, do not treat these outputs as potential-free relay contacts.
Check pickup current for relays and contactor coils; use a suitable interposing relay and socket where required. Maximum switching frequency is 100 Hz for resistive loads and 2 Hz for inductive loads at nominal loading.
Mounting space, addressing and connections
For this approximately 40 mm-wide board, ST 53 specifies two mounting positions. Check the rack arrangement and front connection. Label cables and connections before removal rather than assuming the layout of a narrower board applies.
Photograph the address socket and jumper settings. Compare the output addresses in the PLC program with the board’s existing configuration. During troubleshooting, verify the command, group supply and load voltage in sequence. Do not move jumpers randomly as a trial.
Comparison with related models
Check the mechanical arrangement and channel layout of the 444-5AA11, 445-3AA11 and 445-3AA12 separately. Sharing the 444 or 445 designation does not establish direct interchangeability.
The 451-3AA11 and 450-3AA11 have different isolation and output-current characteristics. Review the 454-4UA11 against its own rack and wiring requirements as well. Select a spare using the full code, load limits and connection arrangement together.
Editor’s note
Keep the 4 A group limit beside the 2 A channel rating when assessing this board. Writing the loads down in four groups makes it much easier to see where the current is adding up.
If outputs in one group disappear together, begin with that group’s supply and fuse. Checking the shared connection first can save condemning the entire board.
If a fuse blows repeatedly, let us find the cause rather than fit a larger one. Inspect the wiring, coil current and possible short circuits. Removing the cause also protects the replacement from repeating the same failure.
Before removal, photograph the label, address socket, jumpers and front connection, and back up the program. Switch off power and follow the system instructions for replacement. Recording the original settings now is easier than relying on memory later.
For a used digital output board, ask for all 16 channels across all four groups to be checked with suitable loads. Agree on the test voltage and load. An LED check does not replace a test under load.
OtomasyonAVM resources and PDFs
+ About Siemens S5 PLCs · Siemens S5 PDF files — our manual archive. Manufacturer documents for this model appear below.
Related topics
+ 444-5AA11 · 445-3AA11 · 445-3AA12 · 451-3AA11 · 454-4UA11
Browse SIMATIC S5
+ S5 digital output modules · SIMATIC S5 · S5 racks · Used digital I/O modules · Siemens second-hand equipment
Siemens and external references
+ Siemens ST 53, 1985 — 8/12: compact 444-3 specifications and loading limit (German, archived copy)
+ Same catalogue — 8/24: four L+ groups and connection arrangement