6ES5 441-4UA12
Siemens 6ES5 441-4UA12 – 32-Channel 24 V DC Digital Output Module
Siemens 6ES5 441-4UA12 is a 32-channel, 24 V DC / 0.5 A digital output module for the SIMATIC S5 U range. The permitted load supply is 20–30 V DC. This S5 digital output module is non-isolated and uses a common M reference; the manufacturer’s diagram requires the load supply’s L− terminal to be connected to system M.
The switching current range for resistive and inductive loads is 5 mA–0.5 A per channel, with a 4 A maximum per eight outputs. Include the ventilation-dependent simultaneous-load limit in the load calculation alongside these ratings.
Ventilation, simultaneous loading and switching rate
The specified simultaneous-load factor is 100% with a fan, and 50% without a fan, increasing to 100% up to 35 °C. Assess the rack layout and airflow accordingly. Do not assume that all channels can operate at full load at every temperature.
The maximum switching frequency is 100 Hz for resistive loads. For inductive loads, it is 2 Hz at 0.3 A or 0.5 Hz at 0.5 A. Lamp loads have a separate 5 W maximum rating.
Eight-channel fuses and H+ fault signaling
There is one 6.3 A slow-blow fuse per eight outputs. Assess the fuses together with the electronic short-circuit protection. The manual specifies a maximum line resistance of 15 Ω for the electronic protection to respond.
The red short-circuit LEDs monitor groups of eight outputs. H+ is the common fault-signaling output, and 1L+ must be supplied for this function to operate. These protection groups are not galvanically isolated output groups.
F+ enable input, X20 and supply consumption
The F+ enable input is referenced to M. Its rated voltage is 24 V DC, with a logic “1” range of 13–33 V. On UA12, F+ is active when the X20 jumper is fitted, which is the factory setting. Compare the existing jumper position with the machine drawings and enable arrangement.
The digital section draws 80 mA typical from the 5 V system rail. Module consumption from the external 24 V L+/L− rail is 150 mA typical. Include these currents in the S5 power-supply calculation in addition to field-load current.
42-pin front connection and address checks
Match the S5 cables and connectors to the existing termination type. The 42-pin screw-terminal option is 6ES5 497-4UB12. The 20 mm crimp connector 6ES5 497-4UA12 appears in the fan-cooled installation table; check the connector and mounting width separately for an unventilated installation.
M is the signal and supply reference. Keep its role distinct from protective grounding and preserve the reference arrangement in the drawings. Include the common return, shielding and loose contacts when investigating electromagnetic interference.
The 32 channels occupy four output bytes. Compare the address switch with the byte and bit addresses in the PLC program. During troubleshooting, test each channel separately under load. In an expansion unit, also review the interface module and address arrangement of the existing Siemens S5 system.
441-4UA11, UA13, UA14 and 451-4UA12 differences
Do not assume that the 441-4UA11 has the UA12 enable-mode selection feature. Check the 441-4UA13 and 441-4UA14 ratings separately; the UA14’s 7 A fast fuse must not replace the UA12’s 6.3 A slow-blow fuse. The 451-4UA12 is a different, galvanically isolated model. Check both the 441/451 designation and the final two digits when selecting a spare.
Editor’s note
Start by reading the full 441-4UA12 marking. This card uses a common M reference. A 451 card having 32 outputs does not make it identical; comparing the supply and isolation arrangements now is easier than untangling a mismatch later.
If the program commands outputs but they do not respond, measure F+ relative to M. Record the existing X20 position too. Avoid changing the jumper while searching for a fault; establish its role in the machine first.
If eight channels fail together, check the group fuse, supply and field wiring first. Remember the 1L+ supply when expecting an H+ fault indication. A missing supply should not be mistaken for a failed card.
All 32 channels operating is useful evidence, but their loading matters too. Review cabinet temperature, fan operation and simultaneous loads together. A short bench test does not reproduce every condition of sustained operation in a warm cabinet.
When buying a used Siemens card, request on/off testing of all 32 channels. Include the correct fuses, connector contacts and evidence of previous repair. A successful test of the first few outputs does not establish the condition of the rest.
OtomasyonAVM resources and PDFs
+ S5 digital output modules · About Siemens S5 PLC
+ Siemens S5 shared PDF archive and operating manuals. For the exact UA12 version, use the ratings and wiring diagram in U Periphery, section 5.9.
Related topics
+ 6ES5 441-4UA11 · 6ES5 441-4UA13 · 6ES5 441-4UA14: revisions within the same family.
+ 6ES5 451-4UA12: a different, galvanically isolated model.
+ 6ES5 497-4UB12 · 6ES5 497-4UA12: front-connection options to be matched to installation conditions.
Browse SIMATIC S5
+ S5 digital output modules · S5 racks · SIMATIC S5
+ Siemens S5 PLC · Siemens second-hand equipment
Siemens and external references
+ Siemens U Periphery – English; 6ES5 998-0PC22, Release 01. Section 5.9, printed pages 50–52 / PDF pages 253–255 cover the exact 441-4UA11 / 441-4UA12 ratings, common M connection and X20 note. Section 3.2 covers front connectors.
+ Siemens S5-135U/155U System Manual – English; C79000-G8576-C199-07. Section 8.4.9, printed pages 8-48–8-49 / PDF pages 362–363 compare UA13/UA14 and identify the UA14’s different fuse and consumption ratings.