6ES5 441-4UA11
Siemens 6ES5 441-4UA11 – 32-Channel 24 V DC Digital Output Module
6ES5 441-4UA11 is a 32-channel electronic digital output module rated at 24 V DC / 0.5 A in the Siemens SIMATIC S5 family. This S5 output module has no galvanic isolation. Outputs form four groups of eight, with a maximum combined current of 4 A per eight outputs.
It belongs to the U-type SIMATIC S5 peripheral range, designed for S5-135U, S5-150U and S5-155U systems and their associated expansion racks. Check the S5 system architecture, rack and wiring against the complete order number. Typical loads include suitably rated valves, relay and contactor coils, and indicator lamps.
Supply and channel ratings
Nominal load supply is 24 V DC, with an operating range of 20–30 V DC. Include field loads when checking the power supply and PLC supply. The specified switching-current range per channel is 5 mA–0.5 A; the lamp-load limit is 0.22 A / 5 W.
Output voltage is at least L+ − 1.5 V when on and at most 3 V when off, with maximum off-state leakage of 0.5 mA. Check coil inrush current when selecting a contactor or control relay. Assess inductive loads such as a relay coil beyond their continuous-current rating.
Group current, fuses and ventilation
The 0.5 A channel limit and 4 A group limit apply together. Each group of eight outputs has a fuse. For fuse replacement, follow the board markings and the manual for its revision. In load-current calculations, distinguish the fuse rating from permissible output current.
Within the permitted environmental and installation conditions, the simultaneous-on factor is 100% with a fan. Without a fan, the manual specifies 50%, or 100% up to 35 °C. Check rack cooling and inlet-air temperature before operating every channel continuously at full load.
Switching frequency and wiring
Maximum switching frequency is 100 Hz for resistive loads. For inductive loads, it is 2 Hz at 0.3 A and 0.5 Hz at 0.5 A. The 100 Hz figure therefore does not apply to coil loads.
Follow the shared-reference arrangement when checking S5 connection parts and the front connector. The manufacturer's diagram connects the load-supply L− line to system reference M. Separate fuses do not provide galvanic isolation. For intermittent faults, also inspect electromagnetic interference and earthing connections.
F+ enable and H+ fault signalling
The F+ enable input is rated at 24 V DC / 5 mA. Check it alongside the load supply if outputs fail to operate. A red short-circuit indicator serves each group of eight. The H+ fault-signalling output is limited to 10 mA and must not drive field loads. Supply at 1L+ is required for this signalling function.
Addressing and mechanical data
The 32 outputs occupy four bytes. Match the board's addressing switch to the CPU configuration and output addresses in the PLC program. For example, a starting byte of 32 covers Q32.0–Q35.7; German notation uses A for outputs. During troubleshooting, check the program command, F+ and output voltage under load together.
Dimensions are 20 × 255 × 195 mm (W × H × D), with an approximate weight of 0.45 kg. Select the S5 rack and rack/slot arrangement for this mechanical format.
Related versions and used-module checks
Compare 6ES5 441-4UA12, 6ES5 441-4UA13 and 6ES5 441-4UA14 using their labels and wiring details. 6ES5 451-4UA11 is a different, galvanically isolated model. A 32-output / 0.5 A description alone does not establish replacement suitability.
On used Siemens equipment, inspect the label, contacts, fuse holders and signs of overheating. Test every output under suitable load while respecting channel, group and cooling limits.
Editor’s note
Start with the group supplies and fuses. If eight outputs stop together, give the board a fair check before writing it off: a missing supply or fuse fault can produce the same symptom.
For coil loads, take a moment to check switching speed. A 0.5 A inductive load is limited to 0.5 Hz; the resistive-load figure of 100 Hz is no guide here. Measure the coil's inrush current too, and save yourself trouble later.
If many outputs will be loaded together, check the rack fan, airflow and temperature. A board running cool on the bench may face different conditions inside a cabinet. Include cooling in the load assessment.
If the program commands an output but the load stays off, follow F+ enable and the shared reference. An LED alone does not settle the matter; measure output voltage under a suitable load. Keep coil loads off the H+ signalling terminal.
For a used board, check all 32 outputs, rather than stopping after a few channels. Photograph the address setting and wiring before removal, and isolate board and field power before working. Those small records make fitting the spare much easier.
OtomasyonAVM resources and PDFs
Start with the OtomasyonAVM Siemens S5 PDF archive, About Siemens S5 and S5 digital output modules.
The model's technical table appears in Siemens U Periphery, 6ES5 998-0PC22, section 5.9. In the English PDF below, pages 253–255, printed pages 50–52, contain its specifications and connection diagram.
Related topics
+ 6ES5 441-4UA12 · 6ES5 441-4UA13 · 6ES5 441-4UA14 · 6ES5 451-4UA11.
+ Fuses and load current · PLC troubleshooting · Connectors.
Browse SIMATIC S5
Siemens S5 home · S5 digital output modules · S5 PDF archive · Used Siemens equipment