Siemens 6ES5 432-4UA12 — 32-Channel 24 V DC Digital Input Module with Interrupt Capability

Siemens 6ES5 432-4UA12 is a 32-channel, 24 V DC digital input module with process interrupt capability for SIMATIC S5 S5-135U/155U systems. Galvanic isolation is arranged in four groups of eight inputs. Its distinguishing feature among S5 digital input modules is the ability to report input changes through an interrupt or group signal when configured accordingly.

Typical field signals come from relay contacts, contactor auxiliary contacts and suitable 24 V DC sensors. Relay sockets and field wiring form part of the signal path. The module reads inputs; controlling a coil or load requires a suitable digital output module.

Input voltage and channel grouping

The defined input voltage ranges are −33…+5 V for logic “0” and +13…+33 V for logic “1”. The region between +5 V and +13 V lies between the defined logic ranges. Rated input current is 8.5 mA. Trace each eight-channel group’s return using its connection diagram.

Byte-selectable filtering and speed

Switch S5 selects a typical delay of 3 ms, 1 ms or 0.3 ms for each input byte. The corresponding maximum input frequencies are 100 Hz, 300 Hz and 1 kHz, respectively. These figures do not specify the CPU’s complete interrupt response time.

Shorter filtering makes interference more likely to be accepted as a valid signal. Assess S5 cable routing and line length together with the setting. The manual’s unshielded line limits are 600 m / 200 m / 50 m in the same order; installation EMC requirements must also be observed.

Process interrupts and addressing

The module can operate as a normal input module or with process interrupts. Interrupt-line operation depends on a suitable S5 rack slot and CPU support. The process alarm via IB 0 option specifically requires a CPU 948 in single-processor operation and a matching PLC program.

In interrupt mode, input addresses must be above 127, and the four input bytes must be read in ascending order within the interrupt routine. A start address of 128, for example, occupies bytes 128–131. This is an address example only. During PLC debugging, remember that additional reads from the cyclic program can cause alarm loss; review the PLC input-reading process together with interrupt handling.

Front connections and enable input

The manufacturer’s diagram shows the F+ / F− enable input and separate returns for the four groups. The enable function is active with X20 inserted, the factory setting. When replacing a module, compare X20, X3/X4 and S1–S5 settings with the existing project. Protective grounding must not substitute for the signal return.

Distinguishing similar order numbers

6ES5 430-4UA14, 6ES5 431-4UA12 and 6ES5 434-4UA12 differ in channels, signal characteristics or function. 6ES5 432-7LA11 belongs to another hardware family. Settings from the earlier 6ES5 432-4UA11 must also be checked before being applied to 4UA12; “432” alone does not establish interchangeability.

Editor’s note

Take a little time to test more than the input LEDs. Normal input reading may work while the interrupt configuration is still wrong; check both functions before deciding the job is finished.

Photograph every switch and jumper before removing the old module. Recording X20, X3/X4 and S1–S5 can save hours of reconstructing the settings after replacement.

Do not set every byte to 0.3 ms simply because it is faster. Long cables or bouncing contacts may produce unwanted interrupts; match the response to the actual field signal.

If eight inputs fail together, start with that group’s return and terminals. Isolate the supply and verify absence of voltage before changing wiring; give the cables a proper check before condemning the card.

When buying a used digital I/O module, test all 32 channels. If interrupts will be used, verify real signal changes with a suitable CPU and slot; an LED test alone does not demonstrate every function.

OtomasyonAVM resources and PDFs

For family background, see about Siemens S5 PLCs. Other S5 documents are available in our S5-115 PDF archive; use the S5-135U/155U manual below for this 4UA12 module’s specifications and interrupt operation.

Related topics

+ 6ES5 432-4UA11 · 6ES5 430-4UA14 · 6ES5 431-4UA12 · 6ES5 434-4UA12 · PLC debugging

Navigation: SIMATIC S5 | Digital input modules | S5 racks | Used digital I/O | Siemens

External references

+ Siemens S5-135U/155U System Manual — 8-36–8-38, specifications and connections (English)

+ Same manual — 8-8–8-11, interrupt modes and program access requirements (English)

+ Siemens U Periphery — section 5.4, 4UA11/4UA12 specifications and functions (English)

+ Siemens ST 50, 1998 — 4/34, exact model comparison (English)