6ES5 431-3BA11
6ES5 431-3BA11 – SIMATIC S5 16-Channel Compact K Digital Input Module
Siemens 6ES5 431-3BA11 is a 16-channel digital input module in the compact K format for S5-130K, S5-130W and S5-150K systems. Within the S5 digital input module range, it provides two galvanically isolated groups of eight inputs. Operating instructions C79000-B8500-C233-3 describe this Siemens S5 module as having 24 V DC inputs with jumper selection for 48 V DC.
The module transfers the states of compatible sensors, limit switches and contactor auxiliary contacts in DC control circuits. Its distinguishing features include individual input-voltage jumpers, an address coding socket and a typical 3 ms input delay. Voltage selection and address configuration require separate checks.
24 V and 48 V input levels
The C233-3 instructions specify logic 0: −33…+4.5 V; logic 1: +13…+33 V in the 24 V setting. In the 48 V setting, logic 0 is −66…+9 V and logic 1 is +26…+66 V. Match the power supply and sensor output direction to the selected input level and common reference.
Typical input current is 8.5 mA. Input resistance is 2.8 kΩ at the 24 V setting and 5.6 kΩ at the 48 V setting. When connecting an inductive sensor or photoelectric sensor, check ON/OFF voltage levels and leakage current as well as nominal voltage.
Voltage jumpers and documentation differences
The operating instructions identify 24 V DC as the delivery configuration and describe Br.2–Br.17 as the input jumpers used for 48 V selection. Record the existing jumper arrangement for each channel before replacement. Do not assume that all inputs have been configured for the same voltage.
The sources use different voltage descriptions: the ST 53 / 1985 catalogue lists 24/60 V, while operating instructions C233-3 specify 24/48 V. The thresholds above come from C233-3. Use at 60 V requires verification against the actual hardware revision and its matching manufacturer documentation.
Isolation groups and field reference
The sixteen inputs form two separate groups of eight; individual channels are not isolated from every other channel. Preserve the group commons, signal returns and grounding arrangement shown in the wiring diagram. If an entire group loses its signals, check the common connection and field supply together.
Input delay and switching frequency
The maximum input frequency is 100 Hz. Input delay is typically 3 ms, with a minimum of 1.4 ms and a maximum of 5 ms. These specifications alone do not guarantee that the PLC program will capture every short pulse. Assess pulse duration, CPU scan time and the program’s input-reading sequence together.
Address coding socket and channel checks
The byte address is selected using the module’s address coding socket. STEP 5 accesses inputs by byte and bit address, using E in German notation or I in English notation. Preserve the existing coding arrangement when replacing a SIMATIC S5 module. During troubleshooting, compare the channel LED, field voltage and corresponding program bit.
Mounting, connections and supply loading
The compact K module measures 19 × 244 × 202 mm and weighs approximately 0.3 kg. Match the front connection hardware and S5 subrack to the existing K-format installation. Check connector seating, contact condition and the address coding socket during inspection.
According to C233-3, consumption from the internal 5 V supply is approximately 150 mA. Operating temperature is 0…+55 °C. The same instructions specify maximum unshielded field-cable lengths of 600 m at the 24 V setting and 400 m at the 48 V setting. Include airflow and separation of signal wiring from power cables in the control-panel layout.
Differences from related order codes
The 420-3BA11 has 32 non-isolated inputs, while the 430-3BA11 is a different 32-channel isolated model. The 431-4UA12 uses the U-format mechanical construction. A replacement for 431-3BA11 must match channel count, voltage configuration, isolation groups, housing and front connections.
Editor’s note
Start with the complete label on this S5 module: 431-3BA11, compact K. Ordering only a “431 input card” can lead to receiving a different housing and connector arrangement. Read the code right to the end.
Before removal, photograph the address coding socket and Br.2–Br.17 jumpers. A spare with the same order code may have been configured for another machine. Check its settings before reconnecting the existing field wiring.
If eight inputs disappear together, check the group common, field supply and connector contacts first. One shared connection problem can make an entire group appear faulty.
Do not apply 60 V simply because a parts list says 24/60 V. Check the 24/48 V arrangement in the operating instructions, the hardware revision and the actual jumper settings together. Resolving an old documentation difference first is easier than repairing a damaged module later.
For a used Siemens module, ask whether all sixteen channels were tested in the selected voltage configuration. Check for a missing coding socket, altered jumpers and worn front contacts. Isolate power before replacement. Understand the existing arrangement first, then work through it one step at a time.
OtomasyonAVM resources and PDFs
+ S5 digital input modules · S5 cables and connection hardware · S5 subracks.
+ Siemens S5 shared PDF archive. Exact 431-3BA11 operating information appears in C79000-B8500-C233-3, printed page 8, linked below. The ST 53 / 1985 catalogue covers compact inputs on page 8/11 and wiring on page 8/24.
Related topics
+ 420-3BA11 · 430-3BA11 · 432-3BA12 · 431-4UA12.
+ NPN and PNP differences · PLC troubleshooting · Grounding.