6ES5 430-4UA14
6ES5 430-4UA14 – SIMATIC S5 32-Channel 24 V DC Isolated Digital Input Module
Siemens 6ES5 430-4UA14 is a 32-channel, 24 V DC digital input module for S5-135U/155U systems. Within the S5 digital input module range, it provides one galvanically isolated group containing all 32 inputs. This Siemens S5 module has a rated input current of 7 mA, a typical delay of 3 ms and typical system-bus consumption of 30 mA at 5 V.
The module transfers signals from compatible 24 V DC sensors, position switches and contactor auxiliary contacts to the PLC. It collects a large number of digital field signals on one card. Isolation is provided for the group, rather than for individual channels.
Input levels and sensor compatibility
For 4UA14, the specified ranges are −33…+7 V for logic 0 and +13…+33 V for logic 1. Do not treat the intermediate 7–13 V region as a defined logic state. When assessing PNP/NPN compatibility, check output direction and the input common reference together. A negative voltage within the logic-0 range does not establish NPN compatibility.
Typical input resistance is 3.3 kΩ, and rated input current is 7 mA. For an inductive sensor or photoelectric sensor, assess output-current capacity, OFF-state leakage and voltage under load. The manufacturer specifies a 100% coincidence factor.
One isolation group
All 32 inputs belong to one galvanic isolation group. The eight-bit LED and byte arrangement does not create four independent isolation groups. Preserve the field commons and grounding arrangement shown in the manufacturer’s wiring diagram. Channel count alone is insufficient when deciding whether field circuits with different references can share a module.
Input delay and differences from 4UA13
The 4UA14 delay is typically 3 ms, with a 1.4–5 ms range; maximum input frequency is 100 Hz. CPU scan time and the PLC program’s reading sequence also affect short-pulse detection. Do not assess this module as a high-speed counter input.
The 430-4UA13 has a typical delay of 4 ms, typical 5 V bus consumption of 100 mA and rated-operation power dissipation of 8.3 W. The corresponding 430-4UA14 values are 3 ms, 30 mA and 5.6 W. The lower limit of the logic-0 range is −3 V for UA13 and −33 V for UA14.
Supply and the terminal-3 distinction
The digital section draws typically 30 mA from the 5 V system bus. The manufacturer explicitly states that L+ wiring to terminal 3 is not required for 4UA14. This does not eliminate the field-sensor power supply or the enable circuit. Do not transfer the UA13 external-supply consumption specification to this revision.
F+/F– enable input and X20
The enable input is rated at 24 V DC and 5 mA. Its logic-0 range is −33…+5 V, and logic 1 is +13…+33 V. Jumper X20 determines whether the enable function is active. If no inputs are being read, include F+/F– wiring and the existing X20 position in troubleshooting. Avoid arbitrary jumper changes.
Addressing, front connector and mounting
The thirty-two inputs are monitored through four input bytes, each containing eight bits. With a starting byte N, the channel area covers bytes N…N+3; verify the actual starting address against the existing address configuration. Record the address setting and cable markings before replacing a SIMATIC S5 module. Green LEDs indicate channel signal status.
Dimensions are 20 × 255 × 195 mm, with an approximate weight of 0.4 kg. Match the front connector and S5 subrack to the existing U-format installation. Use in S5-115U requires an adapter casing and a suitable slot arrangement; do not assume direct insertion is possible.
Permissible field-cable lengths are 600 m maximum unshielded and 1000 m maximum shielded. The separate enable-line limit is 200 m. Include shield connections, common reference, cable routing and the rated 5.6 W power dissipation when assessing the control-panel layout.
Differences from related input modules
The 420-3BA11 has 32 non-isolated inputs, while the 430-3BA11 is a different 32-channel isolated model. Both use the compact K construction. Matching channel counts do not establish mechanical or electrical equivalence between these K-format modules and the U-format 430-4UA14.
Editor’s note
Read the complete label on this S5 module: 430-4UA14. Its resemblance to UA13 does not make the timing and supply specifications identical. A small suffix can make a useful difference during fault finding.
“Isolated” does not mean every input is independent. All thirty-two channels share one group. Understand where the field commons originate before combining circuits on the module.
If all inputs disappear together, check F+/F– enable wiring, the X20 setting and addressing before changing the program. Look for a shared cause before assuming thirty-two simultaneous channel failures.
Do not immediately treat a missing L+ wire at terminal 3 as a fault. That connection is not mandatory for UA14. Check the drawing and existing arrangement before adding a jumper out of habit.
For a used Siemens module, ask whether all 32 channels and the enable function were checked. Examine front contacts, corrosion and previous repairs. Photograph the address and wiring before removal, and isolate power before replacement. Understand the existing arrangement first, then work through it one step at a time.
OtomasyonAVM resources and PDFs
+ S5 digital input modules · S5 cables and connectors · S5 subracks.
+ Siemens S5 shared PDF archive. Exact 430-4UA14 specifications and wiring appear in the S5-135U/155U manual below, section 8.4.2, printed pages 8-32–8-33 / PDF pages 346–347.
Related topics
+ 430-4UA13 · 420-3BA11 · 430-3BA11 · 431-4UA12.
+ NPN and PNP differences · PLC troubleshooting.
Browse SIMATIC S5
S5 digital inputs · SIMATIC S5 · Siemens S5 PLC · Siemens second-hand main page