Siemens 6ES5 470-4UA12 – 8-Channel ±10 V / 0–20 mA Analog Output Module

6ES5 470-4UA12 is an eight-channel analog output module in compact U construction for Siemens SIMATIC S5 U peripheral systems. In suitable U peripheral configurations, including S5-135U, S5-150U and S5-155U systems, it converts digital commands into ±10 V voltage and 0–20 mA current signals. The analog section of this S5 analog module requires 24 V DC. Data representation is 12-bit two’s complement; the delay from data transfer to analog output is 1 ms maximum.

Typical applications include speed references for servo systems, valve commands and setpoints in pump pressure control, provided the receiving input matches the signal. In PLC-based PID control, each channel’s voltage and current terminals follow the same digital command. The module provides eight independently commanded channels.

Signal ranges and load limits

For the analog signal, 0 / 512 / 1024 scaled units correspond to 0 / 5 / 10 V and 0 / 10 / 20 mA. At −1024 units the voltage output is −10 V, while the current output remains at zero. The current output is not a bipolar ±20 mA output. Check the difference between 0–10 V and 4–20 mA when matching the receiving input.

The 4UA12 provides both ±10 V and 0–20 mA terminals. 6ES5 470-4UB12 provides ±10 V voltage outputs only; 6ES5 470-4UC12 uses 1–5 V / 4–20 mA ranges. These suffixes change the signal range and its zero point.

The receiving input’s load resistance must be at least 3.3 kΩ for a voltage output. For a current loop, total resistance including the cable must be 300 Ω or less. When connecting an analog signal controller, check its input type and resistance in its own documentation.

All eight outputs share a common MANA reference. The module’s galvanic isolation does not provide individual channel-to-channel isolation. Review the receiving devices’ references together with the installation’s grounding arrangement.

Power, front connector and sense leads

The SIMATIC S5 system bus supplies the digital section with 5 V ±5%, drawing approximately 250 mA. The external analog supply is specified as 24 V DC, 200–400 mA. Check the PLC rack supply and the field supply as separate parts of the circuit.

The 42-way front connector assigns 1 to F+, 2 to F−, 3 to L+, 21 to L− and 42 to MANA. Channel 0 uses 4 QV0, 5 S+0, 6 S−0 and 7 QI0. Match the S5 cable and connector to this pin arrangement.

For voltage operation, QV drives the load and S+ / S− sense the voltage at the receiving input. In a four-wire circuit, run the sense leads directly to the load. Where a voltage output is unused, including current-only operation, fit QV–S+ and S−–MANA jumpers for that channel. Unused current outputs may remain open.

The F+/F− enable input uses 24 V DC and draws approximately 7 mA. Removing the enable jumper on the 4UA12 allows the module to respond to the bus independently of the F+/F− voltage. When considering replacement with 6ES5 470-4UA11, compare the enable circuit and jumper arrangement.

Addressing and digital representation

The module’s address switch sets its starting address. Eight channels occupy 16 bytes; each channel word starts at base address + 2 × channel number. With a base address of 128, channel 3 uses bytes 134–135. The PLC program must address the module accordingly.

Output data is left-justified across two bytes; the lowest four bits are irrelevant. With those bits set to zero, −1024 / 0 / 512 / 1024 scaled units correspond to raw words C000h / 0000h / 2000h / 4000h. Voltage is then −10 / 0 / 5 / 10 V, while current is 0 / 0 / 10 / 20 mA.

Loss of enable and hardware revision

The module does not evaluate BASP. With the enable function active, loss of F+/F− removes bus acknowledgement while the last analog value remains stored. During PLC troubleshooting, check QVZ handling, enable voltage and the actual output together. Loss of enable must not be assumed to force the output to zero.

A Siemens supplement updates the maximum capacitive load, including the cable, to 1 µF for 6ES5 470-4UA12 version 04 onwards. The original table specifies <100 nF for earlier versions. For S5 system maintenance, record the hardware version as well as the order number.

Editor’s note

Start with the label. Photograph the 4UA12 order number, hardware version and address switches. When comparing a nearby code such as 6ES5 470-4UA13, also compare the field wiring and enable circuit.

Test with a representative load. Command 0, 512 and 1024 units on channel 0, then check both voltage and current using the appropriate measurement circuit. A correct unloaded voltage reading does not establish that the current output works under load.

Missing jumpers can resemble a faulty card. Check QV–S+ and S−–MANA connections when using current outputs. Compare every jumper before transferring a front connector from another module.

Check what enable loss actually does. The enable jumper and the project’s QVZ handling affect plant behaviour. Verify this response under controlled conditions after replacement.

Long cables make the revision relevant. Assess capacitive loading against the actual hardware version. For a used module, request connector inspection and separate loaded measurements for all eight channels.

OtomasyonAVM resources and PDFs

+ Browse About Siemens S5 PLC and S5 analog modules for the system background and module groups.

+ The OtomasyonAVM S5 PDF archive collects the available system manuals. For this exact module’s wiring and specifications, use the U Periphery document below.

Related topics

+ 6ES5 470-4UA11: ±10 V / 0–20 mA; check the enable circuit and revision differences.

+ 6ES5 470-4UB12: ±10 V voltage outputs only.

+ 6ES5 470-4UC12: 1–5 V / 4–20 mA output ranges.

Browse SIMATIC S5

+ S5 analog modules · SIMATIC S5 · Siemens S5 PLC · Siemens second-hand main page

Siemens and external references

+ Siemens SIMATIC S5 U Periphery – 6ES5 998-0PC22, Release 01 (English PDF): archived copy of the manufacturer’s manual. Analog module instructions C79000-B8576-C300-06, §5.6; PDF pages 199–200, printed pages 5-24–5-25, cover specifications and connector pins.

+ U Periphery load connections and jumper instructions: §3.6, PDF pages 173–174. Digital output representation: §3.3, PDF page 164.

+ Siemens supplement C79000-Q8576-C017-03: PDF page 2, item 3, updates capacitive loading to 1 µF for 4UA12 version 04 onwards.