6ES5 243-1AC11

Siemens 6ES5 243-1AC11 — IP 243 Analog Output and Signal Processing Module

6ES5 243-1AC11 is the IP 243 output configuration without an A/D converter for Siemens SIMATIC S5. It contains two 12-bit, ±10 V D/A converters and one 8-bit, 0–10 V D/A converter. This S5 analog module has five physical analog outputs, with their signal sources determined by soldered jumper connections.

The module generates and routes analog signals between its internal circuits. It also includes two difference amplifiers for proportional signal processing. When considering its analog I/O functions, remember that the 1AC11 is not an eight-channel analog input module that digitizes external voltages for the PLC.

Three D/A converters and five physical outputs

DAC1 and DAC2 are independent bipolar converters with 11 bits plus sign; DAC3 is an 8-bit unipolar converter. The signals present at AO1–AO5 depend on the installed jumper arrangement. Five output terminals must not be interpreted as five independently programmable D/A channels.

The fully configured 6ES5 243-1AA11 and the 6ES5 243-1AB11 without D/A converters provide different functions. The 1AC11 has no A/D converter, eight-channel digital I/O groups or comparator alarm hardware. Wiring and program examples for another IP 243 configuration cannot be transferred without checking their applicability.

Soldered routing and the control application

The X29 and X32 soldering bases connect the D/A converters, difference amplifiers and physical outputs as required by the application. In PLC control, the internal path to the output terminal matters just as much as the reference generated by the program. Check any feedback connection against the machine’s existing circuit diagram.

In analog control applications, two modules carrying the same order number may have different jumper arrangements. A signal feeding a servo drive reference input may come from a D/A converter or from another internal processing path. Match the servo drive by its required voltage range, reference connection and circuit diagram.

Connections, supply and reference potentials

The front connector assigns AO1 to pin 28, AO2 to 29, AO3 to 30, AO4 to 31, and AO5 to 32. The AO5 path uses the output amplifier. When checking S5 cables and connectors, trace the internal jumper route as well as the terminal numbers.

The external supply is 24 V DC, with an allowable range of 20–30 V DC. Pins 1 and 2 are +24 V; 42 and 43 are Mext. Analog reference MANA is on pins 19, 23 and 33. When reviewing grounding and reference connections, do not arbitrarily bridge MANA and Mext: Siemens requires them to remain separate.

The analog signals are not galvanically isolated. Check the receiving device’s reference potential and input load. The specific 1AC11 configuration is listed at approximately 0.39 kg with 6.1 W power loss. Do not substitute the weight and power figures for the fully configured 1AA11.

Programming and power-up behaviour

In the PLC program, DAC1 is written at base address +0, DAC2 at +2, and DAC3 at +4. Use word transfers for DAC1/2. The CPU-specific FB 161 — PER:ANS provides analog value output. Direct writes must use the special DAC1/2 data format; a standard two’s-complement value must not be sent unchanged.

At power-up, DAC1/2 start with a code corresponding to approximately +9.9951 V; DAC3 has no defined initial value. Do not assume a zero output before initialization. During commissioning and troubleshooting, compare the startup program’s written value with the voltage measured at the assigned output.

System compatibility and related modules

The IP 243 family is used with S5-115U/H, S5-135U, S5-150U/S and S5-155U/H systems; S5-115U installation requires an adapter casing. Match the rack, CPU and existing address settings when reviewing SIMATIC S5 hardware. Understanding the Siemens S5 system architecture helps avoid selecting the wrong module.

The 6ES5 470-4UA11 and 6ES5 470-8MA11 are other analog output options. They are not direct replacements for the 1AC11’s internal signal routing and difference amplifiers. Any proposed change needs a joint review of the hardware and program.

Editor’s note

Start by photographing the original card’s soldered jumpers. When buying used Siemens equipment, matching the order number is a useful first step, but find out how the replacement was wired in its previous machine. Identical labels do not guarantee that the same signal reaches the same terminal.

Resist the temptation to turn a trimmer just to see whether the reading improves. Measure the reference and output first, and record the existing settings. A working machine’s adjustment is easy to lose and can take considerably longer to recover.

If the program displays a zero command while you measure voltage at the output, check the encoding before condemning the card. This module’s raw format deserves care. Confirm the value actually written and trace which internal circuit feeds the terminal you are measuring.

For a bench test, one changing output is only a starting point. Test every signal path you intend to use with a suitable load. Following the converter, jumper connection and amplifier separately makes it much easier to identify where a fault lies.

A green supply LED does not confirm that every function is healthy. Check the supply, fuse, analog reference and startup value together. If the card supplies a drive reference, keep machine movement under controlled conditions for the first test. Take the time to get that first step right.

OtomasyonAVM resources and PDFs

+ See the S5 analog modules and About Siemens S5 PLC pages for module selection and system context.

+ OtomasyonAVM S5 PDF archive and system manuals. For this model, use the IP 243 manual’s 1AC variant table, analog output descriptions, soldered routing diagrams and FB 161 instructions.

Related topics

+ 6ES5 243-1AA11: fully configured IP 243 · 6ES5 243-1AB11: version without D/A converters · 6ES5 470-4UA11 analog output module.

Browse SIMATIC S5

+ S5 analog modules · SIMATIC S5 · Siemens S5 PLCs · Siemens second-hand equipment.

Siemens and external references

+ Siemens IP 243 Equipment Manual — English; 6ES5 998-0KF21, R 02/92; p. 2-2 variant table and p. 2-5 1AC block diagram.

+ Same manual, pp. 3-7–3-10: D/A converters, data encoding and power-up behaviour.

+ Same manual, pp. 5-2–5-7: connector and analog routing; p. 6-5: power loss and weight for the exact 1AC11 code.

+ Same manual, pp. 7-7–7-11: FB 161 PER:ANS analog value output.