6ES5 700-2LA22
Siemens 6ES5 700-2LA22 CR 700-2F central mounting rack
The 6ES5 700-2LA22 is a CR 700-2F central mounting rack for the power supply, CPU, I/O and interface modules of a SIMATIC S5-115F controller. It mounts in a 19-inch cabinet. Use the S5 rack range and S5 CPU family to identify installed hardware by its order number.
Slot layout and capacity
The S5-115F has separate PS and CPU positions. Select the power supply using Siemens Table 3-3, which lists the PS 951-7ND31 and PS 951-7ND41. When comparing CPU 942F codes such as 7UF12 and 7UF15, use the installed CPU nameplate and the matching manual edition.
Figure 3-2 shows slots 0–5 for permitted digital input, digital output and analog I/O modules. The CP 523 uses slots 0–4. Check the system table for other communications modules. Using slot 5 for an interface reduces the I/O capacity.
A/B link and expansion
The role of each interface module depends on the S5-115F topology. The A/B parallel link uses IM 304 and IM 324. In the distributed expansion example, the central rack uses IM 304 and the expansion rack uses IM 314. With centralized expansion, the IM 306 occupies the separate IM position. Identify interconnecting cables from the modules and connector numbers at both ends.
For a central rack without expansion racks, Siemens allows the factory termination connector to remain in the IM slot. This assigns fixed initial module addresses. For systems using ER 701-1 or ER 701-2 expansion racks, check the existing topology and addressing against the project drawings.
Selecting a spare rack
The 700-2LA12 and 700-2LB11 have separate slot tables. When buying a used 2LA22, ask for photos of the complete nameplate, backplane and IM area. Siemens ST 50 also lists 2LA22 in specific S5-115H configurations. Use the S5-115H CPU and interface slot table for those systems.
Editor’s note
1. Document A and B separately. Safely isolate power. Photograph each rack’s nameplate, module order and both ends of each interface cable.
2. Check slots 5 and 6. Mark each interface in this area as serving the A/B link or distributed expansion. Preserve the existing use of slot 5.
3. Inspect the IM position. Record whether the original rack has an IM 306 or the factory terminator. Compare the sockets, pins and terminator with the spare.
4. Determine the extent of the fault. If one side drops out, check that side’s power indicators and cable endpoint first. If the same I/O address disappears on both sides, check any shared field supply and compare the slot-to-address mapping on both sides.
5. Capture the diagnostics. Read the error information in COM 115F. Save the error record and existing parameters before following the approved maintenance procedure.
6. Verify before returning to service. Have qualified personnel test the A/B link, I/O addresses and relevant safety functions under the site’s functional test procedure.
Manuals and PDF archive
S5-115F Volume 1, Figure 3-2 shows the slots and termination. Volume 2, Figure 7-1 shows the A/B example. ST 50 pages 3/73 and 3/69 list the exact order number. Siemens S5 PDF archive.
Related topics
About Siemens S5 PLCs · S5 expansion modules
Second-hand Siemens
S5 racks · SIMATIC S5 · Siemens S5 PLCs · Second-hand Siemens equipment
Siemens documentation
S5-115F Volume 1 (EN) · S5-115F Volume 2 (EN) · Siemens ST 50 (EN)