6ES5 701-1LA12

Siemens 6ES5 701-1LA12 SIMATIC S5 ER 701-1 expansion rack

The 6ES5 701-1LA12 is an ER 701-1 expansion rack that adds I/O slots to a centralized SIMATIC S5-115U/F installation. In S5-115U systems, the expansion link can run from central racks such as the CR 700-1 or CR 700-2. In an S5-115F installation, confirm the full code of the F-series central rack, such as the CR 700-2F.

Slots, supply and compatibility

The rack has nine I/O positions numbered 0–8 and a separate IM slot on the right. It measures 483 × 303 × 47 mm (W × H × D) and weighs approximately 5 kg. Hardware interrupt processing is unavailable. The ER 701-1 receives power through the expansion interface from the central controller or the ER 701-2/ER 701-3 unit it is attached to. For a supply fault, include the shared path from the S5 power supply to the interface in your checks.

S5-115U uses the IM 305 or IM 306 for centralized configurations. The IM 305 uses fixed slot addressing. Analog I/O on this rack requires the IM 306. For S5-115F, the Siemens ST 50 catalog specifies the IM 306 in the expansion unit. Match the S5 interface modules and S5 connecting cables by full order number. Identify the S5 CPU family and read the CPU label before selecting an installation diagram.

Suitable block-type digital input, digital output, combined digital I/O and analog I/O modules can be fitted. The S5-115U manual excludes the 434-7 input module and ES 902-design S5-135/155U modules. Check the card code and position against Figure 3-10.

How to distinguish similar racks

When sourcing a spare, compare the complete 701-1LA11 and 1LA12 nameplates. Check the slot count, interface layout and power path when comparing the 701-2LA12, 701-3LA13 and the S5-115H 701-3LH11. Distributed interfaces such as the IM 304 and IM 314 belong to a different configuration. Where several racks are present, use the wiring drawing to trace the actual chain of S5 expansion modules.

Editor’s note

1. Record the rack before removal. Photograph the rack and interface labels, the module order in slots 0–8 and both cable ends. In an IM 305 installation, moving a card can change the address read by the PLC.

2. If the whole rack is down, start with the shared path. Have qualified personnel check the central supply, interface module and expansion cable. The ER 701-1 receives its power through that connection.

3. If only one slot is affected, narrow the fault. Check field wiring and channel diagnostics first. Have qualified personnel isolate power before fitting a known-good card of the same order number in the same slot. A controlled test can then help distinguish a failed card from a backplane connector fault.

4. If digital I/O works and analog I/O fails, read the interface label. Confirm that an IM 306 is fitted, then check the analog card’s order number and address before suspecting the rack.

5. Inspect the rear connectors on a used rack. Ask for close-up photos of the slots and the IM connector. Look for bent pins, oxidation and damaged guides. Ask which interface and slot positions were covered by the bench test.

To offer a rack for sale, send the full order number, quantity, condition, label and connector photos, and asking price to otomasyonavm@gmail.com.

Siemens PDF documentation

Exact 6ES5 701-1LA12 data sheet (EN) · S5-115U manual, Figure 3-10 (EN) · S5-115U specifications, p. 15-8 (EN) · Siemens ST 50, S5-115F installation, p. 3/74 (EN) · OtomasyonAVM S5-115 PDF archive

Related topics

Siemens S5 PLC overview · ER 701-0 rack · IM 306 expansion interface