6ES5 307-0MM11

Siemens 6ES5 307-0MM11 — IM 307/317 Fiber Optic Media Module

The Siemens 6ES5 307-0MM11 is a fiber optic media submodule for IM 307 and IM 317 interfaces in SIMATIC S5 systems. It is separate from the complete 307-3UA11 interface board. The manufacturer’s manual states that the media modules used in the two interfaces are identical.

The submodule converts outgoing data from parallel to serial form and incoming data from serial to parallel form. The manual specifies an optical transmission rate of 44 Mbit/s. Within these S5 interfaces, it provides the data conversion for the fiber optic link.

Fiber cable and transmission distance

The specified link uses 722-2XXX0 duplex silica-glass fiber cable, with fiber dimensions in the 62.5/125 µm group. Compare the cable and connectors with the installation. Each fiber core must connect a transmitter at one end to a receiver at the other.

The IM 307/317 manual specifies 50–1500 m between interfaces. The minimum prevents receiver overload from excessive optical input power. These limits apply to the documented optical arrangement; a test with an arbitrary short cable is insufficient to establish serviceability.

Host board, rack and system matching

Identify the host interface and rack first. The manual covers expansion arrangements including ER 701-2, ER 701-3LA, EU 183U and EU 185U. Select available functions, slots and settings from the table for the particular system.

Finding an S5-135U or S5-150U central controller is only part of the identification. Record the complete host-board number, opposite interface and cable route together. When ordering 0MM11, distinguish the media submodule from the complete IM board.

Checks during fault investigation

During troubleshooting, check optical-end cleanliness, fiber directions, cable condition and both host boards’ supplies in sequence. Review cabinet grounding and fault records in the PLC program as well. A lost connection alone does not establish a media-module fault.

Differences from other communications modules

When selecting S5 communications hardware, do not substitute a 308-3UC11 or 308-3UC21 for this media module. They serve different connection roles; similar model numbers do not establish compatibility.

Likewise, ET 200U interfaces such as 318-8MB12 and 318-8MC12 are different from the IM 307/317 media submodule. Select a replacement using the complete ordering code and existing host board.

Editor’s note

Keep this small but important distinction clear: 0MM11 is the media module; 3UA11 is the main interface board. Photograph both labels together so the replacement request identifies the right part from the outset.

Protect optical ends from dust and use suitable fiber-cleaning materials. A fingertip can leave contamination that is difficult to see. A careful cleaning check can sometimes save a long fault investigation.

Mark the fiber cores and photograph both ends before disconnecting them. Reversing transmitter and receiver connections can make sound equipment appear faulty. Keep the original arrangement close to hand.

Switch off power and follow the manual’s sequence when replacing the host board or media module. Save the settings and program beforehand. A little preparation makes reassembling an older system much easier.

For used equipment, ask where possible for data-transfer tests in both directions with a suitable IM 307/317 pair. Record the cable and distance used. Seeing a light alone does not prove that the complete link works correctly.

OtomasyonAVM resources and PDFs

+ About Siemens S5 PLCs · S5 interface modules · What is fiber optic?

+ Siemens S5 PDF files — our manual archive. English manufacturer references for the IM 307/317 media module appear below.

Related topics

+ 307-3UA11 host interface · ER 701-2 rack · ER 701-3LA rack · S5 cables

Browse SIMATIC S5

+ S5 interface modules · S5 communications modules · S5 racks · SIMATIC S5 · Siemens second-hand equipment

Siemens and external references

+ Siemens IM 307/IM 317 manual — 1-2: serializer/deserializer function and 44 Mbit/s transmission (English)

+ Same manual — 4-7: exact 6ES5 307-0MM11 code and X3 connector

+ Same manual — 5-2: fiber connection and identical media modules in IM 307/317