6ES5 441-8MA11
Siemens 6ES5 441-8MA11 — 8-Channel 24 V DC / 0.5 A Digital Output Module
The Siemens 6ES5 441-8MA11 is an 8-channel, 24 V DC / 0.5 A digital output module for SIMATIC S5 systems. Within the S5 digital output range, it is a non-isolated model with eight outputs sharing one supply group.
The load supply is 24 V DC, with a permitted range of 20–30 V DC. The module has no built-in short-circuit protection. Load and cable protection must be addressed in the cabinet design.
Channel current, total load and temperature
Siemens specifies 0.5 A per channel at 60 °C and 1 A at 30 °C. The total current of all outputs remains limited to 4 A. Calculate the current for each of the eight channels; the 1 A rating at 30 °C does not allow eight channels to deliver 8 A simultaneously.
Maximum switching frequency is 100 Hz with resistive loads and 2 Hz with inductive loads. Check pickup current when selecting relays or contactor coils; use a suitable interposing relay and socket where required.
Output protection and wiring principles
Do not assume the output automatically shuts down during a short circuit. Select fuses and protective devices for the load and output limits. Apply coil suppression according to the load manufacturer’s instructions.
These outputs are not potential-free relay contacts. Compare the NPN/PNP wiring principles and M return with the existing diagram. Check cabinet grounding and the common return before transferring a wiring arrangement from another board.
Terminals and address checks
The Siemens diagram identifies terminal 1 as L+ and terminal 2 as M. For example, output .6 is on terminal 10, with the other side of the load returning to M. Record cable and terminal numbers before removal; channel numbers and terminal numbers are different.
For the compact S5 module arrangement, check the installed slot together with the output address in the PLC program. The manual’s Q5.6 example refers to slot 5 and is not a fixed address for every installation. During troubleshooting, check the program command, L+/M supply and voltage at the load in sequence.
Comparison with related models
Do not automatically treat the 440-8MA12, 440-8MA11 or 440-8MA22 as equivalents to this eight-channel board. Review channel count, current and protection against the complete order number.
The 451-8MA11 has isolated DC outputs, while the 452-8MR11 is a different relay-output model. Check voltage, current and wiring direction separately for the 453-8MA11 as well. A similar appearance does not establish the same electrical function.
Editor’s note
Keep one point clearly in mind when selecting this board: there is no built-in short-circuit protection. Checking the cable and load before fitting a spare helps avoid passing the original fault on to the replacement.
Let us look beyond a lit LED. Check the command, the supply and operation under load, one step at a time. A small wiring fault need not lead to replacing a healthy board.
The 1 A rating at 30 °C is not a reason to load every channel to its maximum. The 4 A total limit still applies. Writing down the load currents now is easier than tracking down overheating later.
Photograph the label, slot and terminal numbers before removal, and back up the program. Switch off power and verify the absence of voltage. Siemens warns that the board’s capacitor can remain charged after L+ is switched off.
For a used digital output board, ask for all eight channels to be tested with suitable loads. Agree on the test voltage and current. One working channel does not establish that the other seven are healthy.
OtomasyonAVM resources and PDFs
+ About Siemens S5 PLCs · Siemens S5 PDF files — our manual archive. Manufacturer documents for this model appear below.
Related topics
+ 440-8MA12 · 440-8MA22 · 451-8MA11 · 452-8MR11 · 453-8MA11
Browse SIMATIC S5
+ S5 digital output modules · SIMATIC S5 · Compact S5 modules · Used digital I/O modules · Siemens second-hand equipment
Siemens and external references
+ Siemens S5-100U system manual — 14-28: exact 441-8MA11 specifications and wiring diagram (English)
+ Same manual — 3-17, Figure 3-15: terminal wiring example for channel .6