6ES5 441-4UA13

Siemens 6ES5 441-4UA13 — 32-Channel, 24 V DC / 0.5 A Digital Output Module

6ES5 441-4UA13 is a 32-channel, 24 V DC / 0.5 A electronic digital output module for Siemens SIMATIC S5 S5-135U/155U systems. This model in the S5 digital output range is non-isolated, with a field-supply range of 20–30 V DC.

The board switches suitable DC coils and signal loads. Within SIMATIC S5, distinguish it from isolated models with the same channel count. This U-type module measures 20 × 255 × 195 mm and weighs approximately 0.45 kg; check it together with the existing rack and front wiring arrangement.

Supply, common reference and load current

The switching-current range for resistive and inductive loads is 5 mA–0.5 A per channel. Provide the L+ feeds from an appropriate 24 V DC power supply; connect L−, the common reference and grounding according to the manufacturer’s diagram. The non-isolated design requires careful treatment of field circuits at different potentials.

For contactor and valve coils, check inrush current as well as steady-state current. Higher-current loads require a suitable interposing relay or driving stage. Maximum total switching current is 4 A per eight outputs; the separate lamp-load limit is 0.22 A / 5 W per channel.

Four fuse groups and short-circuit signalling

There is one 6.3 A slow fuse per eight outputs, giving four fuse groups across the 32 channels. Preserve the correct fuse characteristic. If a fuse opens, inspect its loads and wiring. These eight-output fuse groups are not galvanically isolated groups.

Green LEDs display channel status; red LEDs indicate short circuits in the associated eight-output group. H+ is the common short-circuit signalling output, with a maximum switching current of 10 mA. For 4UA13, the manufacturer specifies short-circuit protection response with line resistance of 15 Ω or less; do not assume identical protection behaviour under every wiring condition.

Cooling and simultaneous loading

The total-load factor is 100% with a fan and 50% without a fan, with 100% permitted without a fan up to 35 °C. The specified power dissipation for 4UA13 at rated operation is 17 W. Assess cabinet temperature, fan operation and simultaneous channel loading together.

Switching and off-state measurements

Maximum switching frequency is 100 Hz for resistive loads. For inductive loads, it is 2 Hz at 0.3 A and 0.5 Hz at 0.5 A. Maximum off-state leakage is 0.5 mA, while minimum on-state voltage is L+ − 1.5 V. With low-current loads, interpret measurements together with actual load behaviour.

The maximum unshielded output-line length for these S5 field connections is 400 m. On long runs, also check voltage drop, conductor size and short-circuit loop resistance. Cable length alone does not establish correct output operation or protection performance.

Enable input and X20 jumper

The enable input is rated 24 V DC, with a logic-1 range of 13–33 V. The front wiring diagram shows F+ referred to M. Inserting X20 makes the enable input active; this is the factory setting. Record the existing jumper position and enable wiring before replacement; do not change them simply to force an output to operate.

Addressing and fault checks

The 32 outputs occupy four output bytes. Match the starting address and channel sequence to the PLC program. A changing bit in the programming software does not establish that the complete load circuit is sound; measure the output voltage at the load too.

During troubleshooting, inspect the relevant digital input conditions, enable input, group supply and fuse together. Also check the S5 system operating state. Isolate system and field power before disconnecting wiring.

Related models and revision differences

When comparing 6ES5 441-4UA11 and 6ES5 441-4UA12, verify the complete hardware revision and wiring diagram. The table specifies 7 A fast fuses for 6ES5 441-4UA14; do not transfer that rating to 4UA13. 6ES5 451-4UA13 is an isolated model. Similar order codes do not establish identical electrical details.

Editor’s note

Start by following the common 0 V return carefully. On a non-isolated output board, one loose return can look like several separate faults. Check both sides of the load circuit before replacing the board.

If eight channels disappear together, their fuse group is a sensible starting point. Do not stop at fitting a new fuse: a crushed cable or faulty coil may open it again. Keep the specified 6.3 A slow rating for 4UA13.

Years of reliable operation do not make cooling checks unnecessary. A few extra valves, a blocked filter or a stopped fan can change the load assessment. Check the fanless loading limit against the actual cabinet temperature.

Photograph X20 and the front wiring before removing the old board. An enable-circuit problem can easily be mistaken for a board fault. Keeping a record makes the replacement much easier to follow.

When buying a used Siemens 441-4UA13, look beyond the LEDs. Have all thirty-two channels tested with suitable loads, together with the four fuse groups and enable function. A little care at the start is easier than having to do the job again at the machine.

OtomasyonAVM resources and PDFs

S5 digital output modules · S5 racks and expansion units · Siemens S5 PDF archive. The specifications and wiring are covered in the S5-135U/155U System Manual, §8.4.9, pp. 8-48–8-49. The archived English document is C79000-G8576-C199-07; the German document is C79000-G8500-C199-07.

Related topics

441-4UA11 · 441-4UA12 · 441-4UA14 · 451-4UA13 · PLC troubleshooting.

Navigation

S5 digital output modules · SIMATIC S5 · Siemens S5 PLC · Used Siemens.

Siemens and external references

Siemens S5-135U/155U System Manual — German; §8.4.9, pp. 8-48–8-49: 441-4UA13/4UA14 specifications, fuse difference, enable input and wiring diagram.