6ES5 095-8MB01

Siemens 6ES5 095-8MB01 SIMATIC S5-95U SINEC L2 Compact PLC

The Siemens 6ES5 095-8MB01 is an S5-95U compact PLC in the SIMATIC S5 family. It runs local machine logic and exchanges data with other stations through a 9-pin RS-485 SINEC L2 interface. The bus rate is selectable from 9.6 kbit/s to 1.5 Mbit/s. The PLC runs on 24 V DC and has 16 digital inputs, 16 digital outputs, eight analog inputs and one analog output on board.

The PLC can run a machine station’s sensors and outputs locally while reporting ready status, cycle state or a measured value to the line controller. Its SINEC L2 interface uses DIN 19245 Part 1 communications on the PROFIBUS network. When selecting a spare, check the SINEC L2 services in use and how the PLC program exchanges data.

How do the SINEC L2 and programming connections differ?

The 9-pin L2 port takes shielded, twisted-pair RS-485 bus cable. Trace the A and B conductors at the PROFIBUS connector against the plant wiring diagram. Termination belongs at the two physical ends of the segment. The PROFIBUS troubleshooting guide covers additional checks on the cable side.

For local STEP 5 access, use the separate 15-pin PG/OP port. Select an S5 cable for the programming device in use. For PG 7xx connections, the 6ES5 734-2BD20 and 6ES5 734-2BF00 are the 3.2 m and 5 m options, respectively.

What is stored in DB1 and program memory?

The L2 parameter block in DB1 sets the station address, active or passive station role, bus rate and timing. Siemens lists 9.6 / 19.2 / 93.75 / 187.5 / 500 / 1500 kbit/s. If the project uses a standard connection, check the STEP 5 send and receive areas and the coordination bytes that control them.

Siemens lists 16 KB of internal memory for hardware revision 8MB01 A02, with up to 8 KB available for STEP 5 instructions. Identify any fitted EPROM or EEPROM submodule separately. Before replacing the CPU, compare the uploaded program backup, DB1 and the memory submodule contents.

How is the onboard I/O used?

The 16 digital inputs and 16 digital outputs use 24 V DC signals. The eight analog inputs accept 0–10 V. The single analog output supports 0–10 V or 0–20 mA. The PLC also has four interrupt inputs and two counter inputs. The Siemens wiring diagram shows onboard digital I/O at 32.0–33.7, analog input words at 40–54 and the analog output word at 40.

In an expanded cabinet, record the S5 digital input modules, digital output modules and analog modules separately from the onboard I/O. Note the full order number of the S5 bus unit and the order of the installed modules.

Siemens specifies a 20–30 V DC operating range for the PLC supply. Include the CPU, expansion modules and field loads when checking the S5 power supply. The PS 931 6ES5 931-8MD11 is an example of an external 24 V supply used with S5-95U systems.

How do nearby S5-95U order numbers differ?

The 8MA01 is the base S5-95U, and the 8MC01 has two serial interfaces. The 8MB02 and 8MB03 also have SINEC L2. Siemens lists network PG functions and additional Layer 2 services beginning with 8MB02 A01. The 8MD models are DP slaves, and the 8ME01 is a DP master.

Editor’s note

When sourcing a spare, record the full 6ES5 095-8MB01 order number and the A01/A02 hardware revision from the label.

Back up the STEP 5 project, DB1 and memory submodule before replacing the CPU. Record which data areas the program sends and receives over the network.

If BF is lit, verify that DB1 contains the L2 parameter block and that the communications interface is enabled. Then check the station address, baud rate, A/B wiring and termination.

When testing the onboard analog output, verify whether the receiving device expects 0–10 V or 0–20 mA. Compare the output wiring with the plant drawing.

After replacement, monitor one known local input and one bus data word separately. This gives you a separate check for local I/O and SINEC L2 data transfer.

OtomasyonAVM resources and PDFs

See the Siemens SIMATIC S5 PLC overview for the product family and the S5 communications modules section for related interfaces.

Browse the SIMATIC S5-90U PDF archive and the SIMATIC S5 system manuals archive for family documentation.

Related topics

S5-95U 8MB02 SINEC L2, S5-95U 8MB03 SINEC L2 and S5-95U 8ME01 DP master.

Browse the S5 range

SIMATIC S5-90U–115U CPU family and SIMATIC S5 models.

If you have a unit to sell, send a label photo, quantity and working condition to otomasyonavm@gmail.com.

Siemens and external technical references

Siemens S5-95U SINEC L2 interface manual, 6ES5 998-8MB12 (German PDF)

Siemens S5-95U SINEC L2 interface manual, 6ES5 998-8MB22 (English online copy)

Siemens S5-95U hardware guide, Appendix A specifications and Appendix H revision history (German PDF)