6ES5 095-8ME01
Siemens 6ES5 095-8ME01 SIMATIC S5-95U Compact PLC with PROFIBUS DP Master
The Siemens 6ES5 095-8ME01 is a SIMATIC S5 S5-95U compact PLC with an integrated PROFIBUS DP master interface. It runs on 24 V DC and provides 16 digital inputs, 16 digital outputs, 8 analog inputs, and 1 analog output on board. The DP master operates from 9.6 kbaud to 1.5 Mbaud and supports up to 16 DP slaves.
This S5 controller with a communications interface handles local machine signals while cyclically reading inputs and writing outputs at distributed stations such as SIMATIC ET 200. A suitable ET 200U IM 318-B station can serve as remote I/O. The 8ME02 and 8ME03 also belong to the DP master family. The 8MB02 uses a different PROFIBUS interface variant. Verify the full order number, hardware revision, and EEPROM when selecting a replacement.
How is the DP bus wired and addressed?
The DP interface uses a 9-pin D-sub port. Siemens assigns line B to pin 3 and line A to pin 8. Keep the A/B assignments consistent at each PROFIBUS connector and enable termination at both ends of each RS-485 segment. Follow the PROFIBUS cabling rules for the selected line rate.
The master provides 128 input bytes and 128 output bytes for PROFIBUS DP stations, using linear addressing. Each DP slave can use up to 32 input bytes and 32 output bytes. Check the station count and the byte limits together when laying out the network.
What is built in and how is local I/O expanded?
The onboard digital inputs are addressed I 32.0–I 33.7, and the digital outputs are Q 32.0–Q 33.7. Field wiring connects to the 40-pin front connector. The digital signals are 24 V DC.
The analog signals use a separate D-sub connector. The eight 0–10 V inputs are addressed IW 40–IW 54. The single output is QW 40 and provides 0–10 V or 0–20 mA. Use the S5-95U wiring diagram to select the voltage or current output pin.
The power terminals are rated for 24 V DC nominal, with a 20–30 V DC operating range. When choosing an S5 power supply, such as the PS 931-8MD11, account for the combined PLC and field load. Local S5 expansion modules attach to the local I/O bus through a suitable carrier, such as the 6ES5 700-8MA11 bus module, on a 35 mm DIN rail.
Where are the STEP 5 program and DP configuration stored?
Siemens specifies the 6ES5 375-0LC61, 32 KB EEPROM as the memory module for DP master operation. It stores both the STEP 5 application program and the DP configuration created with COM PROFIBUS. Siemens reserves 19.9 KB for the program and 12 KB for the compressed DP configuration.
Transfer the DP configuration from COM PROFIBUS over the PROFIBUS network with the EEPROM installed in the PLC. STEP 5 uses the separate PG/TTY port. Match the PG cable to the programming device’s connection type.
Editor’s note
Check the 8ME01 suffix and hardware revision on the housing before ordering a spare. The Siemens ET 200 manual lists this exact order number from revision 3 onward.
Back up the STEP 5 program and COM PROFIBUS project separately before removing the PLC. Record the master address, line rate, and the addresses of the connected stations.
When receiving a used unit, check that the 375-0LC61 EEPROM and the 40-pin front connector are physically present. Put the CPU in STOP and switch off power before changing the EEPROM.
If BF flashes while RUN is on, at least one configured DP slave is unreachable. Check its power and address first, then the cable and termination. FB 230 can provide detailed diagnostics in STEP 5.
If a DP configuration transfer fails, check that COM PROFIBUS is using the PLC’s current address and line rate. The Siemens manual gives address 1 and 19.2 kbaud as the defaults after a general reset.
OtomasyonAVM resources and PDFs
For system and station information, see the Siemens S5 PLC overview and the SIMATIC ET 200 distributed I/O page.
Siemens ET 200 manuals and PDF archive · SIMATIC ET 200B distributed I/O manual (English PDF) · Siemens PROFIBUS network manual (English PDF).
Related topics
6ES5 095-8ME02 DP master, 6ES5 095-8ME03 DP master, and 6ES5 318-8MB12 ET 200U interface.
Browse SIMATIC S5
SIMATIC S5 family › S5 communications modules
External references
Siemens ET 200 distributed I/O system manual, S5-95U DP master chapter (English PDF) · Siemens S5-90U/S5-95U system manual (English PDF) · Siemens 6ES5 095-8ME01 data sheet (German PDF).