6ES5 095-8ME02
Siemens 6ES5 095-8ME02 – SIMATIC S5-95U PROFIBUS DP Master CPU
The Siemens 6ES5 095-8ME02 is a compact SIMATIC S5-95U PLC with a 24 V DC supply and an integrated PROFIBUS DP master interface. It has 16 digital inputs, 16 digital outputs, 8 analog inputs, 1 analog output, 4 interrupt inputs and 2 counter inputs. A separate 20 mA TTY port is available for programming.
The CPU can read push buttons and position sensors through its onboard inputs while exchanging data with a remote ET 200 station. It reads the station’s inputs and sends output commands over PROFIBUS DP. The front port marked SINEC L2-DP is the connection for that fieldbus.
Onboard inputs, outputs and counters
The onboard digital inputs and digital outputs operate at 24 V DC. The outputs are rated at 0.5 A per channel. Local digital signals are wired through a 40-pin front connector. The STEP 5 addresses are I 32.0–I 33.7 for the inputs and Q 32.0–Q 33.7 for the outputs.
The analog inputs read 0–10 V signals. The single analog output provides 0–10 V or 0–20 mA, depending on the wiring. Counter channel A accepts up to 5 kHz and channel B up to 2 kHz. Local expansion uses compatible S5-100U I/O modules and S5 bus units.
PROFIBUS station count and data limits
The S5-95U DP master supports up to 16 DP slave stations at data rates from 9.6 kbit/s to 1.5 Mbit/s. The total linear DP address space is 128 input bytes and 128 output bytes. Each station can use up to 32 input bytes and 32 output bytes. Four stations using 32 input bytes each would fill the available input address space.
The fieldbus connects to a 9-pin D-sub port through a suitable PROFIBUS connector. When checking an ET 200U station fitted with an IM 318-B interface, compare its station address and module layout with the DP project. Check the connector wiring and termination at both ends of the PROFIBUS segment as part of the same inspection.
STEP 5 program and DP station configuration
The programmer connects through the 20 mA TTY port using a suitable S5 programming cable. The STEP 5 application holds the machine logic. The COM PROFIBUS project defines station addresses, module layouts and data assignments. The Siemens DP master manual specifies a dedicated 32 KB EEPROM module for storing both sets of data.
If RUN is lit and BF is flashing, at least one configured DP station cannot be reached. During fault diagnosis, identify the missing station and check its power supply, address and bus connection. The STEP 5 application can read DP diagnostics through FB 230.
Related order numbers and replacement checks
The 6ES5 095-8ME01 and 6ES5 095-8ME03 also belong to the DP master family. The 6ES5 095-8MA05 is a standard compact S5-95U variant. When selecting a spare, compare the full order number, the fitted EEPROM and the existing DP project. When tracing the cabinet supply, record the CPU’s 24 V DC input and the nameplate of the PS 931 power supply if one is fitted.
Editor’s note
Photograph both labels. Keep the full 6ES5 095-8ME02 order number, the hardware revision if visible and the EEPROM label in the same maintenance record.
Keep two backups. Save the COM PROFIBUS project alongside the STEP 5 application. Record the station addresses and the input and output byte counts for each station.
Record which signals failed. If cabinet inputs still work but a remote valve stops responding, start at the valve’s DP station. Note the state of both RUN and BF while the fault is present.
Check what comes with a used unit. Confirm whether the 32 KB EEPROM and front connector are included with the CPU. Ask whether the bench test covered both local I/O and data exchange with a DP station.
Verify the field signals after replacement. Check that a local input appears at the correct STEP 5 address, then confirm that an input and an output at the remote station match the project’s address assignments.
OtomasyonAVM resources and PDFs
For onboard wiring and installation, see our S5-90U/S5-95U system manual reference page. The OtomasyonAVM S5 PDF archive contains documentation for the S5-100U and S5-115H.
Related topics
For the other parts of a DP installation, see S5 communications modules, the ET 200U IM 318-B interface and Siemens PROFIBUS connectors.
Site navigation
Siemens Automation › Siemens SIMATIC S5 › S5-90U–S5-115U CPU models
External references
Siemens ST 80 catalog – 6ES5 095-8ME02 DP master identification (PDF)
Siemens ET 200 manual – S5-95U DP master hardware, Chapter 4 (PDF)