6ES5 095-8MB03
Siemens 6ES5 095-8MB03 SIMATIC S5-95U SINEC L2 Compact PLC
The Siemens 6ES5 095-8MB03 is a compact PLC in the SIMATIC S5 range, built on the S5-90U/S5-95U platform with a SINEC L2 (PROFIBUS, RS-485) interface. It runs on 24 V DC and has 16 KB of RAM, 16 digital inputs, 16 digital outputs, 8 analog inputs and 1 analog output.
This S5 CPU runs the local machine program and exchanges data with other SINEC L2 stations. The 6ES5 095-8MA04 is the base S5-95U. Siemens lists a DP slave interface for the 6ES5 095-8MD02 and a DP master interface for 8ME units such as the 6ES5 095-8ME02.
SINEC L2 wiring and DB1 settings
The 9-pin RS-485 network port supports six rates from 9.6 kbaud to 1.5 Mbaud. When selecting a PROFIBUS connector and S5 cable, check the segment’s connectors, shield connection and end termination. The programming device uses a separate 15-pin TTY port. The 6ES5 095-8MC01 is an S5-95U variant with a second serial interface.
DB1 holds the station address, active or passive SINEC L2 station type, and baud rate. The STEP 5 program may call FB252 L2-SEND and FB253 L2-RECEIVE. When commissioning a replacement CPU, check DB1 along with the data areas used by those blocks.
Onboard digital, analog and counter connections
The 16 digital inputs use addresses I 32.0–I 33.7, and the 16 digital outputs use Q 32.0–Q 33.7. The outputs are rated at 24 V DC and up to 0.5 A per channel. The 40-pin screw-terminal front connector and 40-pin crimp front connector are separate parts. Record the addresses of external digital input and digital output modules separately.
The 8 onboard analog inputs accept 0–10 V and are read at IW 40–IW 54. The single analog output at QW 40 provides 0–10 V or 0–20 mA, depending on the wiring. Record the channels and signal ranges of external S5 analog modules separately.
The unit has 4 interrupt inputs and two counter inputs. Siemens specifies a counting limit of 5 kHz for A and 2 kHz for B. Match the pulse input to its counter address in the manual before connecting the signal.
Power supply and local I/O expansion
Siemens shows the PS 931 6ES5 931-8MD11 as an example of a 24 V DC CPU supply. Use the cabinet drawing to trace the S5 power supply and output load circuits separately. The CPU and bus units mount on a 35 mm DIN rail.
Connect up to 32 S5-100U I/O modules directly using bus units such as the screw-terminal bus unit or crimp-terminal bus unit. Record slot order, addresses and total current demand for the S5 expansion modules.
Editor’s note
Read the 8MB03 suffix and hardware revision from the label. The 8MB02 is also a SINEC L2 model. Match the hardware revision, STEP 5 project and network settings when choosing a replacement.
Back up the program and DB1 before replacement. Record the fitted S5 memory submodule part number. If a module such as the 375-0LC31 EEPROM is fitted, compare its contents with the service backup.
Label the PG and L2 ports separately. The 6ES5 734-2BD20 PG cable connects to the programming side. Photograph the bus connector, cable orientation and termination position before removal.
If the CPU is in RUN and the L2 fault LED is on, check the station address and baud rate in DB1, then inspect the segment connection and termination. The Siemens S5 system page covers the hardware layout.
Ask what was tested on a used unit. When buying a used Siemens PLC, confirm both local I/O and SINEC L2 communications tests. To offer a unit for sale, email the full part number, quantity, condition, label photo and asking price to otomasyonavm@gmail.com.
OtomasyonAVM resources and PDFs
SIMATIC S5-90U and S5-95U CPU and module information · Siemens S5 system page
OtomasyonAVM S5-90 PDF archive
SIMATIC S5-90U/S5-95U system manual, 6ES5 095-8MB03 model table
Related topics
6ES5 095-8MA04, base S5-95U · 6ES5 095-8ME02, PROFIBUS-DP master version
6ES5 931-8MD11 PS 931, 24 V DC power supply
Browse the S5 range
Siemens SIMATIC S5 PLCs › S5-90U and S5-95U
External references
Siemens S5-90U/S5-95U system manual, 8MB03 model table · S5-95U onboard I/O specifications