6ES5 095-8MA04
Siemens 6ES5 095-8MA04 SIMATIC S5-95U Compact PLC
The Siemens 6ES5 095-8MA04 is a SIMATIC S5-95U central unit with the CPU and onboard I/O in one housing. The Siemens system manual covers this order number from hardware edition 01. See the Siemens S5 PLC guide for the family and the used PLC CPU section for other units.
24 V DC supply and digital I/O
The rated supply is 24 V DC. The manual gives a permissible range of 20–30 V DC. Check the PLC power supply and the output load supply separately. The onboard 16 digital inputs use I32.0–I33.7, and the 16 digital outputs use Q32.0–Q33.7. Siemens specifies a 0.5 A limit per digital output. When several I/O points are under load, check the total current and ambient temperature limits on page B-3.
Analog channels, interrupt inputs and counters
The onboard analog I/O comprises eight 0–10 V inputs and one analog output. The inputs occupy even word addresses IW40–IW54. The output at QW40 provides 0–10 V or 0–20 mA, depending on the terminals used. The unit also has four interrupt inputs and two counter inputs. The manual gives 5 kHz for counter A and 2 kHz for counter B. For counter A, check the conditions that apply when a programmer, operator panel or SINEC L1 is connected. When comparing with the S5-90U, check the onboard channel count and address table for each unit.
STEP 5, memory and expansion
The PG/TTY interface is used for STEP 5 programming. When choosing a Siemens PLC cable, verify the programmer interface. Siemens provides a separate supplement for the 095-8MB03 with SINEC L2.
The unit has 16 KB of onboard RAM. STEP 5 program capacity is specified as 8K statements. Siemens lists 16 KB 375-1LA21 EPROM and 375-0LC41 EEPROM options among the memory submodules. To reduce the risk of data loss, back up the existing program and data blocks before replacing the unit or performing an overall reset.
S5-100U modules connect through the external I/O bus. Record the order numbers of the fitted interfaces, connecting cables and bus units such as the 6ES5 700-8MA11. External module addresses depend on slot position.
Used equipment checks
Ask for a photo showing the full order number and hardware edition. Check the electronic boards and terminals for damage, corrosion and rework. Confirm whether a memory module and battery are included. Ask for a test record showing RUN status, programmer communication and the I/O channels tested.
Editor’s note
Along with the digital I/O test, ask for a measured result from at least one 0–10 V analog input and the QW40 analog output. The record should identify whether the output was tested on its voltage or current terminals.
If you have this PLC for sale, send photos of the unit and its label to otomasyonavm@gmail.com.
Siemens S5 PDF archive
See the shared Siemens S5 PDF archive for S5 manuals and technical documents.