6ES5 470-7LC12
Siemens 6ES5 470-7LC12 SIMATIC S5 Eight-Channel 1–5 V / 4–20 mA Analog Output Module
The Siemens 6ES5 470-7LC12 is an eight-channel 470 analog output module documented for S5-115U and S5-115F controllers in the SIMATIC S5 family. Each channel has 1–5 V voltage and 4–20 mA current terminals. A digital-to-analog converter turns the PLC command into a field signal. The analog output group is galvanically isolated, and all eight channels share MANA as their reference.
Use QI to send a 4–20 mA analog signal to a valve positioner or QV to send a 1–5 V reference to a compatible drive. Connect a voltage load between QV and MANA and run the S+ and S− sense leads to the load’s positive and negative terminals. For current output, connect the load between QI and MANA.
Front connector, output load and unused terminals
At the front connector, pin 1 is L+, pin 47 is L− and pins 13 and 37 are MANA. The external supply is 24 V DC nominal, within 20–30 V DC. On channel 0, 3 = QV, 4 = S+, 5 = S− and 6 = QI. Use the 7LC12 pin diagram for the other channels.
Fit QV–S+ and S−–MANA jumpers at the front connector for each unused voltage output, including channels wired for current output. Leave unused QI terminals open. The total resistive load on a current output is 300 Ω maximum. The load resistance on a voltage output is 3.3 kΩ minimum.
Siemens specifies up to 200 m of shielded signal cable and a capacitive load of less than 100 nF, including cable capacitance. Check the MANA and shield connections against the cabinet’s grounding arrangement. If the receiving device requires a different range, assess the need for analog signal conversion against its input specifications.
STEP 5 output word and scaling
On the S5-115U, each channel uses two bytes. The output value occupies bits 15–4 of the 16-bit word. The rated output pairs are 0000h → 1 V / 4 mA, 2000h → 3 V / 12 mA and 4000h → 5 V / 20 mA. These are direct output word values. For a project using FB 251, check the block parameters and scaling in the Siemens S5 manual index.
When moving an output, add 2 × the channel number to the module base address to find the new output word. Match the STEP 5 address to the field wiring. Siemens specifies a 1 ms conversion time and an operating error limit of ±6‰ at 0–55 °C. See the S5-115 PDF archive and the module manual for details.
S5-115F/H and related order numbers
The Siemens S5-115F wiring diagram lists the full 7LC12 order number. On a project using a CPU 942F, verify the output’s role and commissioning test against the system configuration. Siemens also lists the 7LC12 and CPU 942H in its S5-115F/H product list. For an S5-115H cabinet, check the module list for its hardware and project revision.
The 470-7LC11 and 470-7LC13 are separate order numbers with the same rated ranges. The 470-8MC12 and 470-8MD12 are two-channel S5-100U peripheral modules for 4–20 mA and 1–5 V respectively. Check the full order number and rack when selecting a spare.
Editor’s note
Read the full label. Record the rack type, the 7LC12 suffix and the signal type used on each channel.
Photograph the jumpers. After isolating power, record which channels have QV–S+ and S−–MANA jumpers before removing the front connector.
Check the supply and return first. If an output is missing, verify the L+/L− supply, then check the MANA connection and load resistance.
Test the output and feedback separately. In a loop with a 460-7LA13 or 463-4UA12 analog input module, measure the 470 output at the load first. Then compare it with the feedback value read by the PLC.
Ask for a load test on the spare. When buying a used Siemens part, verify the low, midpoint and high readings on the channels you will use. To sell a module, email its code, quantity, condition, label photo and price to otomasyonavm@gmail.com.
OtomasyonAVM resources and PDFs
SIMATIC S5 analog input and output modules · SIMATIC S5-115 hardware
OtomasyonAVM S5-115 PDF archive · SIMATIC S5 system manuals and STEP 5 documentation · SIMATIC S5-115H system manual, analog output wiring principles
Related topics
470-7LC11, eight-channel 1–5 V / 4–20 mA · 470-7LC13, eight-channel 1–5 V / 4–20 mA · 460-7LA13 analog input module
Browse the S5 range
Siemens SIMATIC S5 › S5 analog modules
External references
Siemens S5-115U system manual, 470-7LC12 pinout and specifications · Siemens S5-115U, load wiring and digital output values
Siemens S5-115F manual, 470-7LC12 load wiring · Siemens S5-115F/H declaration of conformity and product list