Analog to Analog conversion

Analog-to-analog conversion for industrial measurement signals

Analog-to-analog conversion: making devices work together

A transmitter can be working perfectly and still be incompatible with its controller. It might deliver 4–20 mA while the receiving channel expects 0–10 V. An analog signal converter bridges that gap: it changes the electrical representation of an analog signal while preserving the measurement it represents.

For example, a pressure transmitter with a current output can feed a voltage-only analog input on a PLC through a suitable converter. A 0–10 V sensor can also be adapted to a current input. The important relationship is between the two measurement scales, rather than simply between the numbers printed beside the terminals.

What should 5 V become?

With a linear mapping from 0–10 V to 4–20 mA, 5 V becomes 12 mA. Both represent the midpoint of the measurement range. The table shows the matching voltage and current values:

Example mapping: 0–10 V ↔ 4–20 mA
Range position Voltage Current
0% 0 V 4 mA
25% 2.5 V 8 mA
50% 5 V 12 mA
75% 7.5 V 16 mA
100% 10 V 20 mA

Voltage to current: Iout (mA) = 4 + 16 × [Vin (V) / 10]
Current to voltage: Vout (V) = 10 × [(Iin (mA) − 4) / 16]

If the transmitter measures 0–10 bar, the midpoint is 5 bar. The receiving controller must therefore interpret 5 V as 5 bar. A converter does not automatically know the engineering unit or the transmitter’s pressure range. Set zero, span and display scaling consistently throughout the signal path. In a 4–20 mA measurement, zero process value normally corresponds to 4 mA, not zero current.

The resistor shortcut—and its limit

A suitable shunt resistor can turn loop current into a measurable voltage. Using V = I × R, a 250 Ω resistor gives 1–5 V from 4–20 mA. A 500 Ω resistor gives 2–10 V. Neither produces 0–10 V on its own. That mapping also needs an offset correction and the appropriate gain.

Check resistor tolerance, temperature coefficient, power rating and receiver input impedance. The resistor adds a voltage burden to the loop, alongside the receiver and cable voltage drop. The source must have enough voltage available to drive the total load. Use the equipment’s wiring diagram to establish the correct signal reference; connector compatibility alone does not establish electrical compatibility.

Conversion, buffering, filtering and isolation

Range conversion changes the relationship between input and output. Examples include 0–5 V to 0–10 V, 1–5 V to 0–10 V and bipolar voltage ranges. Some mappings require both gain and offset adjustment, rather than amplification alone.

Buffering reduces the load placed on the signal source and provides an output suited to the receiver. Filtering can reduce unwanted signal components, including some interference associated with nearby variable frequency drives. A smoother reading may also respond more slowly. Choose the filter setting for the process dynamics, especially when the signal is used for control.

Galvanic isolation separates signal circuits without a direct conductive connection across the isolation barrier. It can interrupt ground-loop current caused by different reference potentials. An isolator may accept 4–20 mA and deliver 4–20 mA: isolation does not require a change of range. Check whether the specified barrier separates input, output and power supply as your application requires.

Sensor conditioning is another distinct task. A bare Pt100 element or load cell does not provide a ready-made 0–10 V output. It needs a transmitter with the appropriate sensor input. Understanding the difference between an RTD and a thermocouple helps avoid choosing the wrong temperature interface.

Analog terminals can hide digital processing

An analog-input, analog-output device may contain an ADC, a processor and a DAC. Its terminal signals describe the interface, not the entire internal circuit. Assess conversion accuracy, temperature drift and response time; where digital processing is used, resolution is relevant too. An additional conversion stage contributes its own error to the measurement chain.

A practical commissioning check

Match the interfaces first. Confirm current or voltage, the exact range and polarity. Read the electrical specifications for the analog I/O, rather than relying on its general label. For a current loop, identify which device supplies loop power and follow the manufacturer’s active/passive connection diagram.

Check operation under load. Verify the permitted load for a current output and the required receiver impedance for a voltage output. Also establish the response to a disconnected sensor or an out-of-range input. The resulting output can affect a pressure PID loop or temperature control loop, so fault behaviour belongs in the commissioning plan.

Test the bottom, midpoint and top of the range with the actual receiver connected. Compare the electrical output with the displayed engineering value. A correct midpoint does not prove that both endpoints are correct. This simple check helps distinguish wiring, scaling and conversion errors before the system enters normal service.

Where analog modulation fits

In communications, analog-to-analog conversion can also mean placing information on a carrier. AM varies carrier amplitude; FM varies instantaneous frequency; PM varies phase. These descriptions identify the controlled carrier property. They do not mean phase remains fixed during FM or that instantaneous frequency can never change during PM.

Radio modulation solves a transmission problem. A 4–20 mA to 0–10 V converter solves an industrial interface problem. Keeping these applications separate makes it easier to select the right equipment.