Siemens 6ES5 942-7UH11 – S5-115H CPU 942H Redundant-System Processor

Siemens 6ES5 942-7UH11 is the CPU 942H central processing unit for the S5-115H high-availability system in the SIMATIC S5 family. Used in subunits A and B, this S5 CPU executes the user program and participates in synchronization, data comparison and fault management. An S5-115H requires two CPU 942H units of the same version.

Redundancy here involves two working controller subunits connected through a high-speed parallel interface and running the same application program. Assess the rack arrangement, power supplies and I/O configuration together. Switchover behaviour depends on the correct H-system configuration.

H-system connection and version matching

The Siemens manual specifies checking the system software version through the PG’s SYSPAR function. Record this version as well as the complete order number when selecting a replacement. The operating system and application program must match in both subunits.

Check the roles of interface modules such as IM 304-3UB11 and IM 324-3UR11 against the actual central-controller and expansion arrangement. Distinguish the CPU-to-CPU parallel link from the I/O expansion connections. Compare cables and connectors with the wiring drawings and module labels.

Internal memory and 375 submodules

The exact 6ES5 942-7UH11 technical table lists 5120 statements of internal memory. With a statement usually occupying two bytes, this corresponds to the 10 KB memory class. Do not treat the entire capacity as free application space. Check available memory through the PG, accounting for H-system data and loaded blocks.

The CPU has a 375 memory-submodule receptacle. The technical table specifies up to 16,384 statements for compatible RAM or EPROM submodules and 8,192 statements for EEPROM. Match the memory submodule type, capacity and contents to the existing H project.

STEP 5 program and processing resources

CPU 942H executes cyclic, time-controlled and interrupt-driven programs in the STEP 5 programming environment. COM 115H is used for H-system configuration. Preserve the programming software, H parameters and project files together.

The CPU provides 2048 flag bits, 128 timers and 128 counters. The technical table specifies approximately 1.6 µs per binary operation. The complete H-system cycle also depends on synchronization, testing and I/O configuration. An individual instruction time is not the overall machine response time.

Serial connection, I/O and 942-family differences

The TTY serial interface supports a PG or OP connection and, with the appropriate configuration, SINEC L1. Check the assigned port function and cable when assessing communication hardware. Verify the single-channel, redundant or switched arrangement of digital inputs, digital outputs and analog modules against the project.

6ES5 942-7UA11 and 6ES5 942-7UB11 belong to the S5-115U family; 6ES5 942-7UF15 belongs to the S5-115F family. 7UH11 identifies CPU 942H for the S5-115H. A similar 942 designation does not establish compliance with the H-system’s functional and version requirements.

Editor’s Note

When buying a used Siemens CPU, verify the 942-7UH11 label and read the existing partner CPU’s version with SYSPAR. Match the system software versions on both sides as well as the hardware identification.

Before maintenance, back up both subunits’ programs, data blocks and COM 115H parameters. Label the memory submodules A and B and photograph them. Confirm that the available project represents the current installation.

Check the standby subunit separately while the machine is running. Continued machine operation alone does not prove healthy redundancy. The S5 system may be operating on one subunit; inspect the status indications and H diagnostics together.

Investigate parallel-link connectors, cables, battery condition and supplies before replacing the CPU. Distinguish the CPU link from I/O expansion wiring. Follow the S5-115H manual’s sequence for removal, insertion and reintegration in a running H system.

After replacement, verify diagnostics, version matching and redundant operation through the PG. Perform any switchover test under suitable controlled plant conditions. Record A/B identification, versions, work completed and backup filenames.

OtomasyonAVM resources

+ 6ES5 942-7UH11 model page · Siemens S5 second-hand models · S5-115 series PDF files · S5 memory cards.

Related topics

+ 6ES5 942-7UA11 · 6ES5 942-7UB11 · 6ES5 942-7UF12 · 6ES5 942-7UF15. These links compare different functions within the 942 family; they are not direct replacements for CPU 942H.

Browse SIMATIC S5

+ SIMATIC S5 CPU models · S5 racks · S5 power supplies · S5 interface modules · Siemens second-hand main page.

Siemens and external references

+ Siemens S5-115H system manual, English. 6ES5 998-0UH21 / EWA 4NEB 811 6111-02b; printed page 1-2: redundant structure; 2-14: two CPUs of the same version and SYSPAR verification; 17-12: exact 6ES5 942-7UH11 technical table.