6ES5 470-4UC11
Siemens 6ES5 470-4UC11 — 8-Channel 1–5 V / 4–20 mA Analog Output Module
Siemens 6ES5 470-4UC11 is an eight-channel, galvanically isolated analog output module for the SIMATIC S5 U peripheral range. Each channel provides parallel 1–5 V and 4–20 mA outputs driven by the same command. These are eight control channels, rather than sixteen independent channels. Applications include suitable U peripheral configurations in S5-135U, S5-150U and S5-155U systems.
The module uses digital-to-analog conversion to turn a PLC command into an analog signal. Typical applications include a drive speed reference or proportional valve command, provided the receiving input is configured for the selected signal range.
An analog input acquires measurements; this module sends commands to field equipment. This distinction matters when selecting analog I/O. At the bottom of its nominal range, a zero command produces 1 V or 4 mA.
Output ranges and load limits
The voltage output requires a load resistance of at least 3.3 kΩ. The total load on the current output must be no greater than 300 Ω. When comparing 0–10 V and 4–20 mA signals, remember that this module’s voltage range is 1–5 V. The specified delay from data transfer to analog output is 1 ms maximum.
Power, connector and sense wiring
The analog section requires 24 V DC; the digital section receives 5 V from the system bus. The F+ / F− enable input requires 24 V. Front connector assignments include 1: F+, 2: F−, 3: L+, 21: L− and 42: MANA.
When checking the cables and connector, channel 0 uses 4: QV0, 5: S+0, 6: S−0 and 7: QI0. The eight channels share MANA as their analog reference. Group isolation does not provide individual isolation between channels. Treat protective grounding and the analog reference as separate wiring functions.
For a current-only channel, jumper S+ to QV and S− to MANA at the front connector. For voltage outputs using remote sensing, connect the sense leads at the load as shown in the manual’s four-wire arrangement.
Addressing and command scaling
Each channel occupies one word, giving 16 bytes for the complete module. The address switch must agree with the peripheral address used in the PLC program. During troubleshooting, account for the 12-bit two’s complement value, left-justified within the output word.
Nominal commands of 0 / 512 / 1024 units correspond to 1 / 3 / 5 V and 4 / 12 / 20 mA. With the lower four bits set to zero, the raw words are 0000h / 2000h / 4000h, or 0 / 8192 / 16384 in decimal. Distinguish an engineering value used by the application from the raw word transferred to the module.
System compatibility and model selection
Check the existing S5 rack, interface arrangement, address switch and front connector together. Review the Siemens S5 system architecture before treating a module that fits mechanically as a compatible replacement.
6ES5 470-4UA11 provides ±10 V / 0–20 mA, while 6ES5 470-4UB11 provides ±10 V. The 4UC11 uses different 1–5 V / 4–20 mA scaling. When comparing it with 6ES5 470-4UC12, check the complete order number, hardware version and system documentation.
Editor’s note
Do not mistake 4 mA for a fault. A nominal zero command calls for 4 mA and 1 V. Those readings alone do not indicate a defective module when the machine display shows zero.
Photograph the sense jumpers. If jumpers disappear from a current-only channel during connector work, investigate the wiring before condemning the conversion circuitry.
Measure all eight channels. Record low, midpoint and full-range readings separately. One working channel is insufficient evidence that the remaining seven are healthy.
Trace the MANA connection. A broken or incorrect common reference can affect several channels. Compare readings at the module terminals with those at the receiving input.
Inspect the label and connector together when buying used equipment. Confirm the full order number, hardware version, connector condition and channel test results before selecting a module described merely as an “S5 470”.
OtomasyonAVM resources and PDFs
+ About Siemens S5 PLC — system overview
+ S5 analog modules — input and output cards
+ SIMATIC S5 PDF archive — our general manual index
Related topics
+ 6ES5 470-4UC12 — another 4UC revision
+ 6ES5 470-4UC13 — revision comparison
+ 6ES5 470-4UA11 — different voltage and current ranges
Browse SIMATIC S5
+ Siemens second-hand equipment
Siemens and external references
+ Siemens U Periphery — 4UC11 specifications and connector, pp. 5-24–5-25 (English)
+ Siemens U Periphery — output scaling, p. 3-10 (English)
+ Siemens 6ES5470-4UC11 product sheet — third-party archive copy (English)