6ES5 318-8MB13
Siemens 6ES5 318-8MB13 — ET 200U IM 318-B PROFIBUS-DP Slave Interface
6ES5 318-8MB13 is the IM 318-B slave interface connecting an ET 200U station to PROFIBUS-DP within the Siemens ET 200 range. It belongs to the SIMATIC S5 hardware family. The front panel provides a 24 V DC supply connection, a 9-pin D-sub communications socket, a RUN/STOP switch and RUN, BUS-FAULT and IM-FAULT indicators. Within the S5 interface module range, its purpose is to exchange local I/O data with the PROFIBUS-DP master.
ET 200U uses suitable S5-100U I/O modules as a distributed station. When selecting a board from the S5-90/110 module group, check the module types supported by ET 200U and the configured station as well as physical fit. The master PLC executes the control program; the IM 318-B handles the station’s network data exchange.
Supply and local I/O connection
Check the 24 V DC input supply separately from the field supplies of the connected I/O modules. The interface connects to the local I/O bus through its rear bus-unit connector. Inspect local connection components such as the 6ES5 700-8MA11 bus unit, the supply terminals and the seating of the interconnected bus units.
The 9-pin D-sub socket is the PROFIBUS connection. Use a suitable Siemens PROFIBUS connector and PROFIBUS network cable. When reviewing S5 cables and connectors, distinguish the network connection from a programmer cable.
Bus termination and shielding
The two physical ends of a PROFIBUS segment require suitable termination. Establish the station’s position on the segment before changing its connector’s termination switch. Cable-screen connection and grounding affect communications reliability, particularly in cabinets containing drives and contactors.
Observe whether disconnecting a connector also removes stations farther along the line. One loose connection can affect several slaves. When investigating PROFIBUS connection faults, check cable routing, shielding, termination and supply together.
Station address and master configuration
The station address, selected communications mode and master hardware configuration must agree. Before tracing addresses in the PLC program, check the slave definition in the configuration software and the physical I/O module order. In S5 applications using an IM 308-B master, the master and IM 318-B slave entries represent different functions.
During troubleshooting, record the RUN, BUS-FAULT and IM-FAULT indications separately. A lit RUN indicator does not establish that the I/O map is correct. If the station joins the network but data does not appear at the expected addresses, check module order, module definitions and master addressing.
8MB11, 8MB12 and other IM 318 versions
The 6ES5 318-8MB11 and 6ES5 318-8MB12 differ in protocol support and switch functions. Before copying an older module’s switch positions to an 8MB13, compare the complete order code, the setting chart on the housing and the master configuration. The shared IM 318-B designation does not establish identical switch meanings across all versions.
The 6ES5 318-8MC12 and 6ES5 318-8MA12 are also distinct order numbers. Identify more than the general “318 module” description when selecting a spare. In the ET 200 system architecture, assess the station head, network protocol, bus units and connected modules together.
Editor’s note
Before removing the module, photograph the label, address switches and RUN/STOP position. On a station that has worked for years, those settings are worth preserving. A simple record is more dependable than memory and can save a long search during replacement.
A BUS-FAULT indication is a reason to check the master, station address and connector before ordering another interface. If IM-FAULT is present, inspect the local module arrangement too. Knowing which indicator lights under which conditions is a much better starting point than a general report of “no communications.”
Measure the 24 V supply at the interface terminals as well as at the power supply. A loose connection or voltage drop can remain after a board swap. Establish the supply condition and inspect the bus units before deciding which component needs replacing.
If the station is online but the machine behaves incorrectly, compare the I/O module order one position at a time. A module may have moved or its configured definition may have changed. Establishing communications and getting the correct data at the correct address are separate checks.
When buying an 8MB13 from the used Siemens equipment range, inspect the 9-pin socket, rear bus connector, terminals and switches closely. Where possible, request a working data-exchange test with a master and several I/O modules. A photograph of the RUN indicator alone gives limited evidence of the station head’s condition.
OtomasyonAVM resources and PDFs
+ S5 interface modules · Siemens ET 200 range · PROFIBUS connectors.
+ OtomasyonAVM Siemens ET 200 manuals · Shared Siemens S5 PDF archive. Use the ET 200U Distributed I/O Station manual, EWA 4NEB 812 6087-02b, for family-level installation, I/O and diagnostic guidance. This edition covers 8MB11/8MB12 versions; the exact 8MB13 identity is established by the Siemens data sheet below.
Related topics
+ IM 318-B 8MB11 · IM 318-B 8MB12 · IM 318 8MC12 · IM 308-B master · 700-8MA11 bus unit.
Browse SIMATIC S5
+ S5 interface modules · Siemens ET 200 · S5-90/110 modules · Siemens S5 PLCs · Siemens second-hand equipment.