6ES5 304-3UB11

Siemens 6ES5 304-3UB11 — IM 304 Expansion Interface Module

The Siemens 6ES5 304-3UB11 is an IM 304 interface module fitted in the central controller of a SIMATIC S5 system. It provides a symmetrical parallel bus connection between the S5 central controller and remote expansion racks. This S5 interface module operates with the 6ES5 314-3UA11 / IM 314 at the expansion unit.

The module has two branches, X3 and X4. Each branch supports up to four expansion units equipped with IM 314 interfaces. With 721 connecting cable, the permitted total length from the central controller to the final expansion unit is 600 m per branch; this allowance does not apply separately to each cable segment.

Expansion racks and the IM 306 requirement

The IM 304/314 arrangement supports EU 183U and EU 185U expansion units. Connections through ER 701-2 and ER 701-3 racks additionally require an IM 306 adapter module. Review the rack type, module placement and address allocation against the installed system.

721 cable and branch termination

The connection uses the 6ES5 721-0xxxx cable family. Examples include the 721-0BB00 — 1 m, 721-0BB60 — 1.6 m and 721-0BF00 — 5 m. When selecting S5 cables, add the lengths of every segment on each branch.

The last IM 314 on each branch requires a 6ES5 760-1AA11 terminating plug. The 6ES5 760-0AB11 belongs to the IM 312 connection arrangement and should not be selected as the terminator for a standard IM 304/314 branch.

X11 length setting and branch selection

Set jumper X11 according to the total cable length of the longer X3 or X4 branch. Siemens specifies 0–100 m: 3–4; 100–250 m: 5–6; 250–450 m: 7–8; 450–600 m: 9–10. The manual's special 10 m setting is not for a standard IM 304/314 connection.

X22 controls branch X3; X21 controls branch X4. Set a used branch to ON and a branch without an expansion unit to OFF. Leave other jumpers and switches unchanged except where the applicable system manual requires a different setting.

Fault checks and other connection arrangements

A FAULT LED alone does not establish a defective module. Loss of expansion-unit power, a broken cable, missing termination, an incorrect S3 setting or a powered unit connected to a disabled branch can also cause it. During PLC debugging, identify the affected branch and the last working rack first.

Check grounding and cable-shield connections together when assessing noise immunity. The IM 310 / 6ES5 310-3AB11 belongs to a different connection arrangement; similar appearance or connectors do not establish interchangeability with the IM 304/314. Change modules and jumper settings with system power switched off.

Editor's note

Before removing the old board, take a clear photograph of its label and jumper positions. A sound replacement can still leave the machine waiting if its settings differ.

Give the module a fair chance when FAULT lights up. Check the remote rack's supply, cable and terminating plug first; sometimes a loose connection is the whole problem.

Keep the plug at the end of the branch safe. It is easy to mistake it for a cover, but the correct terminator on the final IM 314 is part of the working system.

For the distance setting, measuring only the first cable is not enough. Add every segment on the longest branch before checking X11. A small note now can save time at the next service.

Where possible, test a used board's X3 and X4 branches separately with a working IM 314. Keep the result with the S5 system information; a short, recorded functional test tells you more than illuminated LEDs.

OtomasyonAVM resources and PDFs

+ Start with the OtomasyonAVM S5 PDF archive.

+ The S5-115H system manual — English provides additional information for H systems. Distinguish their special connections and jumper settings from the standard IM 304/314 arrangement.

Related topics

+ IM 314 — 314-3UA11 · IM 306 — 306-7LA11 · 760-1AA11 terminating plug.

+ ER 701-2 rack · ER 701-3 rack · S5 cable types.

Browse SIMATIC S5

+ S5 interface modules · SIMATIC S5 central controllers · Siemens S5 main page.

+ Used Siemens automation equipment.

Siemens and external references

+ Siemens S5-135U/155U System Manual — C79000-G8576-C199-07: pages 2-5 and 7-14–7-17; module pairing, branch limits, termination and X11/X21/X22 settings.

+ Siemens U Periphery — IM 304/314, C79000-B8576-C716-02: PDF pages 110–126; connection, installation and fault finding. This is an English compilation.

+ Siemens 6ES5 304-3UB11 data sheet — April 28, 2018: exact order number and central-controller IM 304 description; an externally hosted copy of the manufacturer's document.