6ES5 948-3UR22
Siemens 6ES5 948-3UR22 — S5-155H CPU 948R-2, 1664 Kbytes RAM
Siemens 6ES5 948-3UR22 is a CPU 948R-2 central processing unit for SIMATIC S5-155H. Siemens ST 50 lists the exact part number with 1664 Kbytes of internal user RAM. This CPU in the Siemens S5 family processes the program and data in installations requiring high availability.
An S5-155H arrangement has a CPU 948R in each of its two subunits. System software handles synchronization, self-testing and continued operation after a fault. Replacement selection must consider both CPUs’ operating-system versions and the installed rack arrangement, alongside RAM capacity.
1664 Kbytes of RAM and Flash EPROM card
Internal working memory and the removable non-volatile memory card are separate resources. The CPU 948R-2 has 1664 Kbytes of RAM for user program and data. Match the application size and exact S5 memory-card part number when selecting storage.
Siemens’ corresponding ordering table lists 6ES5 374-2KH21 — 256 Kbytes, 6ES5 374-2KK21 — 1 Mbyte and 6ES5 374-2KL21 — 2 Mbytes. These Flash EPROM cards are not RAM expansions. The manual explains that an overall reset copies card contents into internal RAM; verify the stored program before carrying out that operation.
Two-slot installation, dimensions and supply
The CPU occupies two slots in the central rack. The S5-155H manual gives dimensions of 40.6 × 233.4 × 160 mm and identifies the UR22 weight as approximately 1 kg. When selecting a 135U/155U central rack, assess CPU placement, other modules and cooling together.
The CPU uses the system’s internal 5 V supply. Siemens ST 50 specifies maximum power dissipation of 20 W for CPU 948R. The rack’s mains or 24 V DC input is not a voltage to apply directly to the CPU. Check the installed power supply and fan arrangement against the system documentation.
Programmer connection and programming
The integral serial programmer connection is TTY; the manual specifies 9600 bps for this port. Select a matching programmer interface and PG cable for the electrical connection. A familiar connector shape does not make the port MPI, Ethernet or ordinary RS-232.
The CPU is programmed in STEP 5, with SCL also available in a suitable software arrangement. Alongside programming, COM 155H supports H-system configuration and diagnostics. Preserve the program backup together with the H-configuration records.
Redundant operation and diagnostics
During fault-finding, examine both subunits, synchronization connections and diagnostic records. One CPU executing the program does not by itself establish full redundant operation. Also assess whether the digital inputs and digital outputs use single-sided, switched or redundant arrangements.
Siemens’ replacement instructions require the same operating-system version in both CPUs; if versions differ, the other CPU may also need replacement. During Siemens S5 maintenance, record the replacement’s label and software version. For replacement without interrupting operation, follow the sequence in manual Section 9.6.
Differences from 3UR21, 3UR23 and standard CPU 948
6ES5 948-3UR21, 6ES5 948-3UR23 and 6ES5 948-3UR13 are other CPU 948R part numbers. Compare memory, hardware and operating-system details before treating them as direct substitutes. Do not transfer a later hardware revision’s weight or electrical ratings to UR22.
6ES5 948-3UA22 identifies a standard CPU 948 for S5-155U. The UA and UR suffixes matter when selecting a spare. For a used unit, inspect the full 6ES5 948-3UR22 label, revision, memory-card receptacle, PG connection and rear connector, and record the H-system arrangement used for testing.
Editor’s note
Check both the replacement CPU and its installed partner, including operating-system versions. A shared 948R name does not establish that every pairing will work correctly.
If the H system is operating on one CPU, inspect both subunits’ diagnostics and connection status before disturbing the working side. A link fault can otherwise lead to unnecessary CPU replacement.
Identify the machine and program version stored on the Flash card before insertion. A populated card is not proof of the correct program; preserve the running RAM program’s backup.
The two PCBs form a connected assembly. Do not separate them or force aged connectors. Bent contacts or damaged retainers can introduce a second fault during maintenance.
Complete the test by checking standby reintegration and a controlled takeover in suitable conditions. A RUN indication alone is not a complete H-system acceptance test; preserve diagnostics and results.
OtomasyonAVM resources and PDFs
Browse the 6ES5 948-3UR22 model page, SIMATIC S5 CPU family and used Siemens equipment. General documents are collected in the shared Siemens S5 PDF archive. The exact-code catalogue and CPU 948R/RL system manual are linked below.
Related topics
+ 6ES5 948-3UR21 — another CPU 948R code; verify version matching.
+ 6ES5 948-3UR23 — CPU 948R with a different hardware revision.
+ 6ES5 948-3UR13 — another CPU 948R memory/version option.
+ 6ES5 948-3UA22 — standard CPU 948 for S5-155U.
+ 6ES5 374-2KL21 — catalogued 2 Mbyte Flash EPROM card.