6ES5 948-3UR13

Siemens 6ES5 948-3UR13 CPU 948R — S5-155H, 640 KB RAM

Siemens 6ES5 948-3UR13 is a CPU 948R central processing unit with 640 KB RAM for the S5-155H in the SIMATIC S5 family. This S5 CPU serves the high-availability H system. The Siemens data sheet for the exact 3UR13 order number confirms its memory capacity.

Check the UR13 suffix, hardware revision and existing H-system project together. Similar codes such as 948-3UA13 and 948-3UR23 must be identified separately. The CPU 948 family name or a physical fit in the rack is insufficient for selecting a replacement.

Internal RAM and Flash memory cards

Record the 640 KB internal RAM separately from the capacity of the installed memory card. For cards such as 374-2KH21 or 374-2KK21, check the complete code, contents and application with the installed CPU. A fitted card does not establish that its program is current.

Prepare a recovery record containing the STEP 5 program, data blocks and COM 155H project data. A RAM or CPU-version upgrade must be assessed against the manual’s COM 155H upgrade procedure; inserting another CPU and attempting a normal start does not complete that process.

SI1 connection and unused SI2 slot

SI1 is a 15-pin serial programmer connection; the manual specifies 9600 bit/s. Select the programming interface and connecting cable accordingly. The SI2 interface-submodule slot is not used in the S5-155H application. A visible slot does not establish a second operational communications channel.

Master–standby operation and the parallel link

A redundant S5-155H arrangement uses master and standby central controllers. The documented inter-controller parallel link uses IM 304 and IM 324R. Check the 304-3UB11, 324-3UR11, connecting equipment and project assignment. Distinguish this link from switched-I/O connections using an IM 314R.

UR13 supply and mechanical specifications

Siemens specifies 5 V ±5% and 0.5 A typical in the UR13 column. Dimensions are 40.6 × 233.4 × 160 mm, with an approximate weight of 0.6 kg. The dimension order is width × height × depth. Use the correct revision data when checking rack installation and power-supply loading.

Front panel and fault assessment

The UR13 has no INIT LED. Do not treat its absence as a missing component when comparing the unit with an older drawing. Record RUN, STOP, SYS FAULT and the fault indicators together. Investigate QVZ, ADF and ZYK in relation to peripheral response, addressing and cycle time respectively.

Test the digital inputs, digital outputs and communications equipment against the actual project. A CPU reaching RUN on its own does not verify master–standby switchover or peripheral behaviour.

For used equipment in an older Siemens S5 system, state the rack and partner CPU used for acceptance testing. List included supporting equipment, memory cards and connection parts separately. Distinguish a single-CPU bench test from a complete H-system test.

Editor’s note

Ask for a readable 948-3UR13 label and revision marking. A similar front panel can belong to a UA CPU or another UR memory variant. Photographs should also show the memory-card slot and lower connections.

Reaching RUN independently is an initial test. For a redundant installation, test the partner connection, standby activation and switchover behaviour separately. State clearly when those functions have not been tested.

Do not reject a UR13 because an INIT lamp appears to be missing. This revision has no INIT LED. Account for the revision difference when comparing an older manual illustration with the actual module.

An empty SI2 slot is not a reason to order an interface submodule for S5-155H operation. First establish whether the problem concerns the SI1 cable, parallel link or project configuration.

A STOP or fault indication should not automatically lead to an overall reset. Preserve the program, COM 155H project and diagnostic records first, then isolate CPU, link and peripheral faults in sequence.

OtomasyonAVM resources and PDFs

+ 6ES5 948-3UR13 product and information page, IM 324R and IM 314R.

+ OtomasyonAVM shared SIMATIC S5 PDF archive. Use S5-155H 948R/RL documentation for this CPU; an S5-115H or standard S5-155U manual alone does not document this model’s H functions.

Related topics

+ S5 memory cards, PLC programming, S5 interfaces and S5 racks.

Browse SIMATIC S5

S5 CPU models  |  Siemens S5 homepage  |  S5 function modules  |  Siemens second-hand homepage

Siemens and external references

+ Siemens 6ES5948-3UR13 data sheet, English — third-party archive copy. Dated 16 February 2020: exact code, CPU 948R, S5-155H and 640 KB RAM.

+ Siemens S5-155H CPU 948R/948RL Manual, Volume 1/2, English. 6ES5 998-4SR21, Edition 06; Chapter 3 covers hardware, Chapter 6 connections and Section 9.7 CPU upgrades.

+ Siemens CPU 948R Programming Guide, Volume 2, German. C79000-B8500-C136-05; pages 4-4–4-6 cover the front panel and absence of the INIT LED on UR13.