Siemens 6ES5 948-3UR23 – S5-155H CPU 948R, 1600 KB RAM
Siemens 6ES5 948-3UR23 is a CPU 948R central processing unit for SIMATIC S5-155H. Siemens' exact-order-number data sheet specifies 1600 KB RAM. This CPU executes the user program and participates in H-system synchronization within a redundant Siemens S5 PLC installation.
Keep the memory documents distinct: the older CPU 948R/948RL family manual lists 1664 Kbyte for the 948R-2, while the 3UR23-specific sheet states 1600 KB. This page follows the exact-order-number sheet. A Flash EPROM memory card is a separate program/data storage medium; its capacity must not be added to the internal RAM figure as working memory.
Redundant operation and CPU matching
A correctly configured S5-155H executes the same user program in two subunits operating as master and standby. The manual describes checks on RAM capacity, operating-system code and memory-card checksum when activating the standby. Installing a second CPU alone does not establish redundant operation.
Assess the installed IM 324R, interface modules and other auxiliary equipment against the plant's H configuration. When replacing a CPU, check both sides' hardware labels, operating systems and project records together.
Programming connection and the SI2 limitation
The front panel provides a 15-pin SI1 programmer connection; the family table specifies 9600 bit/s for the serial PG port. Use the appropriate S5 programming cable and communication arrangement. The SI2 interface-submodule receptacle is marked as unused with S5-155H. Two connector areas must not be interpreted as two available PG ports.
The user program is handled in STEP 5, with the H configuration handled through COM 155H. Alongside the PLC program backup, retain the H configuration, relevant data blocks and memory-card contents. An overall reset reinitializes RAM and copies the memory-card contents to RAM where a card is present. Obtain backups before beginning fault investigation.
Timers, counters and I/O structure
The family specification lists 256 timers and 256 counters. Digital inputs, digital outputs and analog I/O use separate modules. Channel capacity and redundancy behaviour depend on the installed modules and H-system I/O arrangement; these are not onboard field connections on the CPU.
Supply, consumption and physical installation
Siemens' UR13 / UR23 / UR53 column specifies a 5 V ±5% supply and typical 0.5 A consumption. The older-version column's 3.6 A figure must not be assigned to UR23. Include CPU consumption when assessing the rack power budget with supplies such as 6ES5 955-7NC11 or 6ES5 955-7NC12.
Dimensions are 40.6 × 233.4 × 160 mm, and the UR23 group's approximate weight is 0.6 kg. The manual specifies two rack slots and describes installation in slot 11 for the illustrated H arrangement. This is not an I/O address. The table lists IP00 protection and an operating range of 0–55 °C; preserve the required rack cooling and installation conditions.
Differences from other 948 order numbers
6ES5 948-3UR13, 6ES5 948-3UR21 and 6ES5 948-3UR22 are different order numbers in the 948R family. Check capacity, consumption and operating-system compatibility individually. 6ES5 948-3UA23 belongs to the standard UA-coded 948 family. Do not overlook the UA/UR distinction when selecting a spare. These models should not be presented as automatically interchangeable.
Editor's note
First record which subunit is master and which is standby. One CPU entering RUN is only part of the check; verify that the installation has actually returned to redundant operation.
With STOP and SYS FAULT off, a steady RUN indicator can identify the master and a flashing RUN indicator the standby. Do not condemn a standby merely because its green LED flashes; read the complete indication pattern.
Do not begin with an overall reset. Preserve the working side's program, data blocks, H configuration and memory-card contents before making changes.
During fault finding, collect ISTACK and H-system error records. Distinguish CPU faults from connection, supply or configuration problems before relying on a board replacement.
The manual requires the two connected CPU boards to remain together and factory jumpers to remain unchanged. Remove or insert the CPU only with power disconnected from the relevant subunit, following the installation's maintenance plan.
For used Siemens equipment, request the complete 948-3UR23 label, hardware revision, programmer-port test and a suitable H-system test record. “It goes into RUN” does not verify operating-system matching or successful standby activation.
OtomasyonAVM resources and manual
Browse About Siemens S5 PLC, S5 CPUs, memory cards and interface modules for related equipment. The exact-order-number sheet and S5-155H system manual are linked separately below.
Related models
+ 6ES5 948-3UR13: a different capacity version in the CPU 948R family.
+ 6ES5 948-3UR21: another CPU 948R order-number version.
+ 6ES5 948-3UR22: check consumption and system version separately.
+ 6ES5 948-3UA23: standard UA-coded CPU; not a direct H-system substitute.
Browse S5 equipment
Siemens S5 PLC · CPUs · Memory · Interfaces · Cables · Used Siemens equipment
Manufacturer documents and external references
+ Siemens Data Sheet – 6ES5948-3UR23, English: archive copy of Siemens' product sheet. Confirms the exact order number, CPU 948R / S5-155H designation and 1600 KB RAM.
+ Siemens S5-155H CPU 948R/948RL Manual – C79000-G8576-C197, Volume 1, English: section 2.2 covers matching; sections 3.1–3.3 cover installation, indications and specifications. PDF pages 54–63; the UR23 current column is on page 62 and weight column on page 63.